C6.1.6/0513-0515/E
35
LABEL
DESCRIPTION
ZXME
Level
ZXLE
Level
ZXDE
Level
C08
Setpoint offset
-
0-NV
L2
0-NV
L2
0-NV
L2
C09
Ambient temperature operature setpoint
°C
-20
L2
-20
L2
-20
L2
C10
pressure/temperature operation for ambient differential
bar
1.0
L2
1.0
L2
1.0
L2
C11
Ambient temperature recover differential
°C
5.0
L2
5.0
L2
5.0
L2
5.5.3 Low Ambient Operation
C12
Ambient temperature required to initiate low ambient on time
°C
-10
L2
-10
L2
-10
L2
C13
Temperature/pressure to end low ambient timer and resume normal operation
bar
10
L2
10
L2
10
L2
C14
Low ambient minimum on time
sec
10
L2
10
L2
10
L2
C15
Pressure to end low ambient timer and shut off the compressor
bar
0.2
L2
0.2
L2
0.3
L2
5.3.2 Compressor Digital Scroll Operation Signal
C16
Digital compressor setpoint
bar
3.3
L1
C17
Proporational band for compressor regulation
bar
2.0
L1
C18
Band offset for compressor regulation
bar
0.0
L2
C20
Start up time: interval with digital valve before start regulation
sec
10.0
L2
C21
Cycle time for digital compressor
sec
10.0
L1
C22
Safety value for PI regulator (in case of probe error)
%
50.0
L2
C23
Number of active compressor(s) when probe error
-
1.0
L2
C24
Minimum capacity for digital compressor
%
20.0
L1
C25
Maximum capacity for digital compressor
%
100.0
L1
C38
Compressor regulation control signal
-
0-Pressure
L2
0-Pressure
L2
0-Pressure
L2
Compressor Safety
D01
Output delay at start up
sec
5
L2
5
L2
5
L2
5.3.1 Compressor Operation with Faulty Suction Probe
D02
Compressor On time with faulty probe
min
5
L2
5
L2
5
L2
D03
Compressor Off time with faulty probe
min
3
L2
3
L2
3
L2
D04
Minimim time between two starts (same compressor)
min
4
L2
4
L2
4
L2
D05
Delay between compressor switch-off and start-up (same compressor)
sec
120
L2
120
L2
120
L2
D13
Low suction pressure error signal enabling
-
1-YES
L2
1-YES
L2
1-YES
L2
5.5.2 Discharge Pressure Protection
D14
Minimum time of compressor off with high pressure switch protection
min
5
L2
5
V
5
L2
D15
Number of high pressure switch activations before compressor lock
-
7
L2
7
V
7
L2
5.4.2 Bump Start (only for ON/OFF compressor)
D16
Bump start enable
-
0-NO
L2
0-NO
L2
D17
Bump start ambient threshold
°C
0.0
L2
0.0
L2
D18
Compressor stop time for next bump start
hour
1:00
L2
1:00
L2
D19
Compressor on time during bump function
sec
2
L2
2
L2
D20
Compressor off time during bump function
sec
15
L2
15
L2
D21
Number of cycles during bump start
-
3
L2
3
L2
5.4.1 Ambient Based Suction Pressure Offset