Electrical connection
HyPower-Geko
66
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
6.7.4 Connecting external sensor (option)
MATRIX
2001
3001
4001
4001+IO
9
Control panel connection – air-handling unit
Control panels MATRIX OP3x/44/5x can only be operated with
units fitted with MATRIX 3000 controller electronics.
•
Connect the control cables in accordance with the wiring
diagram.
– The following cable is recommended for the bus line:
Manufacturer: HELUKABEL
Type: CAN-BUS flexible 2 x 2 x ... mm
2
:
(refer to note on Seite 66 at the bottom)
Fig. 6-14: Control panel connection – air-handling unit
12
99
98
97
96
95
13
34
33
32
37
36
35
38
99
98
97
96
95
Co
nt
ro
l pan
e
l
MAT
R
IX OP30
to OP51
Unit wi
th
MA
TRIX300
0
Connecting master unit with slave units
If units are fitted with MATRIX 3000 controllers, a 2-core bus
line must be used.
•
Connect the control cables in accordance with the wiring
diagram.
– Individual units can be fitted with MATRIX 3000.
– The following cable is recommended for the bus line:
Manufacturer: HELUKABEL
Type: CAN-BUS flexible 2 x 2 x ... mm
2
:
(refer to note on Seite 66 at the bottom)
Fig. 6-15: Connecting master unit with slave units
User instructions!
For connection, use only twisted-pair wire with braided shield certified according to
DIN 19245 T3 and EN 50170.
Further slave units
99
98
97
96
95
99
98
97
96
95
Slave u
n
it
with
MATRIX 30
00
Slav
e un
it
wit
h
MAT
R
IX 3000
MATRIX
2001
3001
4001
4001+IO
9
9