HyPower-Geko
Commissioning
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
113
7.12.2 Fans with MATRIX 511
The fan control behaviour depends on the selected operating mode on the control
panel.
– In position "A" the fan speed 3 is continuously activated.
– In positions "1" to "5" the fan is deactivated as soon as the setpoint temperature is
reached. Deactivation is performed by taking into account the minimum running
time (2 min.) and repeated activation following minimum downtime (1 min.).
7.12.3 Valves
Depending on the selected controller, the integrated valve controller supports open/
close and modulating valves.
The valves can be controlled in the following modes:
– Heating
– Cooling
– Cooling or heating
– Heating and cooling
In order to reach a common starting position, the factory-set synchronization mecha-
nism moves all connected valves (only modulating valves) to OPEN or CLOSE position
every 12 hours.
7.12.4 Condensate pump
The condensate pump drains the condensate that forms on cooling units. Depending
on requirements, the condensate pump is activated by a float switch.
When a limit value is exceeded, the fan is switched off, the cooling valve is closed and
an error message is displayed on the control panel.
7.12.5 Standby mode
Standby mode is only available with room temperature control option. This does not
regulate the temperature to a fixed setpoint, but instead to a pre-set setpoint range.
The MATRIX.PC service software enables to change this setpoint.
The standby mode is activated if a room temperature sensor is connected but no room
temperature setpoint, i.e. no control panel, is available (e.g. during construction phase
and drying of building).
The “standby mode” function is terminated as soon as the fixed room temperature set-
point is set.
MATRIX
511
2001
3001
4001
4001+IO
9
MATRIX
511
2001
3001
4001
4001+IO
9
9
9
9
9
MATRIX
511
2001
3001
4001
4001+IO
9
9
9
9
9
MATRIX
511
2001
3001
4001
4001+IO
9
9
9