Quantity and size of filters in standard units

WHEN TO REPLACE FILTERS

MODEL SIZE

SIZE 5

SIZE 9

SIZE 13

SIZE 18

SIZE 24

SA FILTER 

QTY AND 

SIZE

24" x 24" (4)

24" x 24" (4)

24" x 24" (6)

24" x 24" (9)

24" x 24" (12)

12" x 24" (4)

12" x 24" (3)

12" x 24" (3)

12" x 24" (4)

EA FILTER 

QTY AND 

SIZE

24" x 24" (2)

24" x 24" (2)

24" x 24" (3)

24" x 24" (6)

24" x 24" (8)

12" x 24" (2)

12" x 24" (3)

12" x 24" (3)

12" x 24" (2)

It is recommended that filters be changed when the 
pressure differential gauge reaches the final resistance 
rating illustrated in 

FIGURE 26

 and 

FIGURE 27

 (on 

PAGE 

14

). Experience with the new system may suggest 

changing filters at a slightly higher or lower reading. 
Depending upon the total volume of air required in 
the building, altering the replacement differential may 
be necessary. But waiting to change filters when the 
pressure differential reaches or approaches a higher-
than-recommended figure would mean using packed 
air filters that seriously reduce airflow.

If the system is ordered with final filters, then these will 
be located behind the pre-filters.

The procedure for removing the old filters and installing 
new ones is the same as described on 

PAGES 

5

 and 

6

.

For systems equipped with pre-filter and final filter 
banks, it is recommended that pre-filter banks be 
changed twice as often as final filters. 

For air filter replacement, a rigid, cell-type filter that 
matches the specifications shown in the 

PRE-FILTER 

AND FINAL FILTER CAPACITY AND RESISTANCE TABLES

 

is recommended.

SPECIALIZED

HEALTHY

AIR SOLUTIONS

OWNER’S MANUAL

FIGURE 26. 

Pre-filter Capacity and Resistance Data

• 

PRE-FILTER CAPACITY AND RESISTANCE DATA

FILTER 

DEPTH

NOMINAL 

SIZE 

(INCHES)

ACTUAL SIZE 

(INCHES)

CAPACITIES (CFM)

RESISTANCE AT CAPACITY 

(INCHES W.G)

WIDTH

HEIGHT

DEPTH

MEDIUM

HIGH

MEDIUM

HIGH

FINAL

4"

12x24x4

11.38

23.38

3.88

600

1,200

0.12

0.35

0.90

24x24x4

23.38

23.38

3.88

1,200

2,400

0.12

0.35

0.90

2"

12x24x2

11.38

23.38

1.88

500

1,000

0.08

0.28

0.90

12x24x2

23.38

23.38

1.88

1,000

2,000

0.08

0.28

0.90

12" FINAL FILTER CAPACITY AND RESISTANCE DATA*

FILTER MEDIA 

EFFICIENCY

NOMINAL SIZE 

(INCHES)

ACTUAL SIZE

1

 

(INCHES)

AIRFLOW CAPACITY 

(CFM)

RESISTANCE (IN.WG.)

WIDTH

HEIGHT

INITIAL

FINAL

2

60-65%

12x24

11.38

23.38

1,000

0.29

1.5

24x24

23.38

23.38

2,000

0.29

1.5

80-85%

12x24

11.38

23.38

1,000

0.50

1.5

24x24

23.38

23.38

2,000

0.50

1.5

90-95%

12x24

11.38

23.38

1,000

0.68

1.5

24x24

23.38

23.38

2,000

0.68

1.5

FIGURE 27. 

12” Final Filter Capacity & Resistance Data

*NOTES: 

1)  

Actual depth of the 12" filter is 11.50"

2)

  Maximum recommended final resistance. System design may require a lower change-out reistance.

Maximum operating temperature limit for the filters is 180ºF in continuous operation and 200ºF in intermittent operation.

 

Содержание SEMCO Ascendant

Страница 1: ...OWNER S MANUAL SPECIALIZED HEALTHY AIR SOLUTIONS...

Страница 2: ...cant hybrid system Performance is optimized to deliver and control low dew point air while minimizing energy input The system is configurable as a dedicated outdoor air system DOAS or a recirculated a...

Страница 3: ...isture in the air is adsorbed by the desiccant producing dry air A modulating damper allows a portion of the supply air to bypass the wheel The adsorbed moisture is desorbed by heated air regenerating...

Страница 4: ...tions of your lifting equipment see LIFTING on PAGE 3 3 Adjoining ends of modules are covered with plywood and or plastic sheets during transport This must be removed prior to hoisting the modules in...

Страница 5: ...pop rivet to close seal end of panel Crimp roof lips after installation Install butt strap over joint caulk and screw in place butt strap not shown First Foam Panel 16 Apply caulk at high and low poi...

Страница 6: ...the following sections of this manual before proceeding 9 SPECIALIZED HEALTHY AIR SOLUTIONS OWNER S MANUAL ASCENDANT MOUNTING DETAILS CURB SUPPORT SELF FLASHING UNIT BASE SHOWING CURB SUPPORT REQUIREM...

Страница 7: ...s should be torqued to 50 ft lbs The bearing set screws should be torqued to 15 ft lbs 4 The bearing set screws should be checked periodically for tightness A bearing set screw is located on each side...

Страница 8: ...The PRE FILTER CAPACITY AND RESISTANCE TABLE FIGURE 26 and FINAL FILTER CAPACITY AND RESISTANCE TABLE FIGURE 27 provide data for most pre filters and final filters used in Fl ktGroup SEMCO systems Fo...

Страница 9: ...ms equipped with pre filter and final filter banks it is recommended that pre filter banks be changed twice as often as final filters For air filter replacement a rigid cell type filter that matches t...

Страница 10: ...f drive rated current kVA dependent 0 57 208 230 0 29 460 E2 03 Motor No Load Current 0 to E2 01 kVA dependent 0 23 208 230 11 460 Nameplate amps 40 Consult SEMCO PROGRAMMING PARAMETERS Fl ktGroup SEM...

Страница 11: ...abilities which can be useful for troubleshooting or for emergency operation For automatic operation all output switches on the controller should be to the left Manuals for the inverters and any gas f...

Страница 12: ...shaft immediately Fan operating in stall or unstable flow Make sure system is operating at design static pressure and design flow rates Noise motors Supply voltage is high or inconsistent Check suppl...

Страница 13: ...g weather resistant materials Equipment contained within the enclosure requires regular maintenance to keep the system operating smoothly You will find maintenance instructions for every component in...

Страница 14: ...and shafts for dirt and other foreign matter that would impede normal movement and prevent blades and seals from seating properly Clean as necessary Inspect seals every three months to be sure that no...

Страница 15: ...s will be supplied upon request on receipt of order SEMCO is a registered Trademark of SEMCO LLC Other trademarks and logos in this publication may be property of SEMCO LLC its subsidiaries or any of...

Отзывы: