8.4.3.5 Evaporator coil temperature protection
TEstop
T2
Resume
Off
Decrease
TEdown
TEnorm
Hold
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
8.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
ΔT=T1-Ts
Running mode
ΔT
>
1
℃
Cooling
-1<ΔT≤1
℃
Fan-only
ΔT≤-1
℃
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
8.4.5 Drying mode
8.4.5.1 Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as
in cooling mode.
Содержание FSAIF-Pro-123AE2
Страница 8: ...8 O optional function ...
Страница 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Страница 14: ...14 FSAIF Pro 123AE2 ...
Страница 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Страница 16: ...16 FSOAIF Pro 123AE2 ...
Страница 17: ...17 FSOAIF Pro 183AE2 ...
Страница 18: ...18 FSOAIF Pro 243AE2 ...
Страница 29: ...29 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 54: ...54 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1 ...
Страница 59: ...59 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3 ...
Страница 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Страница 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Страница 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Страница 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...