First Alert FA168C-GP Скачать руководство пользователя страница 14

– 

14

 –

 

 

ALPHA VOCABULARY LIST  (For Entering Zone Descriptors) 

 

 000 

(Word Space)  

   

– A – 

• 001  AIR

 

• 002  ALARM 

 004 ALLEY 
 005 AMBUSH 

• 006  AREA 
• 007  APARTMENT 
• 009  ATTIC 

 010 AUDIO 

 

 

– B –

 

• 012  BABY 
• 013  BACK 
• 014  BAR 
• 016  BASEMENT 
• 017  BATHROOM 
• 018  BED 
• 019  BEDROOM 

 020 BELL 

• 021  BLOWER 
• 022  BOILER 

 023 BOTTOM 
 025 BREAK 

• 026  BUILDING 

 

 

– C –

 

 028 CABINET 

 

029 CALL

 

 030 CAMERA 
 031 CAR 
 033 CASH 
 034 CCTV 
 035 CEILING 
 036 CELLAR 

• 037  CENTRAL 

 038 CIRCUIT 

• 040  CLOSED 
• 046  COMPUTER 

 047 CONTACT 

 

 

 

– D –

 

• 048  DAUGHTERS 

 049 DELAYED 

• 050  DEN 

 051 DESK 

• 052  DETECTOR 
• 053  DINING

 

 

 054 DISCRIMINATOR 
 055 DISPLAY 

 

• 057  DOOR 
• 059  DOWN 
• 060  DOWNSTAIRS 

 061 DRAWER 

• 062  DRIVEWAY 
• 064  DUCT 

 

 

– E –

 

• 065  EAST 

 066 ELECTRIC 
 067 EMERGENCY 
 068 ENTRY 

• 069  EQUIPMENT 
• 071  EXIT 

 072 EXTERIOR 

 

 

– F –

 

• 073  FACTORY 

 075 FAMILY 

• 076  FATHERS 
• 077  FENCE 
• 079  FIRE 
• 080  FLOOR 

 081 FLOW 
 082 FOIL 

• 083  FOYER 

 084 FREEZER 

• 085  FRONT 

 

 

– G –

 

• 089  GARAGE 
• 090  GAS 

 091 GATE 

• 092  GLASS 

 093 GUEST 
 094 GUN 

 

 

– 

H –

 

• 095  HALL 
• 096  HEAT 

 098 HOLDUP 
 099 HOUSE 
 100 INFRARED 

• 101  INSIDE 

 102 INTERIOR 
 103 INTRUSION 

 

 

 

– J – 

 104 JEWELRY 

 

 

– K –

 

• 105  KITCHEN 

 

 

 

– L –

 

• 106  LAUNDRY 
• 107  LEFT 

 108 LEVEL 

• 109  LIBRARY 
• 110  LIGHT 

 111 LINE 

• 113  LIVING 
• 114  LOADING 

 115 LOCK 
 116 LOOP 
 117 LOW 

• 118  LOWER 

 

 

– M –

 

• 119  MACHINE 

 121 MAIDS 
 122 MAIN 

• 123  MASTER 
• 125  MEDICAL 

 126 MEDICINE 
 128 MONEY 
 129 MONITOR 

• 130  MOTHERS 
• 131  MOTION 

 132 MOTOR 

 

 

– N –

 

• 134  NORTH 

 135 NURSERY 

 

 

– O –

 

• 136  OFFICE 
• 138  OPEN 

 139 OPENING 

• 140  OUTSIDE 

 142 OVERHEAD 

 

 

– P –

 

 143 PAINTING 

• 144  PANIC 

 145 PASSIVE 

• 146  PATIO 

 147 PERIMETER 

• 148  PHONE

 

 150 POINT 
 151 POLICE 
 152 POOL 

• 153  POWER 

 

   

– R –

 

 155 RADIO 

 

• 156  REAR 

 157 RECREATION 
 159 REFRIGERATION 
 160 RF 

• 161  RIGHT 
• 162  ROOM 

 163 ROOF 

 

 

– S –

 

 164 SAFE 
 165 SCREEN 
 166 SENSOR 

• 167  SERVICE 
• 168  SHED 

 169 SHOCK 

• 170  SHOP 

 171 SHORT 

• 173  SIDE 

 174 SKYLIGHT 
 175 SLIDING 

• 176  SMOKE 
• 178  SONS 
• 179  SOUTH 

 180 SPRINKLER 

• 182  STATION

 

 184 STORE 

• 185  STORAGE 

 186 STORY 
 190 SUPERVISED 
 191 SUPERVISION 
 192 SWIMMING 
 193 SWITCH 

 

