Remote Control Panel P4 Control
23.3.18
Kapitel/Chapter 8: Remote Control Panel P4 Control - Seite/Page 93
8.5.2 Jumper for configuration of the „Override“ time
1 is standard for „override“ activated
2 is standard for „Override“ deactivated“
9 is standard for „Test mode“
The Test mode is active as long as the button „on/off“ is pressed by turning on the panel.
8.6
Maximum ratings
Operation outside of the maximum ratings can causes damage at the panel and the generator
In not indicated otherwise the ambient temperature is assumed. All voltage data are against GND (X1.2).
Operation voltage U
b
is the voltage at terminator X1.1
J104
J105
J106
Test-Mode
Override time [s]
1
open
open
open
no
40
2
closed
open
open
no
20
3
open
closed
open
no
10
4
closed
closed
open
no
5
5
open
open
closed
no
0,16
6
closed
open
closed
no
0,08
7
open
closed
closed
no
0,04
8
closed
closed
closed
no
0,02
9
open
open
- -
yes
2,5
10
closed
open
- -
yes
1,25
11
open
closed
- -
yes
0,63
12
closed
closed
- -
yes
0,31
Parameter
Desc.
min.
max.
Operation Voltage
without time limit. full function
10,5
15
V
without time limit, full function (except H-Meter, LED light
lower)
6
V
maximal 60 min, Ta = 65 °C, full function
17
V
maximal 60 s, Ta = 65 °C, full function
18
V
maximal 100 ms, Ta = 65 °C, full function
22
V
maximal 100 ms, full function, except H-Meter, some LED
out of ordered
4,5
V
ambient temperature for
operation
0
+85
°C
capacity of the outputs
without time limit
0,25
A
without time limit (1 output only)
0,4
A
External voltage on the
outputs
Outputs with freewheeling diode for short out negative
external voltage
-0,3
Ub
V
External Voltage on the
inputs
without time limit. Voltage which are out of the rating will be
short out by the Z- diode.
-0,3
Ub
V
Internal F1
Micro fuse 5 x 20 mm glass fuse slow to blow
0,5
A