DOWNLOAD INFORMATION (

94, 

95) 

94

  DOWNLOAD PHONE No.

 

     |      |     |     |      |     |     |     |     |     |     |     |     |     |     |     |     |     |     |        

 

[18006886186] 

Enter up to 20 digits, 0–9; #+11 for '

'; #+12 for '#'; #+13 for a 2-second pause. Do not fill unused 

spaces. If fewer than 20 digits, exit field by pressing 

. To clear entries from field, press 

94

 

 

 UL: downloading may be performed only if a technician is at the site. 

 

95

  RING COUNT FOR DOWNLOADING 

     [15] 

 

NOTE:

 Do not enter “0” if using 

4285/4286 Phone Module. 

0 = Disable Station Initiated Download; 
1–14 = number of rings (1–9, # +10 =10, # +11 =11, 
# +12 =12, # +13 =13, # +14 =14); 
15 = answering machine defeat (# +15 =15).

 

∗∗∗∗

96, 

∗∗∗∗

97    Initialize/Reset Defaults 

These are commands, not data fields. See page 2. 

∗∗∗∗

98, *99   Exit Commands 

These are commands, not data fields. See page 2. 

 

PAGER OPTIONS (*160-*172) 

160

  PAGER 1 PHONE No. 

     |      |     |     |      |     |     |     |     |     |     |     |     |     |     |     |     |     |     |       

 

 

 

Enter up to 20 digits. 0–9; #+11 = '

'; #+12 = '#'; #+13 = 2-second pause. 

161

  PAGER 1 CHARACTERS

 

     |     |     |     |     |     |     |     |     |     |     |     |     |     |     |        

 

 

Enter the optional prefix characters, up to 16 digits.  

 

 

0–9; #+11 = '

'; #+12 = '#'; #+13 = 2-second pause.  

 

162

  PAGER 1 REPORT OPTIONS 

 

 

  

 

 

 

  

  

 

 

  

  

Part. 1  Part. 2  common 
[0,0,0]

 

For each partition, select from the following options: 
0 =  no reports sent 
1 =  Open/closes all users 
4 =  All alarms and troubles 
5 =  All alarms / troubles, and open/closes for all users 
12 = Alarms / troubles for zones entered in zone list 9 
13 = Alarms / troubles for zones entered in zone list 9, 

and open\closes for all users

 

163

  PAGER 2 PHONE No. 

     |      |     |     |      |     |     |     |     |     |     |     |     |     |     |     |     |     |     |       

 

 

 

Enter up to 20 digits. 0–9; #+11 = '

'; #+12 = '#'; #+13 = 2-second pause. 

164

  PAGER 2 CHARACTERS

 

     |     |     |     |     |     |     |     |     |     |     |     |     |     |     |        

 

 

Enter the optional prefix characters, up to 16 digits.  

 

 

0–9; #+11 = '

'; #+12 = '#'; #+13 = 2-second pause.  

165

  PAGER 2 REPORT OPTIONS 

 

 

  

 

 

 

  

  

 

 

  

  [0,0,0] 

Part. 1  Part. 2  common

 

See field *162 for reporting options. Select for each 
partition (use zone list 10 if using options 12 or 13).

 

 

166

  PAGER 3 PHONE No. 

     |      |     |     |      |     |     |     |     |     |     |     |     |     |     |     |     |     |     |        

 

 

Enter up to 20 digits. 0–9; #+11 = '

'; #+12 = '#'; #+13 = 2-second pause. 

167

  PAGER 3 CHARACTERS 

     |     |     |     |     |     |     |     |     |     |     |     |     |     |     |        

 

 

Enter the optional prefix characters, up to 16 digits.  

 

 

0–9; #+11 = '

'; #+12 = '#'; #+13 = 2-second pause.  

168

  PAGER 3 REPORT OPTIONS 

 

 

  

 

 

 

  

  

 

 

  

  0,0,0] 

Part. 1  Part. 2  common

 

See field *162 for reporting options. Select for each 
partition (use zone list 11 if using options 12 or 13).

 

 

169

  PAGER 4 PHONE No. 

     |      |     |     |      |     |     |     |     |     |     |     |     |     |     |     |     |     |     |       

 

 

 

Enter up to 20 digits. 0–9; #+11 = '

'; #+12 = '#'; #+13 = 2-second pause. 

170

  PAGER 4 CHARACTERS

 

     |     |     |     |     |     |     |     |     |     |     |     |     |     |     |        

 

 

Enter the optional prefix characters, up to 16 digits.  

 

 

0–9; #+11 = '

'; #+12 = '#'; #+13 = 2-second pause.  

171

  PAGER 4 REPORT OPTIONS 

 

 

  

 

 

 

  

  

 

 

  

  [0,0,0] 

Part. 1  Part. 2  common

 

See field *162 for reporting options. Select for each 
partition (use zone list 12 if using options 12 or 13).

 

172 

PAGER DELAY OPTION FOR ALARMS 

     [3]

 

0 = none, 1 = 1 minute,  2 = 2 minutes, 3 = 3  minutes 
This delay is for ALL pagers in the system.

 

MISCELLANEOUS SYSTEM FIELDS (*174-*181) 

174 

CLEAN ME REPORTING OPTIONS 

 

(for ESL smoke detectors)

 

     [0]

 

0 = disable; 1 = Clean Me signal reports; 

Note: 

 If Clean Me is enabled, you must enter “3” in 

field 

56 programming for zone 1 response time.

 

 

 

 

177 

DEVICE DURATION 1, 2 

 

(used in *80 Menu mode-Device Actions 5/6)

 

                [0] [0] 

    1 

2

 

0 = 15 seconds 

6 = 2-1/2 min 

#+11 = 7 min 

1 = 30 seconds 

7 = 3 min 

#+12 = 8 min 

2 = 45 seconds 

8 = 4 min 

#+13 = 10 min 

3 = 60 seconds 

9 = 5 min 

#+14 = 12 min 

4 = 90 seconds 

#+10 = 6 min 

#+15 = 15 min 

5 = 2 minutes 

 

 

 

 

181  

50/60 HERTZ AC OPERATION 

     [0]

 

0 = 60 Hz; 1 = 50 Hz

 

Содержание FA168C-GP

Страница 1: ... Sy ys st te em m Programming Guide ON OFF ARMED READY A B C D 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY FA260 R ARMED READY FA560 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY R AWAY STAY PAGE K5305 5GPPRV2 9 04 Rev A ...

Страница 2: ...9 or 4204 Relay modules Powerline Carrier devices or on board triggers 81 Zone List Programming Zone Lists for relay powerline carrier activation chime zones pager zones etc 82 Alpha Programming Zone alpha descriptors INITIALIZE DOWNLOAD and RESET DEFAULTS 96 Initializes download ID and subscriber account number 97 Sets all data fields to original factory default values TO EXIT PROGRAMMING MODE 98...

Страница 3: ... must be minimum 16 min option 4 34 EXIT DELAY 60 60 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 secs 97 120 secs 98 180 secs 99 240 secs SIA Installations minimum exit delay is 45 seconds UL see inst instr for requirements 35 ENTRY DELAY 1 zone type 01 30 30 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 seconds 97 120 seconds SIA Installations 98 180 ...

Страница 4: ...st be 15 max 55 DYNAMIC SIGNALING PRIORITY 0 0 Primary Dialer first 1 Long Range Radio first For UL Commercial Burglary installations that use a DACT and LRR this field must be 0 56 57 58 Menu Modes These are Menu Mode commands not data fields for Zone Programming Function Key Programming and Expert Mode Zone Programming respectively See page 2 and their respective sections in the Installation and...

Страница 5: ...y disabled if field 199 is set to 1 2 digit display 87 MISC FAULT DELAY TIME used with Configurable Zone Types digit 6 0 0 15 seconds 6 2 1 2 min 12 8 min 1 30 seconds 7 3 min 13 10 min 2 45 seconds 8 4 min 14 12 min 3 60 seconds 9 5 min 15 15 min 4 90 seconds 10 6 min 5 2 minutes 11 7 min UL may only be used on non burglar alarm non fire alarm zones when used in fire and or UL burglar alarm insta...