 

– T –

 

 194 TAMPER 
 196 TELCO 
 197 TELEPHONE 

• 199  TEMPERATURE 

 200 THERMOSTAT 

• 201  TOOL 

 202 TRANSMITTER 

   

– U –

 

• 205  UP 
• 206  UPPER 
• 207  UPSTAIRS 

 

• 208  UTILITY 

 

 

 

 

– V –

 

 209 VALVE 
 210 VAULT 
 212 VOLTAGE 

 

 

– W –

 

 213 WALL 
 214 WAREHOUSE 

• 216  WEST 
• 217  WINDOW 
• 219  WING 

 220 WIRELESS 

 

 

– X –

 

 222 XMITTER 

 

 

– Y –

 

 223 YARD 

 

 

– Z –

 

 224 ZONE 

(No.) 

• 225  ZONE 
• 226  0 
• 227  1 
• 228  1ST 
• 229  2 
• 230  2ND 
• 231  3 
• 232  3RD 
• 233  4 
• 234  4TH 
• 235  5 
• 236  5TH 
• 237  6 
• 238  6TH 
• 239  7 
• 240  7TH 
• 241  8 
• 242  8TH 
• 243  9 
• 244  9TH 

 

 

245  Custom Word #1 

 

246  Custom Word #2 

 

247  Custom Word #3 

 

248  Custom Word #4 

 

249  Custom Word #5  

 

250  Custom Word #6 

 

251  Custom Word #7 

 

252  Custom Word #8 

 

253  Custom Word #9 

 

254  Custom Word #10  

 

Note:

 Bulleted 

(

) words in 

boldface type

 are those that are also available for use by the 4285/4286 Phone Module. If 

using a Phone module, and words other than these are selected for Alpha descriptors, the module will not provide 
annunciation of those words. 

CHARACTER (ASCII) CHART (For Adding Custom Words)

 

 

32 (space) 
33 ! 
34 " 
35 # 
36 $ 
37 % 
38 & 
39 ' 
40 ( 

41 ) 
42 * 
43 + 
44 , 
45 – 
46 . 
47 / 
48 0 
49 1 

50 2 
51 3 
52 4 
53 5 
54 6 
55 7 
56 8 
57 9 
58 : 

59 ; 
60 < 
61 = 
62 > 
63 ? 
64 @ 
65 A 
66 B 
67 C 

68 D 
69 E 
70 F 
71 G 
72 H 
73 I 
74 J 
75 K 
76 L 

77 M 
78 N 
79 O 
80 P 
81 Q 
82 R 
83 S 
84 T 
85 U 
86 V 
87 W 

88 X 
89 Y 
90 Z 

 

 
 

Содержание FA168C-GP

Страница 1: ... Sy ys st te em m Programming Guide ON OFF ARMED READY A B C D 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY FA260 R ARMED READY FA560 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY R AWAY STAY PAGE K5305 5GPPRV2 9 04 Rev A ...

Страница 2: ...9 or 4204 Relay modules Powerline Carrier devices or on board triggers 81 Zone List Programming Zone Lists for relay powerline carrier activation chime zones pager zones etc 82 Alpha Programming Zone alpha descriptors INITIALIZE DOWNLOAD and RESET DEFAULTS 96 Initializes download ID and subscriber account number 97 Sets all data fields to original factory default values TO EXIT PROGRAMMING MODE 98...

Страница 3: ... must be minimum 16 min option 4 34 EXIT DELAY 60 60 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 secs 97 120 secs 98 180 secs 99 240 secs SIA Installations minimum exit delay is 45 seconds UL see inst instr for requirements 35 ENTRY DELAY 1 zone type 01 30 30 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 seconds 97 120 seconds SIA Installations 98 180 ...

Страница 4: ...st be 15 max 55 DYNAMIC SIGNALING PRIORITY 0 0 Primary Dialer first 1 Long Range Radio first For UL Commercial Burglary installations that use a DACT and LRR this field must be 0 56 57 58 Menu Modes These are Menu Mode commands not data fields for Zone Programming Function Key Programming and Expert Mode Zone Programming respectively See page 2 and their respective sections in the Installation and...

Страница 5: ...y disabled if field 199 is set to 1 2 digit display 87 MISC FAULT DELAY TIME used with Configurable Zone Types digit 6 0 0 15 seconds 6 2 1 2 min 12 8 min 1 30 seconds 7 3 min 13 10 min 2 45 seconds 8 4 min 14 12 min 3 60 seconds 9 5 min 15 15 min 4 90 seconds 10 6 min 5 2 minutes 11 7 min UL may only be used on non burglar alarm non fire alarm zones when used in fire and or UL burglar alarm insta...

