Configurable Zone Types Worksheets  

 
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data 
fields*182-*185. Configurable zone types 92 and 93 can only be programmed using the downloader software. 

 

Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and 
field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the 
tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types. 

 
 

ENTRY 1

 

(see note 5 for RF zones)

 

 

ENTRY 2

 

(see note 5 for RF zones)

 

Response when system disarmed and zone is: 

Intact EOL 

RF zone normal 

Open 

RF zone N/A 

Shorted 

RF zn off-normal 

Auto  

Restore 

 

Vent Zone 

0 = normal 
1 = alarm  
2 = trouble 
3 = fault 

0 = normal 
4 = alarm 
8 = trouble  
12 = fault

  

see note 5 

 0 = normal 
 1 = alarm 
 2 = trouble 
 3 = fault 
 see note 6 

0 = no 
4 = yes  

0 = no 
8 = yes 

Entry 1 = EOL + Open  

 Entry 2 = Short + auto r vent zone  

 

ENTRY 3

 

(see note 5 for RF zones)

 

 

ENTRY 4

 

(see note 5 for RF zones)

 

Response when armed STAY and zone is: 

Intact EOL 

RF zone normal

 

Open 

RF zone N/A

 

Shorted 

RF zn off-normal

 

Byp. when 

disarmed 

Byp. when 

armed 

0 = normal 
1 = alarm  
2 = trouble 
3 = fault

 

 

0 = normal 
4 = alarm 
8 = trouble  
12 = fault

  

see note 5 

 0 = normal 
 1 = alarm 
 2 = trouble 
 3 = fault 
 see note 6 

0 = no 
4 = yes  

 

0 = no 
8 = yes 

 

Entry 3 = EOL + Open  

 Entry 4 = Short + byp. di byp. armed 

 

ENTRY 5

 

(see note 5 for RF zones)

 

 ENTRY 6

(see note 5 for RF zones)

 

Response when armed AWAY and zone is: 

Intact EOL  

RF zone normal

 

Open  

RF zone N/A

 

Shorted 

RF zn off-normal

 

Dial Delay 

(see field *50) 

Fault Delay 

(see field *87) 

0 = normal 
1 = alarm  
2 = trouble 
3 = fault  

0 = normal 
4 = alarm 
8 = trouble  
12 = fault  
see note 5 

 0 = normal 
 1 = alarm 
 2 = trouble 
 3 = fault 
 see note 6 

0 = no 
4 = use delay  

 

0 = no 
8 = use delay 
 
see note 1 

Entry 5 = EOL + Open 

 Entry 6 = Short + dial delay + fault delay 

 

ENTRY 7

 

 

ENTRY 8

  

Display Faults  

Power Reset/ 

Verification 

Use Entry 

Delay 1/2 

Use Exit 

Delay 

Respond as 

Interior Type 

0 = show alarms 

when armed 
& disarmed 

1 = don’t show 

alarms when 
armed 

(show 

alarms, trbles, 
faults when 
disarmed)

 

3 = never show 

any alarms, 
trbles, faults 

0 = no 
4 = power reset 

after fault 

(by code + OFF)

12 = verification 
 (see 

zone 

type 16) 

 0 = no 
 1 = delay 1 
 2 = delay 2 

0 = no 
4 = use exit 

delay  

0 = no 
8 = yes  
 
see note 2 

Entry 7 = fault d power 
reset/verification 

Entry 8 = entry delay 1/entry delay 2 + exit delay +   

 interior zone type 

 

ENTRY 9

 

 

ENTRY 10

 

Alarm Sounds 

Use Bell 
Timeout 

Respond as 

Fire Zone 

Trouble  
Sounds 

Chime when 

Chime Mode On

0 = none 
1 = steady 

keypad 

2 = steady bell 

and keypad 

3 = pulsing bell 

and keypad 

0 = no 
4 = yes  
 
see fields *32, 
*33 

0 = no 
8 = yes  
 
see zone type 
09; see note 4 

 0 = none 
 1 = periodic 

beep 

 2 = trouble 

beeps 

0 = no 
4 = yes  

Entry 9 = alarm  bell t fire zone 

 Entry 10 = trouble chime

 

Entries for Fields *182 and *184

 

