5.5.4 Discharge Line Temperature Protection
D22
DLT alarm temperature to stop compressor
°C
130.0
L2
130.0
L2
130.0
L2
D23
DLT alarm recover temperature to turn on compressor
°C
90.0
L2
90.0
L2
90.0
L2
D24
DLT alarm activation delay
sec
30
L2
30
L2
30
L2
D25
Compressor minimum off time for DLT alarm
min
5
L2
5
L2
5
L2
D26
Number of activations of DLT in a hour to stop compressor
-
10
L2
10
L2
10
L2
D27
Time to ignore low DLT sensor error at startup
min
5
L2
5
L2
5
L2
D28
Minimum time of compressor off with low pressure switch protection
min
3
L2
3
L2
3
L2
5.6.3 Fan Modulation Setpoints Based on Compressor Envelope Maps
E01
Condenser fan motor modulation type
-
2-Modulated fan
L2
2-Modulated fan
L2
2-Modulated fan
L2
E38
Fan setpoint modulation enabling
0-NO
L2
0-NO
L2
0-NO
L2
E39
Condenser setpoint when fan setpoint modulation is disabled
°C
35.0
L1
35.0
L1
35.0
L1
5.6.2 Minimum Condensing Setpoint
E40
Minimum condenser setpoint
°C
10.0
L2
10.0
L2
10.0
L2
5.6.3 High Ambient Temperature Override
E41
High ambient fan motor override enabled
1-YES
L2
1-YES
L2
1-YES
L2
E42
High ambient fan motor override differential
°C
5.0
L2
5.0
L2
5.0
L2
5.6.3 Discharge Line Temperature Override
E43
High DLT fan motor override enabled
1-YES
L2
1-YES
L2
1-YES
L2
E44
High DLT fan motor override point for fan
°C
100.0
L2
100.0
L2
100.0
L2
5.6.3 Variable Fan Speed Control
E46
Regulation band of variable fan
°C
10.0
L1
10.0
L1
10.0
L1
E48
Fan full speed duration at fan startup
sec
10
L2
10
L2
10
L2
E49
Fan minimum on time
sec
20
L2
20
L2
20
L2
E50
Fan minimum off time
sec
20
L2
20
L2
20
L2
5.6.3 Fixed Fan Cycling
5.6.11 Condenser Mid-Coil Temperature Sensor With Ambient Sensor Present
E55
Fan control with ambient sensor - Min ambient
°C
0.0
L2
0.0
L2
0.0
L2
E56
Fan control with ambient sensor - Max ambient
°C
20.0
L2
20.0
L2
20.0
L2
E57
Fan speed control with ambient sensor
%
60.0
L2
60.0
L2
60.0
L2
5.5.7 High Condensing Warning
E58
Condenser temperature/pressure threshold for high alarm
bar
27
L2
27
L2
27.8
L2
E59
High condenser temperature alarm delay
min
0
L2
0
L2
0
L2
E60
High condenser temperature alarm with compressor off
1-YES
L2
1-YES
L2
1-YES
L2
E61
Condenser temperature/pressure threshold for alarm recovery
bar
23
L2
23
L2
23
L2
5.6.12 Condenser Mid-Coil Temperature Sensor with Ambient Sensor Present