5800 Series Transmitter Input Loop Identification 

•  All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. 

Each 

of the inputs requires its own programming zone 

(e.g., a 5804's four inputs require four programming zones). 

 

•  Transmitter inputs entered as: 

"RF" (Supervised RF) Type 

send periodic check-in 

signals, as well as fault, restore and low battery signals. 
The transmitter must remain within the receiver's range. 

“UR" (Unsupervised RF) Type 

send all the signals that 

the "RF" Type does, but the control does not supervise 
the check-in signals. The transmitter may, therefore, be 
carried off-premises. 

"BR" (Unsupervised Button RF) Type

 only send fault 

signals. They do not send restore or check-in signals. 
They will indicate a low battery condition when tested or 
activated normally. The transmitter may be carried off-
premises. 

 

Note

: For information on any transmitter not shown 

above, refer to the instructions accompanying that 
transmitter for details regarding loop numbers, etc. 

UL NOTE

The following transmitters are not intended for 

use in UL installations:  5802MN, 5802MN2, 5804, 5804BD, 
5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850. 
The 5827BD and 5800TM can be used in UL Listed 
Residential Burglar installations.

 

 

5802MN

ENROLL AS

"UR" OR "RF"

LOOP

1

V20P-006-V0

5817

ENROLL AS "RF"

5890

ENROLL AS

"RF" OR "RM"

LOOP 1

5808

ENROLL AS "RF"

LOOP 1

5809

ENROLL AS "RF"

5850 (GBD)

ENROLL AS "RF"

(Green)

(Red)

(Yellow)

5 8 0 4 B D

ENROLL AS "BR"

LOOP 4
YOU MUST
ENROLL
THIS BUTTON

SET

HOUSE

CODE

LOOP 3

LOOP 1

LOOP 2

5804

ENROLL AS "BR"

ON

5816MN

ENROLL AS "RF"

LOOP 2
(REED)

5816

ENROLL AS "RF"

LOOP 1
(TERMINALS)

LOOP 2
(REED)

LOOP 3

(TERMINALS)

5819S (WHS & BRS)

ENROLL AS "RF"

LOOP 1
(INTERNAL
SHOCK
SENSOR

LOOP 2

(REED)

5 8 1 9

ENROLL AS "RF"

LOOP 2

(REED)

LOOP 3

(TERMINALS)

LOOP 1
(TERMINALS)

5 8 0 1

ENROLL AS

"UR" OR "RF"

LOOP 3

LOOP 1

LOOP 2

LOOP 4

YOU MUST

ENROLL

THIS

BUTTON

LOOP 1

LOOP 2

LOOP 4

YOU MUST

ENROLL

THIS

BUTTON

LOOP 3

LOOP

1

MOTION

LOOP 2
(AUX.
CENTER)

LOOP 1
(PRIMARY)

LOOP 3
(AUX.
RIGHT)

LOOP 1
(TERMINALS)

ALTERNATE

POSITION

FOR LOOP 2

OFF

 

Wireless Key Predefined Default Templates 

For 5804

 

Loop Function 

Zone 

Type 

For 5804BD Loop 

Function  Zone 

Type 

TEMPLATE 1 

No Response 

23 

TEMPLATE 4 

No Response 

23 

 2 

Disarm 

22 

 

No 

Response 

23 

 

Arm Away 

21 

 

Arm Away 

21 

 4 

No 

Response 

23 

 

Disarm 

22 

TEMPLATE 2 

No Response 

23 

TEMPLATE 5 

No Response 

23 

 2 

Disarm 

22 

 

 

Arm 

Stay 

20 

 

Arm Away 

21 

   

Arm Away 

21 

 4 

Arm 

Stay 

20 

 

 

Disarm 

22 

TEMPLATE 3 

24-hour audible 

TEMPLATE 6 

24-hour audible 

 2 

Disarm 

22 

 

 

Arm 

Stay 

20 

 

Arm Away 

21 

   

Arm Away 

21 

 4 

Arm 

Stay 

20 

 

 

Disarm 

22 

 

Table of Device Addresses 

This Device 

Uses Address  Reports as†† Enabled By… 

RF Receiver

 

00

 

100

 