Entry  ZT 90 

ZT 91 

ZT 92 

ZT 93 

 (*182) 

(*184) 

(download) (download)

 

 1 

[12] [8]

 

 2 

[14] [6]

 

 3 

[4] [8]

 

 4 

[5] [14]

 

 5 

[4] [8]

 

 6 

[6] [2]

 

 7 

[0] [0]

 

 8 

[0] [0]

 

 9 

[6] [0]

 

10 

[6] [2]

 

 

To calculate the value for each entry:

 

Simply add the values of the selected options 
in each of the entry’s columns (one option per 
column). For example, to program Entry 2 for 
“alarm response to short,” “auto restore on,” 
but not a “vent zone,” enter 5 (“1” for alarm 
short + “4” for auto restore yes + “0” for vent 
zone no). 
 

 

OPEN

SHORTED

INTACT

EOL

ZONE-003-V0

 

Zone Conditions Represented  

in Entries 1-6 

 

NOTES: 

1.  Do not use the “fault delay” option with a 

configurable zone type if it is set for an 
entry or exit delay, otherwise 
unpredictable results may occur. 

2.  To create an interior type zone, select 

“respond as interior zone type” (Entry 8, 
interior type = yes), and set zone 
response to “fault” in entries 3-4 to ensure 
fault displays; do not set as “normal,” 
“alarm,” or “trouble.” 

3.  Do not set fire zones to respond as a 

“fault” (entries 1-6), otherwise faults will 
not display unless the [

] key is pressed. 

4.  4219/4229 modules must use EOLRs or 

unpredictable results may occur. 

5.  RF Zones: The “open” option in entries 1, 

3, and 5 is not applicable for RF zones. 
Use the “intact EOL” option for normal RF 
zone conditions and “shorted” for off-
normal RF zone conditions. 

6.  a. Zone-Doubling/Double-Balanced: A 

short on either zone of a zone-doubled 
pair or on a double-balanced zone 
causes a tamper condition. 

 

b. For double-balanced zones, this entry 

must be “0.” 

 

c. For zone-doubled zones, 

both

 zones 

of the doubled pair must be assigned 
the same response to a short. 

Содержание FA168C-GP

Страница 1: ... Sy ys st te em m Programming Guide ON OFF ARMED READY A B C D 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY FA260 R ARMED READY FA560 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY R AWAY STAY PAGE K5305 5GPPRV2 9 04 Rev A ...

Страница 2: ...9 or 4204 Relay modules Powerline Carrier devices or on board triggers 81 Zone List Programming Zone Lists for relay powerline carrier activation chime zones pager zones etc 82 Alpha Programming Zone alpha descriptors INITIALIZE DOWNLOAD and RESET DEFAULTS 96 Initializes download ID and subscriber account number 97 Sets all data fields to original factory default values TO EXIT PROGRAMMING MODE 98...

Страница 3: ... must be minimum 16 min option 4 34 EXIT DELAY 60 60 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 secs 97 120 secs 98 180 secs 99 240 secs SIA Installations minimum exit delay is 45 seconds UL see inst instr for requirements 35 ENTRY DELAY 1 zone type 01 30 30 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 seconds 97 120 seconds SIA Installations 98 180 ...

Страница 4: ...st be 15 max 55 DYNAMIC SIGNALING PRIORITY 0 0 Primary Dialer first 1 Long Range Radio first For UL Commercial Burglary installations that use a DACT and LRR this field must be 0 56 57 58 Menu Modes These are Menu Mode commands not data fields for Zone Programming Function Key Programming and Expert Mode Zone Programming respectively See page 2 and their respective sections in the Installation and...

Страница 5: ...y disabled if field 199 is set to 1 2 digit display 87 MISC FAULT DELAY TIME used with Configurable Zone Types digit 6 0 0 15 seconds 6 2 1 2 min 12 8 min 1 30 seconds 7 3 min 13 10 min 2 45 seconds 8 4 min 14 12 min 3 60 seconds 9 5 min 15 15 min 4 90 seconds 10 6 min 5 2 minutes 11 7 min UL may only be used on non burglar alarm non fire alarm zones when used in fire and or UL burglar alarm insta...

