HUMIDIFIER, FOR CIRCULATED WATER

Installation and maintenance instruction  

8

FläktGroup 

DC_8642GB   20180131_R0

Specifications are subject to alteration without notice

WATER BLEED-OFF 

Water consumption consists of the useful evaporation and 
essential water bleed-off flow. This bleed-off flow is necessary 
to reduce the concentration of salts in the circulating water.
If the salt concentration becomes too high, salts are precipitated 
out in the humidifier fills, which will reduce the performance and 
working life of the humidifier.
Chart 1 can be used to determine the appropriate bleed-off flow, 
by determining zone for the current water quality. Then set the 
appropriate bleed-off flow to ensure that the water in the tray is 
kept clean it is recommended that it is drained and flushed once 
every 24 hours (timing is preset at factory for 12.00–12.15).
If high demands are made on hygiene or if humidification require-
ments are high for an extended period, i.e. 

Δ 

x > 8 gram per kg

of air (90 % humidifier) or 

Δ 

x > 5 gram (60 % humidifier), it is re-

commended that an extra drainage and flushing cycle is added 
in each 24-hour period. It may be necessary to extend the dilu-
tion time, see table 4. The value (T) is set using the display.

Size

Time for dilution, seconds

Normal operation,

preset value

High humidification over

a long period

b = 1

90 %

b = 2

80 %

Δ 

x >8 gram

90 %

Δ 

x >8 gram

80 %

009

011

014

018

020

0

10

10

20

10

0

0

0

0

0

0

20

20

30

20

0

0

0

10

0

023

027

20

10

0

0

40

20

10

0

032

041

047

20

30

40

0

0

0

40

60

80

10

20

30

036

30

0

90

20

045

050

054

072

30

50

50

60

0

0

0

0

80

100

100

120

20

30

30

40

056

063

068

40

50

70

0

0

0

80

100

120

30

30

50

079

190

55

60

0

0

55

60

20

20

Table 5. Presetting the dilution period

AHU

eQ 

009

eQ 

011

eQ 

014

eQ 

018

eQ 

020

eQ 

023

eQ 

027

eQ 

032

eQ 

036

eQ 

050

eQ 

072

eQ 

090

Airflow

m

3

/s

0,8

1

1,5

1,7

2

2,5

3

4

4

5

7

9

Water content of entering air

g/kg

5

5

5

5

5

5

5

5

5

5

5

5

Water content of leaving air

g/kg

10

10

10

10

10

10

10

10

10

10

10

10

Tankvolume, level A

l

30,8 50,4

45,5 60,3 45,5

75,2

60,3

80,1

85,6

148,4 169,3 169,3

Tankvolume, level B

l

15,3

25,1

22,6

30

22,6

37,5

30

39,9

47,8

82,8

94,4

86,9

Tankvolume, level C

l

10,3

16,9

15,2

20,2

15,2

25,2 20,2 26,9

26,6

46

52,5

52,5

Dilution time, T

sek

0

10

10

20

10

20

10

20

30

50

60

60

Operation time/day

(average over the year)

tim

3,6

3,6

3,6

3,6

3,6

3,6

3,6

3,6

3,6

3,6

3,6

3,6

Draining per day 

1

1

1

1

1

1

1

1

1

1

1

1

Water cost

€/m

3

2

2

2

2

2

2

2

2

2

2

2

2

Calculated water consumption: 
Water consumption due to

evaporation

l/h

17,3

21,6

32,4

36,7

43,2

54,0

64,8

86,4

86,4

108,0 151,2

194,4

Water consumption due to

draining to level C

l/h

5,6

7,0

10,5

11,9

14,0

17,6

21,0

27,9

48,5

60,6

84,6

81,2

Water consumption due to

dilution calc on T

l/h

0,0

4,3

7,1

12,1

9,4

14,3

10,7

21,5

34,3

41,2

60,6

70,8

Water consumption due to rinsing 

l/h

8,6

14,0

12,6

16,8

12,6

20,9

16,8

22,3

23,8

41,2

47,0

47,0

Total water consumption

l/h

31,4

46,9 62,6 77,5

79,2 106,8 113,2 158,1 192,9 251,0 343,4 393,4

Total water consumption

m

3

/år

41,3

61,6 82,2 101,8 104,1 140,4 148,7 207,7 253,5 329,8 451,2 516,9

Water cost/year

€/år

83

123

164

204

208

281

297

415

507

660

902

1034

Factor total consump/evaporation 

1,82

2,17

1,93

2,11

1,83

1,98

1,75

1,83

2,23

2,32

2,27

2,02

WATER CONSUMPTION FOR HUMIDIFIER WITH CIRCULATING WATER

CIRCULATION FLOW

 

Dry air

 

                      

 Humid air

Table 4. The water consumption per years is dependant on climate, operation hours, water quality and the quantity of moisture required. 

this table gives an estimate for a typical case.

Содержание EQQA

Страница 1: ...fier cassette EQQA Once through water 2 5 EQQA for circulated water 6 15 EQQZ 01 Humidifier cassette Ordering code 16 HUMIDIFIER EQQA EQQZ INSTALLATION AND MAINTENANCE INSTRUCTION Fl ktGroup DC_8642GB...

Страница 2: ...EQAZ 08 accessory 4 Drain pipe 5 Humidifier fill 6 Droplet eliminator 7 Spray pipe 8 End plug 9 side wall 10 Water filter with a max mesh of 500 m not included 11 Flushing hose 12 Pulse valve and con...

Страница 3: ...ion of air flow see arrows B that there are no water leaks at any of the couplings and connections C that water is being discharged from all holes in the spray pipe or pipes If any holes are clogged u...

Страница 4: ...parate instructions will be supplied with the new block Important The innermost fills can be reached by stepping carefully onto the edge of the tray Avoid stepping on the guides or base of the tray Hu...

Страница 5: ...rior by flushing wiping or if necessary brushing 3 Humidifier fills Droplet eliminator Cleaning 3 Water filter Clean or replace the filter cartridge if necessary The mesh must not exceed 500 m 3 Const...

Страница 6: ...ized electrician When wiring is carried out on the installation site the supply cable must be run via an external high voltage switch to the control box through the cable gland fitted in the casing Th...

Страница 7: ...s If the pipe is clogged with dirt remove the end plugs pos 16 fig 1 clean the spray pipe with a round brush then flush it clean that the supply flow stops when the water reaches level A that the wate...

Страница 8: ...0 Table 5 Presetting the dilution period AHU eQ 009 eQ 011 eQ 014 eQ 018 eQ 020 eQ 023 eQ 027 eQ 032 eQ 036 eQ 050 eQ 072 eQ 090 Airflow m3 s 0 8 1 1 5 1 7 2 2 5 3 4 4 5 7 9 Water content of entering...

Страница 9: ...the lower part of the transition zone where the water is normally of drinking water quality Zone 3 is the upper part of the transition zone where the water is relatively hard Zone 4 is the precipitat...

Страница 10: ...cleaned using the supplied flushing hose E Refit parts in the reverse order F Check the position of the spacer plate and close the door INTERRUPTED OPERATION The control unit of the humidifier switche...

Страница 11: ...a selection INFORMATION IMAGES 1 In operation information in Swedish 2 In operation information in English 3 In operation information in German 4 For setting water quality zone and time delay T for di...

Страница 12: ...e Settingstarttimeto18 30On Press the arrow key three times until the field 00 00 flashes Press OK The timer program for the start time will now be shown Press arrow down twice to get to the last line...

Страница 13: ...ET THE INACTIVITY TIME SETTING The water in the humidifier will be emptied if the humidifier has been inactive for a period longer than the preset inactivity time no need for humidification When the R...

Страница 14: ...level A The most likely reason is that the solenoid valve MV1 is not closing The alarm stops after five minutes The water level does not reach the maximum level A during filling The most likely reaso...

Страница 15: ...MV1 SV1 Circulation pump s Alarm output Hygrostat RH2 Hygrostat RH1 Start signal from TF1 230VAC 24VDC Contactor Contactor Overload protection Overload protection Transformer External high voltage sw...

Страница 16: ...re installed in the humidifier the bevelled corner must face downwards and against the direction of the air flow ORDERING CODE Humidifier EQQA aaa bb c d e f Size aaa 008 090 Humidity level bb 1 90 2...

Отзывы: