HUMIDIFIER, ONCE-THROUGH WATER
Installation and maintenance instruction
5
FläktGroup
DC_8642GB 20180131_R0
Specifications are subject to alteration without notice
SERVICE INTERVALS
Component
Action
Interval, months
Casing (water tray, ends, top,
guide rais)
Drain the water tray. Clean the interior by flushing,
wiping or if necessary brushing.
3
Humidifier fills
Droplet eliminator
Cleaning.
3
Water filter
Clean or replace the filter cartridge, if necessary.
(The mesh must not exceed 500 μm).
3
Constant flow valve
Check that there is no contamination on the rubber
membrane. Clean carefully if needed.
3
Water flow
Clean the spray pipes, if necessary.
3
Water trap
Clean and refill.
6
Water quality
Water pH should not be lower than 5 or higher than 8.5.
Drinking water is suitable.
12