Fläkt Woods
8061 GB 2009.05
7
Specifications are subject to alteration without further notice.
RoomMaster ABR-2
COMMISSIONING
Setting temperature regulation and desired temperature value
The setting ranges are shown after the current window. The default value is underlined.
1. Press the
keys at the same time for approx. 5 seconds. Window 10 is displayed
2. Press the
key. Window 11 is displayed
3. Press the
key 3 times until window 14 is displayed
Room regulation
- Supply air regulation
4. Select
Room regulation
or
Supply air regulation
with
, and confirm with
(cursor stops flashing)
5. Press the
key. Window 15 is displayed
6. Press the
key. Window 15a is displayed
10.0 <–> 30.0ºC
20.0ºC
7. Change to the desired value with
, and confirm with
(cursor stops flashing)
8. Press the
key. Window 15b is displayed
15.0 <–> 25.0ºC
19.0ºC
9. Change to the desired value with
, and confirm with
(cursor stops flashing)
10. Press the
key. Window 15c is displayed
10.0 <–> 30.0ºC
19.0ºC
11. Change to the desired value with
and confirm with
(cursor stops flashing)
12. Press the
key 3 times to return to the operating window.
13. The unit will now operate with the new set values.
10
Set desired value
11 Standard flow
exhaust air: 200 l/s
14 Temperature
regulation: Room reg.
15b Min supp.air.tem.
(Room reg.) 19,0oC
15a Room temp.
(room.reg. 19oC
15
Set temperature
15c Suppl. air temp.
(suppl air reg)19,0oC
Procedure - setting
Содержание RoomMaster ABR-2