*56 zone programming: input device type entry

 

Long Range Radio

 

03

 

103

 

automatic if output to long range radio field *29 enabled

 

4286 Voice Module

 

04

 

104

 

automatic if phone module access code field *28 enabled

 

Zone Expanders (4219/4229): 

module 1 (for zones 09 - 16)
module 2 (for zones 17 - 24)
module 3 (for zones 25 - 32)
module 4 zones 33 - 40 
module 5 zones 41 - 48

 

 

07 
08 
09 
10 
11

 

 

107 
108 
109 
110 
111

 

*56 zone programming: input device type entry, then:

 

automatic if zone no. 9-16 entered as AW type or relay assigned 
automatic if zone no. 17-24 entered as AW type or relay assigned 
automatic if zone no. 25-32 entered as AW type or relay assigned 
automatic if zone no. 33-40 entered as AW type or relay assigned 
automatic if zone no. 41-48 entered as AW type or relay assigned

 

Relay Modules (4204): 

module 1 
module 2 
module 3 
module 4

 

 

12

 

13 
14 
15

 

 

112

 

113 
114 
115

 

*79 output device programming: device address prompt:

 

entered at device address prompt

 

entered at device address prompt 
entered at device address prompt 
entered at device address prompt

 

Keypads:

 

keypad 1

 

keypad 2

 

keypad 3

 

keypad 4

 

keypad 5

 

keypad 6

 

keypad 7

 

keypad 8

 

 

16

 

17

 

18

 

19

 

20

 

21

 

22 
23

 

 

n/a

 

n/a

 

n/a

 

n/a

 

n/a

 

n/a

 

n/a  
n/a

 

data field programming as listed below: 

always enabled, all sounds enabled. 
data field *190 
data field *191 
data field *192 
data field *193 
data field *194 
data field *195 
data field *196

 

5800TM Module

 

28

 

n/a

 

automatic

 

††

 Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device 

reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.

 

Содержание FA168C-GP

Страница 1: ... Sy ys st te em m Programming Guide ON OFF ARMED READY A B C D 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY FA260 R ARMED READY FA560 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY R AWAY STAY PAGE K5305 5GPPRV2 9 04 Rev A ...

Страница 2: ...9 or 4204 Relay modules Powerline Carrier devices or on board triggers 81 Zone List Programming Zone Lists for relay powerline carrier activation chime zones pager zones etc 82 Alpha Programming Zone alpha descriptors INITIALIZE DOWNLOAD and RESET DEFAULTS 96 Initializes download ID and subscriber account number 97 Sets all data fields to original factory default values TO EXIT PROGRAMMING MODE 98...

Страница 3: ... must be minimum 16 min option 4 34 EXIT DELAY 60 60 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 secs 97 120 secs 98 180 secs 99 240 secs SIA Installations minimum exit delay is 45 seconds UL see inst instr for requirements 35 ENTRY DELAY 1 zone type 01 30 30 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 seconds 97 120 seconds SIA Installations 98 180 ...

Страница 4: ...st be 15 max 55 DYNAMIC SIGNALING PRIORITY 0 0 Primary Dialer first 1 Long Range Radio first For UL Commercial Burglary installations that use a DACT and LRR this field must be 0 56 57 58 Menu Modes These are Menu Mode commands not data fields for Zone Programming Function Key Programming and Expert Mode Zone Programming respectively See page 2 and their respective sections in the Installation and...

Страница 5: ...y disabled if field 199 is set to 1 2 digit display 87 MISC FAULT DELAY TIME used with Configurable Zone Types digit 6 0 0 15 seconds 6 2 1 2 min 12 8 min 1 30 seconds 7 3 min 13 10 min 2 45 seconds 8 4 min 14 12 min 3 60 seconds 9 5 min 15 15 min 4 90 seconds 10 6 min 5 2 minutes 11 7 min UL may only be used on non burglar alarm non fire alarm zones when used in fire and or UL burglar alarm insta...

Страница 6: ...ional prefix characters up to 16 digits 0 9 11 12 13 2 second pause 165 PAGER 2 REPORT OPTIONS 0 0 0 Part 1 Part 2 common See field 162 for reporting options Select for each partition use zone list 10 if using options 12 or 13 166 PAGER 3 PHONE No Enter up to 20 digits 0 9 11 12 13 2 second pause 167 PAGER 3 CHARACTERS Enter the optional prefix characters up to 16 digits 0 9 11 12 13 2 second paus...

Страница 7: ... 2 AUI 1 Must set AUI address to 1 AUI 2 Must set AUI address to 2 Enter each touch screen AUI device s home partition 0 disabled 1 partition 1 2 partition 2 3 partition 3 common NOTE Use of AUI does not affect the number of standard keypads supported AUI Compatibility Note To ensure proper AUI device operation connect only to controls having microprocessor version 3 0 or higher and use AUI device...

Страница 8: ... disarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault by code OFF 12 verification see zone type 16 0 no 1 delay 1 2 delay 2 0 no 4 use exit delay 0 no 8 yes see note 2 Entry 7 fault display power reset verification Entry 8 entry delay 1 entry delay 2 exit delay interior zone type ENTRY 9 ENTRY 10 Alarm Sounds Use Bell Timeout Respond as Fire Zone Trouble Sounds Chime when ...

Страница 9: ... BR 52 1 BR 53 1 BR 54 1 BR 55 1 BR 56 1 BR 57 1 BR 58 1 BR 59 1 BR 60 1 BR 61 1 BR 62 1 BR 63 1 BR 64 1 BR 95 15 N A N A N A keypad 1 96 09 N A N A N A keypad 3 99 07 N A N A N A keypad NOTES Zone Type see chart on page 12 Report Code enabled if any digit entered as 1st digit Hardwire Type zns 1 8 0 EOL 3 ZD 1 NC 4 DB 2 NO Input Type 2 AW zones 9 48 3 RF zones 9 48 4 UR zones 9 48 5 BR zones 49 6...

Страница 10: ... 80 and 81 Applicable only if Relays and or Powerline Carrier Devices are to be used 79 RELAY POWERLINE CARRIER DEVICE X 10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 11 04 12 05 13 06 14 07 15 08 16 17 On Board Trigger 1 norm output 1 18 On Board...

Страница 11: ...ction 0 off 1 close 2 secs 2 stay closed 3 pulse 4 toggle 5 duration 1 6 duration 2 duration is set in program field 177 Output Number 1 18 Device Type R relay T trigger X X10 ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 23 No Alarm Response 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 24 Silent Burglary 02 Entry Exit 2 07 24 H...

Страница 12: ...on or to a zone containing monitoring devices such as water or temperature sensors Sends a report to the central station and provides a keypad alarm sound No bell output is provided Type 09 Fire Provides a fire alarm on short circuit and a trouble condition on open circuit A fire alarm produces a pulsing bell output This zone type is always active and cannot be bypassed Note Hardwired zone 1 shoul...

Страница 13: ...is faulted all alarm sounding and dialer reporting stops except for fire alarms which immediately terminate the voice session and cause a fire report to be sent When the zone is restored session ended sounding resumes if bell timeout has not expired and reports that were stopped are sent Types 90 93 Installer Defined These zone types can be programmed for various custom responses See data fields 1...

Страница 14: ...7 PERIMETER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIGHT 175 SLIDING 176 SMOKE 178 SONS 179 SOUTH 180 SPRINKLER 182 STATION 184 STORE 185 STORAGE 186 STORY 190 SUPERVISED 191 SUPERVISION 192 SWIMMING 1...

Страница 15: ...Default Templates For 5804 Loop Function Zone Type For 5804BD Loop Function Zone Type TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23 2 Disarm 22 2 No Response 23 3 Arm Away 21 3 Arm Away 21 4 No Response 23 4 Disarm 22 TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24 hour audible 7 TEMPL...

Страница 16: ...00 OHMS PLUS EOLR RESPONSE ZONES 1 8 10 350 OR 700 MSEC PROGRAMMABLE 8 PIN CONNECTOR USED FOR 1361X10 TRANSFORMER CONNECTIONS AND FOR ON BOARD TRIGGERS SEE INSTRUCTIONS 7 8 USE SA4120XM 1 CABLE TIP BROWN THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE ...