9.2.6 Refrigerant Leakage Detection diagnosis and solution (EC)
Is there cool air blowing
out from indoor air outlet?
Yes
Yes
Check if T2 sensor is well
fixed. Correct the installation
or replace T2 sensor. Does
the problem remain again?
No
Is there any leakage? Especially
the connection parts, such as the
gas valve and the liquid valve.
No
Shut off the power supply and
turn it on 5 seconds later. Is it
still displaying the error code?
Replace indoor PCB.
Yes
Repair the leakage and
recharge the refrigerant.
Yes
Clear the blocking.
Yes
Is there any block i n g ? (Such as the
capillary or the welded points of the pipes.)
Содержание FSAIF-Pro-123AE2
Страница 8: ...8 O optional function ...
Страница 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Страница 14: ...14 FSAIF Pro 123AE2 ...
Страница 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Страница 16: ...16 FSOAIF Pro 123AE2 ...
Страница 17: ...17 FSOAIF Pro 183AE2 ...
Страница 18: ...18 FSOAIF Pro 243AE2 ...
Страница 29: ...29 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 54: ...54 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1 ...
Страница 59: ...59 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3 ...
Страница 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Страница 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Страница 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Страница 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...