Страница 6: ...ional prefix characters up to 16 digits 0 9 11 12 13 2 second pause 165 PAGER 2 REPORT OPTIONS 0 0 0 Part 1 Part 2 common See field 162 for reporting options Select for each partition use zone list 10 if using options 12 or 13 166 PAGER 3 PHONE No Enter up to 20 digits 0 9 11 12 13 2 second pause 167 PAGER 3 CHARACTERS Enter the optional prefix characters up to 16 digits 0 9 11 12 13 2 second paus...

Страница 7: ... 2 AUI 1 Must set AUI address to 1 AUI 2 Must set AUI address to 2 Enter each touch screen AUI device s home partition 0 disabled 1 partition 1 2 partition 2 3 partition 3 common NOTE Use of AUI does not affect the number of standard keypads supported AUI Compatibility Note To ensure proper AUI device operation connect only to controls having microprocessor version 3 0 or higher and use AUI device...

Страница 8: ... disarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault by code OFF 12 verification see zone type 16 0 no 1 delay 1 2 delay 2 0 no 4 use exit delay 0 no 8 yes see note 2 Entry 7 fault display power reset verification Entry 8 entry delay 1 entry delay 2 exit delay interior zone type ENTRY 9 ENTRY 10 Alarm Sounds Use Bell Timeout Respond as Fire Zone Trouble Sounds Chime when ...

Страница 9: ... BR 52 1 BR 53 1 BR 54 1 BR 55 1 BR 56 1 BR 57 1 BR 58 1 BR 59 1 BR 60 1 BR 61 1 BR 62 1 BR 63 1 BR 64 1 BR 95 15 N A N A N A keypad 1 96 09 N A N A N A keypad 3 99 07 N A N A N A keypad NOTES Zone Type see chart on page 12 Report Code enabled if any digit entered as 1st digit Hardwire Type zns 1 8 0 EOL 3 ZD 1 NC 4 DB 2 NO Input Type 2 AW zones 9 48 3 RF zones 9 48 4 UR zones 9 48 5 BR zones 49 6...

Страница 10: ... 80 and 81 Applicable only if Relays and or Powerline Carrier Devices are to be used 79 RELAY POWERLINE CARRIER DEVICE X 10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 11 04 12 05 13 06 14 07 15 08 16 17 On Board Trigger 1 norm output 1 18 On Board...

Страница 11: ...ction 0 off 1 close 2 secs 2 stay closed 3 pulse 4 toggle 5 duration 1 6 duration 2 duration is set in program field 177 Output Number 1 18 Device Type R relay T trigger X X10 ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 23 No Alarm Response 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 24 Silent Burglary 02 Entry Exit 2 07 24 H...

Страница 12: ...on or to a zone containing monitoring devices such as water or temperature sensors Sends a report to the central station and provides a keypad alarm sound No bell output is provided Type 09 Fire Provides a fire alarm on short circuit and a trouble condition on open circuit A fire alarm produces a pulsing bell output This zone type is always active and cannot be bypassed Note Hardwired zone 1 shoul...

Страница 13: ...is faulted all alarm sounding and dialer reporting stops except for fire alarms which immediately terminate the voice session and cause a fire report to be sent When the zone is restored session ended sounding resumes if bell timeout has not expired and reports that were stopped are sent Types 90 93 Installer Defined These zone types can be programmed for various custom responses See data fields 1...

Страница 14: ...7 PERIMETER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIGHT 175 SLIDING 176 SMOKE 178 SONS 179 SOUTH 180 SPRINKLER 182 STATION 184 STORE 185 STORAGE 186 STORY 190 SUPERVISED 191 SUPERVISION 192 SWIMMING 1...

Страница 15: ...Default Templates For 5804 Loop Function Zone Type For 5804BD Loop Function Zone Type TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23 2 Disarm 22 2 No Response 23 3 Arm Away 21 3 Arm Away 21 4 No Response 23 4 Disarm 22 TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24 hour audible 7 TEMPL...

Страница 16: ...00 OHMS PLUS EOLR RESPONSE ZONES 1 8 10 350 OR 700 MSEC PROGRAMMABLE 8 PIN CONNECTOR USED FOR 1361X10 TRANSFORMER CONNECTIONS AND FOR ON BOARD TRIGGERS SEE INSTRUCTIONS 7 8 USE SA4120XM 1 CABLE TIP BROWN THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE ...