C6.1.6/0513-0515/E
38
LABEL
DESCRIPTION
ZXME
Level
ZXLE
Level
ZXDE
Level
5.7.7 Vapour Injection Mode (Cont'd)
F34
Differential between the vapour inlet and the vapour outlet temperature for R407F
°C
10.0
L2
F35
Differential between the vapour inlet and the vapour outlet temperature for N40
°C
10.0
L2
F36
Differential between the vapour inlet and the vapour outlet temperature for DR33
°C
10.0
L2
F38
Max DLT temperature before changing from vapour to liquid injection control
°C
110.0
L2
F39
Differential before resuming vapour injection
°C
15.0
L2
5.7.9 EVI System Checks
F40
Max open EXV warning time
min
2
L2
F41
Delta between setpoint and shortage of refrigerant error during max open warning
°C
8.0
L2
5.7.10 Constant Liquid Temperature Mode for low Ambient EVI Injection
F42
Constant liquid temperature mode enabled for low ambient EVI injection
-
0-NO
L2
F43
Constant liquid temperature setpoint
°C
0.0
L2
F44
Ambient temperature setpoint for constant liquid temperature mode
°C
-20.0
L2
8.0 Low Side Control
G01
Case temperature probe selection
-
0-NU
L2
0-NU
L2
0-NU
L2
G02
Case temperature setpoint
°C
2.0
L2
2.0
L2
2.0
L2
G03
Case temperature differential
°C
1.0
L2
1.0
L2
1.0
L2
G04
Case temperature low range
°C
-10.0
L2
-10.0
L2
-10.0
L2
G05
Case temperature high range
°C
15.0
L2
15.0
L2
15.0
L2
8.0 Low Side Control
G06
Case probe failure limp along on time
min
2
L2
2
L2
2
L2
G07
Case probe failure limp along off time
min
1
L2
1
L2
1
L2
G08
Compressor and fan status when open door
0-NO
L2
0-NO
L2
0-NO
L2
G09
Regulation with door open
1-YES
L2
1-YES
L2
1-YES
L2
G10
Liquid line solenoid control
V
0-Compressor
L2
0-Compressor
L2
0-Compressor
L2
G11
Maximum pump down time
min
3
L2
3
L2
3
L2
G56
Use the liquid line solenoid
-
0-NO
L2
0-NO
l2
0-NO
l2
5.5.9 Over Current Protection
H01
Current sensing 1 enabled
-
1-YES
L2
1-YES
L2
1-YES
L2
H02
Current sensing 2 enabled
-
1-YES
L2
1-YES
L2
1-YES
L2
H06
Voltage and current protection enabled
-
1-YES
L2
1-YES
L2
1-YES
L2
H07
Maximum continous current limit
A
15
L2
15
L2
15
L2
H08
Voltage/current sening trip minimum off time
min
5
L2
5
L2
5
L2
H09
Adjustable current limit before trip
A
12
L2
12
L2
12.5
L2
H10
Ignore current sensing duration at startup duration
sec
3
L2
3
L2
3
L2
H11
Over current trips before lockout
5
L2
5
L2
5
L2
H12
Loss of phase trips number before lockout
5
L2
5
L2
5
L2
H19
Generate warning or shut the regulation when phase imbalance
-
1-Off the unit
L2
1-Off the unit
L2
1-Off the unit
L2
H20
Missing current duration before trip
sec
10
L2
10
L2
10