Страница 6: ...ional prefix characters up to 16 digits 0 9 11 12 13 2 second pause 165 PAGER 2 REPORT OPTIONS 0 0 0 Part 1 Part 2 common See field 162 for reporting options Select for each partition use zone list 10 if using options 12 or 13 166 PAGER 3 PHONE No Enter up to 20 digits 0 9 11 12 13 2 second pause 167 PAGER 3 CHARACTERS Enter the optional prefix characters up to 16 digits 0 9 11 12 13 2 second paus...

Страница 7: ... 2 AUI 1 Must set AUI address to 1 AUI 2 Must set AUI address to 2 Enter each touch screen AUI device s home partition 0 disabled 1 partition 1 2 partition 2 3 partition 3 common NOTE Use of AUI does not affect the number of standard keypads supported AUI Compatibility Note To ensure proper AUI device operation connect only to controls having microprocessor version 3 0 or higher and use AUI device...

Страница 8: ... disarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault by code OFF 12 verification see zone type 16 0 no 1 delay 1 2 delay 2 0 no 4 use exit delay 0 no 8 yes see note 2 Entry 7 fault display power reset verification Entry 8 entry delay 1 entry delay 2 exit delay interior zone type ENTRY 9 ENTRY 10 Alarm Sounds Use Bell Timeout Respond as Fire Zone Trouble Sounds Chime when ...

Страница 9: ... BR 52 1 BR 53 1 BR 54 1 BR 55 1 BR 56 1 BR 57 1 BR 58 1 BR 59 1 BR 60 1 BR 61 1 BR 62 1 BR 63 1 BR 64 1 BR 95 15 N A N A N A keypad 1 96 09 N A N A N A keypad 3 99 07 N A N A N A keypad NOTES Zone Type see chart on page 12 Report Code enabled if any digit entered as 1st digit Hardwire Type zns 1 8 0 EOL 3 ZD 1 NC 4 DB 2 NO Input Type 2 AW zones 9 48 3 RF zones 9 48 4 UR zones 9 48 5 BR zones 49 6...

Страница 10: ... 80 and 81 Applicable only if Relays and or Powerline Carrier Devices are to be used 79 RELAY POWERLINE CARRIER DEVICE X 10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 11 04 12 05 13 06 14 07 15 08 16 17 On Board Trigger 1 norm output 1 18 On Board...

Страница 11: ...ction 0 off 1 close 2 secs 2 stay closed 3 pulse 4 toggle 5 duration 1 6 duration 2 duration is set in program field 177 Output Number 1 18 Device Type R relay T trigger X X10 ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 23 No Alarm Response 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 24 Silent Burglary 02 Entry Exit 2 07 24 H...

Страница 12: ...on or to a zone containing monitoring devices such as water or temperature sensors Sends a report to the central station and provides a keypad alarm sound No bell output is provided Type 09 Fire Provides a fire alarm on short circuit and a trouble condition on open circuit A fire alarm produces a pulsing bell output This zone type is always active and cannot be bypassed Note Hardwired zone 1 shoul...

Страница 13: ...is faulted all alarm sounding and dialer reporting stops except for fire alarms which immediately terminate the voice session and cause a fire report to be sent When the zone is restored session ended sounding resumes if bell timeout has not expired and reports that were stopped are sent Types 90 93 Installer Defined These zone types can be programmed for various custom responses See data fields 1...

Страница 14: ...7 PERIMETER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIGHT 175 SLIDING 176 SMOKE 178 SONS 179 SOUTH 180 SPRINKLER 182 STATION 184 STORE 185 STORAGE 186 STORY 190 SUPERVISED 191 SUPERVISION 192 SWIMMING 1...

Страница 15: ...Default Templates For 5804 Loop Function Zone Type For 5804BD Loop Function Zone Type TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23 2 Disarm 22 2 No Response 23 3 Arm Away 21 3 Arm Away 21 4 No Response 23 4 Disarm 22 TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24 hour audible 7 TEMPL...

Страница 16: ...00 OHMS PLUS EOLR RESPONSE ZONES 1 8 10 350 OR 700 MSEC PROGRAMMABLE 8 PIN CONNECTOR USED FOR 1361X10 TRANSFORMER CONNECTIONS AND FOR ON BOARD TRIGGERS SEE INSTRUCTIONS 7 8 USE SA4120XM 1 CABLE TIP BROWN THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE ...

Отзывы: