HyPower-Geko
Maintenance and Troubleshooting
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
117
8.2
Quarterly maintenance
8.2.1 Examine filter
Check the filter for contamination, damage, and odors and exchange if necessary.
8.2.2 Replacing filter
In order to carry out the exchange of the filter according to fig. 8-1 proceed as follows:
•
Release the sash fasteners on the filter flap by a half-turn counter-clockwise (refer
to fig. 8-1; and open the filter flap by turning downward (refer to fig. 8-1, Pos. 1).
•
Remove the filter evenly from the unit (refer tofig. 8-1; Pos. 3).
•
Pull away the terminal strips left and right of filter frame (refer to fig. 8-1; Pos. 4).
•
Pull the filter material from frame (refer tofig. 8-1; Pos. 5).
•
Once again insert the new filter element in reverse sequence.
•
Close the filter flap and lock the fasteners by pushing into the lock position.
Pos. 1:
Filter panel
Pos. 2:
Quick locks
Pos. 3:
Filter
Pos. 4:
Terminal strip
Pos. 5:
Filter material
User instructions!
Replacement filter set (5 units) can be ordered from FläktGroup using the following
order numbers ZGH.#A823 (filter class G2) or ZGH.#A843 (filter class G4). The
symbol "#" is a placeholder for the size to be specified.
Fig. 8-1:
Removing filter, replacing filter element
Содержание HYPOWER-GEKO