Remote Control Panel P4 Control
Seite/Page 90 - Kaptitel/Chapter 8: Remote Control Panel P4 Control
23.3.18
3. Press „OFF“ button and switch off the generator.
4. Activate additional switches (Battery switch, fuel stop valve etc.).
Notice!:
Never switch off the battery until the generator has
stopped.
5. If necessary, close sea cock.
:Notice!:
If the generator switches itself off with the operation with
load for temperature reasons, must be examined
immediately, which the cause is. That can be an error at
the cooling system or any error in the range of the
outside cooling system.
8.4
Installation of the panel
8.4.1 Connection of the remote control panel
Fig. 8.4.1-1: Remote control panel - back side
As standard a 7 core connection-cable, 7m long, is
included in the supply. Cores are numbered from 1 to 7.
The control cables are securely connected to the genset.
On the back of the control panel there are terminals
numbered from 1 - 7. Connect the cores of the control-
cable in respective order.
Please ensure that the remote control panel is installed
in a protected, dry and easily accessible place.
Term.-No Terminator.-
name
i / o
Description
1
Vbat
i
Power supply 12 V (+)
2
GND
i
Power supply 12 V( -)
3
T-Cyl
i
Error „engine temp“. Temperature switch engine head in.
Can be set up by jumper as NC or NO
Gives 22 mA (12 V +) on the switch.
This error is ignored while the „Start“ button is pressed and several seconds
after it is released (time set up by jumpers)
The yellow „Override“ LED is on while the error is ignored.
Status is displayed by green/red LED.