background image

13

12

SPECIALIZED

HEALTHY

AIR SOLUTIONS

SPECIALIZED

HEALTHY

AIR SOLUTIONS

OWNER’S MANUAL

OWNER’S MANUAL

ASCENDANT

ASCENDANT

SPECIALIZED

HEALTHY

AIR SOLUTIONS

OWNER’S MANUAL

Heating and/or cooling coils can be ordered with the 
energy recovery system. All necessary heating and/
or cooling coils have been installed at the FläktGroup 
SEMCO factory. However, before operating them, a brief 
pre-startup inspection is recommended. 

INSPECTION

  •

 

  Inspect all pipe connections to verify they are tight  

      and that no damage has occurred during transit or  
      on-site installation.

  

   

STEAM COILS

 – Be sure that the unit is level so the  

      coils inside the casing slope toward the header.

  

• 

  

HOT WATER COILS

 – Check the freeze protection  

      thermostat for proper operation so that it will  
      function to prevent freeze-ups.

OPERATION

  

  

STEAM COILS

 – Non-freeze steam coils are  

     designed to operate steam pressures up to, and  
     including, 150 psig and temperatures to 350°F. 

  

  During initial operation, make sure that  

     condensate flows back to the headers. Check for  
     leaks. 

  

  

HOT WATER COILS

 - are designed to operate at  

     pressures to 150 psig, and temperatures to  
     366°F. Check for leaks during initial operation.

  •  

COOLING COILS 

-

 

 are designed to withstand  

     pressures to 200 psig.  During initial operation,  
     check for leaks (See 

FIGURE 25

).

COILS

FIGURE 25.

 

Cooling coils should be checked for leaks during 

operation.

  

3)

  The dampers are controlled by electric motors.   

       Make sure that wiring is complete.  Check the  
       wiring diagram on the motor.

  4)

  Turn on power and observe whether or not the  

      controls trigger dampers correctly. Be sure that  
      limit switches close when blades are open and  
      open when blades are closed.

AIR FILTERS

Air filters for the energy recovery system are boxed, 
tagged and shipped loose inside the system for field 
installation. This minimizes any risk for filter damage 
during transit. The air filters must place installed prior 
to startup or the warranty could be voided.

Throughout the operating life of the system, it will be 
necessary to replace filters as they accumulate dirt 
from the air stream.

The system is equipped with two pressure differential 
gauges. As air filters accumulate dirt, the pressure 
differential will rise.

The 

PRE-FILTER CAPACITY AND RESISTANCE TABLE

 

(

FIGURE 26

) and 

FINAL FILTER CAPACITY AND 

RESISTANCE TABLE

 (

FIGURE 27

) provide data for most 

pre-filters and final filters used in FläktGroup SEMCO 
systems. For each filter size, the pressure differential 
(resistance at capacity) using new, clean air filters in 
air streams is shown. The capacities columns define 
airflow in cubic feet per minute. For specific airflows, 
interpolating and estimating will provide adequate 
data.

SPECIALIZED

HEALTHY

AIR SOLUTIONS

OWNER’S MANUAL

FIGURE 22. 

As an option, the fans can be mounted on seismic   

arrest mounts.

      

  Rotate the impeller by hand; it should turn freely.  

         If not, check for obstructions and contact  
         FläktGroup SEMCO (see the 

BACK COVER

 for    

         contact info.).

      

  Ensure that the fan wheel and fan interior are  

         clean are free of debris.

      

  Check fan set screw for tightness; re-tighten if  

         necessary.

  

4)

  After completing inspection checks on motors and  

      fans, turn power on then off quickly. Power should  
      be on just long enough to start fan rotation.

  

5)

 If fans start rotating in the wrong direction (See  

      

ARROW ON THE BLOWER

) turn off power  

      immediately. To correct rotation, lock out power to     
      the unit feeder, and switch any two line power  
      wires. To change rotation of only an inverter driven  
      wheel and not the fans, switch any two VFD line    
      power wires.

  

6)

 Using an amp probe or amp meter, check the  

      actual operating current of the motor to make  
      sure it is not being overloaded or underpowered.  
      The operating current must not exceed the  
      nameplate current.

 

 7)

 Allow the assembly to run for about an hour. During  

      this time, listen for any unusual sounds. To correct  
      noise problems, see 

TROUBLESHOOTING

 on  

      

PAGE 19

.

OPTIONAL FAN MOUNT

DAMPERS

While they have been installed and checked at the 
FläktGroup SEMCO factory, a pre-startup inspection 
is recommended to be sure that nothing has become 
detached or damaged during shipment or on-site 
installation.

INSPECTION

  

1)

  Check blade rotation clearance. Verify that blades  

      open and close properly and rotate sufficiently.  
      If they do not, check for obstructions, broken or  
      bent blades, or loose linkage. Correct or repair as  
      necessary (See 

FIGURE 23

).

FIGURE 23.

 

Be sure that damper blades open 

and close properly and have sufficient rotation 
clearance.

  

2)

 Be sure that actuator arms and bars connecting  

      damper motors to control rods or shafts are tight.  
      (See 

FIGURE 24

).

FIGURE 24.

 

Damper actuator.

Содержание SEMCO Ascendant

Страница 1: ...OWNER S MANUAL SPECIALIZED HEALTHY AIR SOLUTIONS...

Страница 2: ...cant hybrid system Performance is optimized to deliver and control low dew point air while minimizing energy input The system is configurable as a dedicated outdoor air system DOAS or a recirculated a...

Страница 3: ...isture in the air is adsorbed by the desiccant producing dry air A modulating damper allows a portion of the supply air to bypass the wheel The adsorbed moisture is desorbed by heated air regenerating...

Страница 4: ...tions of your lifting equipment see LIFTING on PAGE 3 3 Adjoining ends of modules are covered with plywood and or plastic sheets during transport This must be removed prior to hoisting the modules in...

Страница 5: ...pop rivet to close seal end of panel Crimp roof lips after installation Install butt strap over joint caulk and screw in place butt strap not shown First Foam Panel 16 Apply caulk at high and low poi...

Страница 6: ...the following sections of this manual before proceeding 9 SPECIALIZED HEALTHY AIR SOLUTIONS OWNER S MANUAL ASCENDANT MOUNTING DETAILS CURB SUPPORT SELF FLASHING UNIT BASE SHOWING CURB SUPPORT REQUIREM...

Страница 7: ...s should be torqued to 50 ft lbs The bearing set screws should be torqued to 15 ft lbs 4 The bearing set screws should be checked periodically for tightness A bearing set screw is located on each side...

Страница 8: ...The PRE FILTER CAPACITY AND RESISTANCE TABLE FIGURE 26 and FINAL FILTER CAPACITY AND RESISTANCE TABLE FIGURE 27 provide data for most pre filters and final filters used in Fl ktGroup SEMCO systems Fo...

Страница 9: ...ms equipped with pre filter and final filter banks it is recommended that pre filter banks be changed twice as often as final filters For air filter replacement a rigid cell type filter that matches t...

Страница 10: ...f drive rated current kVA dependent 0 57 208 230 0 29 460 E2 03 Motor No Load Current 0 to E2 01 kVA dependent 0 23 208 230 11 460 Nameplate amps 40 Consult SEMCO PROGRAMMING PARAMETERS Fl ktGroup SEM...

Страница 11: ...abilities which can be useful for troubleshooting or for emergency operation For automatic operation all output switches on the controller should be to the left Manuals for the inverters and any gas f...

Страница 12: ...shaft immediately Fan operating in stall or unstable flow Make sure system is operating at design static pressure and design flow rates Noise motors Supply voltage is high or inconsistent Check suppl...

Страница 13: ...g weather resistant materials Equipment contained within the enclosure requires regular maintenance to keep the system operating smoothly You will find maintenance instructions for every component in...

Страница 14: ...and shafts for dirt and other foreign matter that would impede normal movement and prevent blades and seals from seating properly Clean as necessary Inspect seals every three months to be sure that no...

Страница 15: ...s will be supplied upon request on receipt of order SEMCO is a registered Trademark of SEMCO LLC Other trademarks and logos in this publication may be property of SEMCO LLC its subsidiaries or any of...

Отзывы: