5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts.
Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on
the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Содержание FSAIF-Pro-123AE2
Страница 8: ...8 O optional function ...
Страница 13: ...13 5 Wiring Diagram FSAIF Pro 93AE2 FSAIF Pro 183AE2 FSAIF Pro 243AE2 ...
Страница 14: ...14 FSAIF Pro 123AE2 ...
Страница 15: ...15 5 2 Outdoor Unit FSOAIF Pro 93AE2 ...
Страница 16: ...16 FSOAIF Pro 123AE2 ...
Страница 17: ...17 FSOAIF Pro 183AE2 ...
Страница 18: ...18 FSOAIF Pro 243AE2 ...
Страница 29: ...29 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 54: ...54 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1 ...
Страница 59: ...59 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3 ...
Страница 61: ...61 9 2 7 IPM malfunction or IGBT over strong current protection diagnosis and solution P0 ...
Страница 62: ...62 9 2 8 Over voltage or too low voltage protection diagnosis and solution P1 ...
Страница 63: ...63 9 2 9 High temperature protection of compressor top diagnosis and solution P2 ...
Страница 64: ...64 9 2 10 Inverter compressor drive error diagnosis and solution P4 ...