HUMIDIFIER, FOR CIRCULATED WATER

Installation and maintenance instruction

 

7

FläktGroup 

DC_8642GB   20180131_R0

Specifications are subject to alteration without notice

ITEMS TO CHECK WHEN MAKING ADJUSTMENTS 

Water:

Determine the proportion of calcium and bicarbonate in the water,
and its pH level. This information can be obtained from a water 
analysis or from the local water company. Enter the values obtai-
ned in chart 1 on page 4 to determine which zone the water can
be classified.
If the water quality is in zone 4 a water softener must be used.

Testing operation of humidifier:

–  Turn on the external switch.
–  Give the start signal to the humidifier by closing input TF1
  (if this signal is interrupted the humidifier will stop and the water  
  will drain out).
–  The tray should only start to fill with water when there is a need  
  for humidification, i.e. when the RH1 input closes.

Now check:

–  that the humidifier starts to fill with water.
–  that the pump starts and pumps water (input RH1 must be   
  closed). If there is no water flow, change the direction of rotation,  
  see figure 3.
–  Preset the required supply water flow rate according to Table 3.
  This is done by setting the adjustment screw on the flow con-
  troller, see figure 4.
–  that water sprays out of all the holes in the spray pipe(s).
  Use a needle to clear any clogged holes. If the pipe is clogged  
  with dirt, remove the end plugs, pos. 16, fig. 1, clean the spray  
  pipe with a round brush, then flush it clean.
–  that the supply flow stops when the water reaches level A.
–  that the water bleed-off rate is correct. Open the outlet valve,  
  figure 2, by holding in the left arrow key on RC1. When the water  
  level has fallen below level B the valve should open fully and
  the display should show ”Emptying”. When the water drops  
  below level C the water inlet should open, and after the preset  
  time the drain valve should start to close. When the water
  reaches level C the pump should stop briefly. The tray will then  
  refill with water.

 

Droplet eliminator

The droplet eliminator must be installed in the correct direction of 
the air flow, see the arrow on the droplet separator.

Table 3 gives the amount of water that the circulation pump must 
be set to. It is not the water consumption.

 

EUQA 2;1

Closed

Open

Fig. 2

0

0

2

4

2

4 6

30

20
10

EUQA Pump

Fig. 3

Adjustment screw

Reading point

Fig. 5  Level sensor

Fig. 4

T1 

Q1 

K1 

Q2 

K2 

RC1 

OK 

ESC 

F1 

11-15 

1-9 

PE 

T1,  Transformator 230VAC/24VDC 
RC1, Reglercentral (PLC) 
K1-K2, Kontaktor 
Q1-Q2, ÷verlastskydd 

F1, S‰kring 2A 

(55) 

(08) 

  YYYY/MM/DD 

      08        :     55 

 2006 / 03 / 07 

Ex. 

OK 

ClockSet 

OK 

TID 

ZEIT 

TIME 

08:55 

TID 

ZEIT 

TIME 

08:55 

  YYYY/MM/DD

      08       :    55

 2006 / 03 / 07

OK

ClockSet

OK

TID 

ZEIT 

TIME 

08:55 

TID

ZEIT

TIME

08:55

Bild 7. Inst‰llning av klockan. 

INAKTIVITET
INACTIVITY
INAKTIVITÄT
T>               240   min

(55)

(08)

  YYYY/MM/DD

      08       :    55

 2006 / 03 / 07

Ex.

OK

ClockSet

OK

TID

ZEIT

TIME

08:55

Size

Water flow, l/min

Aluminium

90 %                  60 %

009

014, 020

011

5

7

8

3

4

4

018, 027, 036

023, 045, 056

032

10

12

13

5

6

7

041, 054, 068

047, 050, 063, 079

072, 090

14

16

18

7

9

10

Содержание EQQA

Страница 1: ...fier cassette EQQA Once through water 2 5 EQQA for circulated water 6 15 EQQZ 01 Humidifier cassette Ordering code 16 HUMIDIFIER EQQA EQQZ INSTALLATION AND MAINTENANCE INSTRUCTION Fl ktGroup DC_8642GB...

Страница 2: ...EQAZ 08 accessory 4 Drain pipe 5 Humidifier fill 6 Droplet eliminator 7 Spray pipe 8 End plug 9 side wall 10 Water filter with a max mesh of 500 m not included 11 Flushing hose 12 Pulse valve and con...

Страница 3: ...ion of air flow see arrows B that there are no water leaks at any of the couplings and connections C that water is being discharged from all holes in the spray pipe or pipes If any holes are clogged u...

Страница 4: ...parate instructions will be supplied with the new block Important The innermost fills can be reached by stepping carefully onto the edge of the tray Avoid stepping on the guides or base of the tray Hu...

Страница 5: ...rior by flushing wiping or if necessary brushing 3 Humidifier fills Droplet eliminator Cleaning 3 Water filter Clean or replace the filter cartridge if necessary The mesh must not exceed 500 m 3 Const...

Страница 6: ...ized electrician When wiring is carried out on the installation site the supply cable must be run via an external high voltage switch to the control box through the cable gland fitted in the casing Th...

Страница 7: ...s If the pipe is clogged with dirt remove the end plugs pos 16 fig 1 clean the spray pipe with a round brush then flush it clean that the supply flow stops when the water reaches level A that the wate...

Страница 8: ...0 Table 5 Presetting the dilution period AHU eQ 009 eQ 011 eQ 014 eQ 018 eQ 020 eQ 023 eQ 027 eQ 032 eQ 036 eQ 050 eQ 072 eQ 090 Airflow m3 s 0 8 1 1 5 1 7 2 2 5 3 4 4 5 7 9 Water content of entering...

Страница 9: ...the lower part of the transition zone where the water is normally of drinking water quality Zone 3 is the upper part of the transition zone where the water is relatively hard Zone 4 is the precipitat...

Страница 10: ...cleaned using the supplied flushing hose E Refit parts in the reverse order F Check the position of the spacer plate and close the door INTERRUPTED OPERATION The control unit of the humidifier switche...

Страница 11: ...a selection INFORMATION IMAGES 1 In operation information in Swedish 2 In operation information in English 3 In operation information in German 4 For setting water quality zone and time delay T for di...

Страница 12: ...e Settingstarttimeto18 30On Press the arrow key three times until the field 00 00 flashes Press OK The timer program for the start time will now be shown Press arrow down twice to get to the last line...

Страница 13: ...ET THE INACTIVITY TIME SETTING The water in the humidifier will be emptied if the humidifier has been inactive for a period longer than the preset inactivity time no need for humidification When the R...

Страница 14: ...level A The most likely reason is that the solenoid valve MV1 is not closing The alarm stops after five minutes The water level does not reach the maximum level A during filling The most likely reaso...

Страница 15: ...MV1 SV1 Circulation pump s Alarm output Hygrostat RH2 Hygrostat RH1 Start signal from TF1 230VAC 24VDC Contactor Contactor Overload protection Overload protection Transformer External high voltage sw...

Страница 16: ...re installed in the humidifier the bevelled corner must face downwards and against the direction of the air flow ORDERING CODE Humidifier EQQA aaa bb c d e f Size aaa 008 090 Humidity level bb 1 90 2...

Отзывы: