8.4.2 Cooling Mode
8.4.2.1 Compressor running rules
The maximum operation frequency of compressor after starting submits to following rule.
50
49
45
44
41
40
33
32
Fmax=T4FREMAX1
T4
30
29
22
20
Fmax=T4FREMAX2
Fmax=T4FREMAX3
Fmax=T4FREMAX4
Fmax=T4FREMAX5
Fmax=T4FREMAX6
Fmax=T4FREMAX7
Meanwhile, the maximum frequency is limited by the indoor fan speed.
Indoor fan speed
Maximum frequency
High speed / turbo function
No limit
Silent mode
Fixed at F3
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to the outdoor ambient temp. During the 7 minutes, the frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
Содержание FSAIF-Pro-123AE2
Страница 8: ...8 O optional function ...
Страница 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Страница 14: ...14 FSAIF Pro 123AE2 ...
Страница 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Страница 16: ...16 FSOAIF Pro 123AE2 ...
Страница 17: ...17 FSOAIF Pro 183AE2 ...
Страница 18: ...18 FSOAIF Pro 243AE2 ...
Страница 29: ...29 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 54: ...54 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1 ...
Страница 59: ...59 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3 ...
Страница 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Страница 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Страница 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Страница 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...