42
If the compressor stops caused by the room temperature rising, the indoor fan will be forced to run 127
seconds with breeze. During this period, the anti-cold-wind is disabled.
Auto fan action in heating mode:
-1.0
-2.0
-3.0
-4.0
0.0
T1-Ts+¦ ¤
T
L
(H+-L)*0.4+L
(H+-L)*0.6+L
-5.0
-6.0
-6.5
H+
(H+-L)*0.8+L
(H+-L)*0.6+L
(H+-L)*0.2+L
Содержание FSAIF-Pro-123AE2
Страница 8: ...8 O optional function ...
Страница 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Страница 14: ...14 FSAIF Pro 123AE2 ...
Страница 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Страница 16: ...16 FSOAIF Pro 123AE2 ...
Страница 17: ...17 FSOAIF Pro 183AE2 ...
Страница 18: ...18 FSOAIF Pro 243AE2 ...
Страница 29: ...29 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 54: ...54 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1 ...
Страница 59: ...59 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3 ...
Страница 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Страница 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Страница 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Страница 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...