C6.1.6/0513-0515/E
37
LABEL
DESCRIPTION
ZXME
Level
ZXLE
Level
ZXDE
Level
5.7.1 Liquid Injection Control
F01
Liquid injection setpoint
°C
110.0
L2
110.0
L2
F02
Max DLT temperature before full open injection
°C
118.0
L2
118.0
L2
F03
Min DLT temperature before close injection
°C
80.0
L2
80.0
L2
5.7.4 Injection Error Handling - DLT failure
F04
Mid-coil limp along for DLT failure - Mid-coil 1
°C
60.0
L2
F05
Mid-coil limp along for DLT failure - Mid-coil 2
°C
50.0
L2
F06
Mid-coil limp along for DLT failure - Mid-coil 3
°C
40.0
L2
F07
Mid-coil limp along for DLT failure - Mid-coil 4
°C
30.0
L2
F08
Mid-coil limp along for DLT failure - Mid-coil 5
°C
20.0
L2
F09
Mid-coil limp along for DLT failure - Valve opening 1
%
100
L2
F10
Mid-coil limp along for DLT failure - Valve opening 2
%
80
L2
F11
Mid-coil limp along for DLT failure - Valve opening 3
%
60
L2
F12
Mid-coil limp along for DLT failure - Valve opening 4
%
35
L2
F13
Mid-coil limp along for DLT failure - Valve opening 5
%
15
L2
5.7.4 Injection Error Handling - DLT failure and Mid-Coil failure
F14
Ambient limp along for DLT and mid-coil failure - Temperature 1
°C
30.0
L2
F15
Ambient limp along for DLT and mid-coil failure - Temperature 2
°C
20.0
L2
F16
Ambient limp along for DLT and mid-coil failure - Valve opening 1
%
80
L2
F17
Ambient limp along for DLT and mid-coil failure - Valve opening 2
%
35
L2
5.7.6 Injection Initial Opening Settings
F18
EVI EXV Initial opening – Ambient 1
°C
35.0
L2
F19
EVI EXV Initial opening – Ambient 2
°C
30.0
L2
F20
EVI EXV Initial opening – Ambient 3
°C
25.0
L2
F21
EVI EXV Initial opening – Ambient 4
°C
15.0
L2
F22
EVI EXV Initial opening – Valve opening 1
%
60
L2
F23
EVI EXV Initial opening – Valve opening 2
%
40
L2
F24
EVI EXV Initial opening – Valve opening 3
%
30
L2
F25
EVI EXV Initial opening – Valve opening 4
%
20
L2
F26
EVI EXV Initial opening – Valve opening 5
%
10
L2
5.7.6 Injection Initial Opening Settings - if Ambient and Mid-Coil sensor failure
F27
EVI EXV Initial opening with sensor failure
%
40
L2
5.7.7 Vapour Injection Mode
F28
Differential between the vapour inlet and the vapour outlet temperature for R404A
°C
5.0
L2
F29
Differential between the vapour inlet and the vapour outlet temperature for R507
°C
5.0
L2
F31
Differential between the vapour inlet and the vapour outlet temperature for R22
°C
5.0
L2
F32
Differential between the vapour inlet and the vapour outlet temperature for R407C
°C
10.0
L2
F33
Differential between the vapour inlet and the vapour outlet temperature for R407A
°C
10.0
L2