Fläkt Woods
8061 GB 2009.05
13
Specifications are subject to alteration without further notice.
RoomMaster ABR-2
COMMISSIONING
Calibration of unit (Window 71b)
1. Press the
keys at the same time for approx. 5 seconds. Window 10 is displayed
2. Press the
key (6 times) until window 70 is displayed
3. Press the
key. Window 71 is displayed
4. Press the
key. Window 71a is displayed
5. Press the
key, once. Window 71b is displayed
6. Press the
key Calibration is activated
Calibration is complete when the ‘calibration‘ text disappears from the operating window.
The time required for calibration is approx. 5 minutes.
Self-test of unit (Window 71a)
1. Press the
keys at the same time for approx. 5 seconds. Window 10 is displayed
2. Press the
key (6 times) until window 70 is displayed
3. Press the
key. Window 71 is displayed
4. Press the
key. Window 71a is displayed
5. Press the
key. Self-test is activated
6. The operating windows
and
will be displayed during the self-test.
The self-test is complete when the ‘self-test‘ and ‘filter test‘ text disappears.
The time required for the self-test is approx. 20 minutes.
10
Set desired value
70 Test /Default value
/ Configuration
71a Self-test
71 Test /Calibration
/ Default value
71b Calibration
10
Set desired value
70 Test /Default value
/ Configuration
71 Test /Calibration
/ Default value
71a Self-test
Automatic
Filter test
Automatic
Self-test
Procedure - setting