HUMIDIFIER, ONCE-THROUGH WATER
Installation and maintenance instruction
4
FläktGroup
DC_8642GB 20180131_R0
Specifications are subject to alteration without notice
CLEANING THE HUMIDIFIER FILLS AND DROPLET
ELIMINATOR
A. Turn off the water supply.
B. Open the inspection door.
C. Slide the droplet eliminator and humidifier fills straight out of
the humidifier.
D. The humidifier fills are relatively fragile and should therefore
be handled very carefully. Clean by spraying with clean
water.
E. Check that the holes in the spray pipe are not blocked.
If necessary remove the end plugs from the pipe and clean it
internally.
F. Refit parts in the reverse order.
G. Check the position of the side wall and close the door.
If it is necessary to replace the humidifier block, separate
instructions will be supplied with the new block.
Important!
The innermost fills can be reached by stepping
carefully onto the edge of the tray.
Avoid stepping on the guides or base of the tray.
Humidifier fills
Droplet eliminator
Size
009
011
014
020
018
023
027
036
045
056
032
041,
047
050
054
068
Humidification
rate 90 %
4
6,5
8
10
11
Humidification
rate 60 %
2
3
4
5
6,5
Size
063
072
079
090
072
090
Humidification
rate 90 %
15
17
Humidification
rate 60 %
8
8,5
Outlet connection
Ø 32, out
Water connection,
ext. thread 1/2”
Constant
flow valve
End plug
Constant flow valve,
located inside
Table 3. Water flow through the constant flow valve and
the pulse valve.
CLEANING THE CONSTANT FLOW VALVE
A. Remove the valve.
B. Check that there is no contamination on the rubber
membrane. Clean carefully if needed.
C. Refit the valve with the arrow pointing in the direction of
the water flow, and check the water flow.
Min. water pressure in supply pipe 100 kPa.
Spray pipe