Remote Control Panel P4 Control
9.2.16
Kapitel/Chapter 10: Remote Control Panel P4 Control - Seite/Page 165
1) Max. current out continuous operation: 0,25 A short time 0,4 A
2) Max. current out is limited by the panel fuse (minus 0,1 A for the panel).
3) The out is protected by an freewheeling diode.
4
T-EXH
i
Error „exhaust temp.“. Temperature switch exhaust elbow in.
Can be set up by jumper as NC or NO
Gives 22 mA (12 V +) on the switch.
Status is displayed by green/red LED.
5
Oil-Press
i
Error „oil pressure“. Oil pressure switch in.
Can be set up by jumper as NC or NO
Gives 22 mA (12 V +) on the switch.
Status is displayed by green/red LED.
6
Start
o
Start relay out . Is active while the „Start“ button is pressed.
The supply voltage is switched on the relay. (see remarks 1-3)
7
Fuel-Pump
o
Fuel pump relay out. Is active, if no error (temp. or oil press. at 3, 4, 5) is
applied. Is active during the „Override“.
The supply voltage is switched on the relay. (see remarks 1-3)