Страница 6: ...ional prefix characters up to 16 digits 0 9 11 12 13 2 second pause 165 PAGER 2 REPORT OPTIONS 0 0 0 Part 1 Part 2 common See field 162 for reporting options Select for each partition use zone list 10 if using options 12 or 13 166 PAGER 3 PHONE No Enter up to 20 digits 0 9 11 12 13 2 second pause 167 PAGER 3 CHARACTERS Enter the optional prefix characters up to 16 digits 0 9 11 12 13 2 second paus...

Страница 7: ... 2 AUI 1 Must set AUI address to 1 AUI 2 Must set AUI address to 2 Enter each touch screen AUI device s home partition 0 disabled 1 partition 1 2 partition 2 3 partition 3 common NOTE Use of AUI does not affect the number of standard keypads supported AUI Compatibility Note To ensure proper AUI device operation connect only to controls having microprocessor version 3 0 or higher and use AUI device...

Страница 8: ... disarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault by code OFF 12 verification see zone type 16 0 no 1 delay 1 2 delay 2 0 no 4 use exit delay 0 no 8 yes see note 2 Entry 7 fault display power reset verification Entry 8 entry delay 1 entry delay 2 exit delay interior zone type ENTRY 9 ENTRY 10 Alarm Sounds Use Bell Timeout Respond as Fire Zone Trouble Sounds Chime when ...

Страница 9: ... BR 52 1 BR 53 1 BR 54 1 BR 55 1 BR 56 1 BR 57 1 BR 58 1 BR 59 1 BR 60 1 BR 61 1 BR 62 1 BR 63 1 BR 64 1 BR 95 15 N A N A N A keypad 1 96 09 N A N A N A keypad 3 99 07 N A N A N A keypad NOTES Zone Type see chart on page 12 Report Code enabled if any digit entered as 1st digit Hardwire Type zns 1 8 0 EOL 3 ZD 1 NC 4 DB 2 NO Input Type 2 AW zones 9 48 3 RF zones 9 48 4 UR zones 9 48 5 BR zones 49 6...

Страница 10: ... 80 and 81 Applicable only if Relays and or Powerline Carrier Devices are to be used 79 RELAY POWERLINE CARRIER DEVICE X 10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 11 04 12 05 13 06 14 07 15 08 16 17 On Board Trigger 1 norm output 1 18 On Board...

Страница 11: ...ction 0 off 1 close 2 secs 2 stay closed 3 pulse 4 toggle 5 duration 1 6 duration 2 duration is set in program field 177 Output Number 1 18 Device Type R relay T trigger X X10 ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 23 No Alarm Response 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 24 Silent Burglary 02 Entry Exit 2 07 24 H...

Страница 12: ...on or to a zone containing monitoring devices such as water or temperature sensors Sends a report to the central station and provides a keypad alarm sound No bell output is provided Type 09 Fire Provides a fire alarm on short circuit and a trouble condition on open circuit A fire alarm produces a pulsing bell output This zone type is always active and cannot be bypassed Note Hardwired zone 1 shoul...

Страница 13: ...is faulted all alarm sounding and dialer reporting stops except for fire alarms which immediately terminate the voice session and cause a fire report to be sent When the zone is restored session ended sounding resumes if bell timeout has not expired and reports that were stopped are sent Types 90 93 Installer Defined These zone types can be programmed for various custom responses See data fields 1...

Страница 14: ...7 PERIMETER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIGHT 175 SLIDING 176 SMOKE 178 SONS 179 SOUTH 180 SPRINKLER 182 STATION 184 STORE 185 STORAGE 186 STORY 190 SUPERVISED 191 SUPERVISION 192 SWIMMING 1...

Страница 15: ...Default Templates For 5804 Loop Function Zone Type For 5804BD Loop Function Zone Type TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23 2 Disarm 22 2 No Response 23 3 Arm Away 21 3 Arm Away 21 4 No Response 23 4 Disarm 22 TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24 hour audible 7 TEMPL...

Страница 16: ...00 OHMS PLUS EOLR RESPONSE ZONES 1 8 10 350 OR 700 MSEC PROGRAMMABLE 8 PIN CONNECTOR USED FOR 1361X10 TRANSFORMER CONNECTIONS AND FOR ON BOARD TRIGGERS SEE INSTRUCTIONS 7 8 USE SA4120XM 1 CABLE TIP BROWN THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE ...

Отзывы: