CONNECTION
The water supply is regulated by a pulse valve and constant flow
valve, pos. 12. Connect the supply pipe, pos. 1, to the inlet pipe
(tab. 1). The supply must have a shut-off valve, pos. 2, and water
filter, pos. 10.
The drain pipe must be fitted with a cleanable water trap, pos. 3,
(EQAZ-08) and should be run, without reduction in diameter, to a
floor gulley.
Water trap EQAZ-08
Shut-off valve, water trap and water filter are not supplied
with EQQA.
CONNECTION
1. Water supply pipe
2. Shut-off valve (not included)
3. Water trap EQAZ-08 (accessory)
4. Drain pipe
5. Humidifier fill
6. Droplet eliminator
7. Spray pipe
8. End plug
9. side wall
10. Water filter, with a max mesh of 500 μm (not included)
11. Flushing hose
12. Pulse valve and constant flow valve
Important!
Use a pipe wrench to stop pipe couplings
rotating when connecting external piping.
Connection number/Diameter
Value
90 %, b = 1 60 %, b = 2
Inlet
Outlet
009-045
056, 068
009-054
056, 068
No. 15 1/2”
diam 32
072, 079
072, 079
No. 20 3/4”
diam 2x32
050, 063
050, 063
No. 20 3/4”
diam 2x32
090
090
No. 20 3/4”
diam 2x32
Connection data – pulse valves
Size
Number of
valves
Date
009-090
1
Connection data 100-230 V
Current 0,5 A
Frequency 50-60 Hz
Protection class I I P65
Output 8 watts
Function Normally Closed
Table 1. Connection dimensions
9
8
7
9
5
6
2
10
11
12
1
4
3
aaa 008-045
054,056,
068
aaa 050,063,072,
079,090
4
5
aaa 050, 063, 072,
079, 090
aaa 008-045
054, 056,
068