Zone Type Definitions

 

Type 00 

Zone Not Used

 

Use this zone type if the zone is not used.  

Type 01 

Entry/Exit Burglary #1

 

 

  Assign to zones that are used for primary entry and exit. 

  Provides entry delay if the control is armed in the Away or Stay modes.  

  No entry delay is provided when the panel is armed in the Instant mode.  

  Entry delay #1 is programmable for each partition. 

   Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is 

independently programmable. 

Type 02 

Entry/Exit Burglary #2

 

  Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.  

  Provides a secondary entry delay, in same manner as entry delay #1.  

  Entry delay #2 is programmable for each partition. 

  Exit delay is same as described for Type 01. 

Type 03 

Perimeter Burglary 

  Assign to all sensors or contacts on exterior doors and windows. 

  Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, Instant, or 

Maximum modes.  

Type 04 

Interior Follower 

  Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon 

entry (to and from the keypad). 

  Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first. 

Otherwise this zone type gives an instant alarm.  

  Active when the panel is armed in the Away mode.  

  Bypassed automatically when the panel is armed in the Stay or Instant modes.  

Type 05 

Trouble by Day/ 

Alarm by Night 

  Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering a 

sensitive area such as a stock room, drug supply room, etc.  

  Can also be used on a sensor or contact in an area where immediate notification of an entry is desired. 

  Provides an instant alarm if faulted when armed in the Away, Stay, Instant, or Maximum (night) modes.  

  During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a 

central station report, if desired).  

Type 06 

24-hour Silent Alarm 

  Usually assigned to a zone containing an emergency button. 

  Sends a report to the central station but provides no keypad display or sounding.  

Type 07 

24-hour Audible Alarm 

  Assign to a zone that has an emergency button. 

  Sends a report to the central station, and provides a keypad alarm sound, and an audible external alarm.  

Type 08 
24-hour  

Auxiliary Alarm 

  Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as water 

or temperature sensors. 

  Sends a report to the central station and provides a keypad alarm sound. 

(No bell output is provided.)

  

Type 09 

Fire 

 

  Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a 

pulsing bell output.  

  This zone type is always active and cannot be bypassed.

  

Note: 

Hardwired zone 1 should be used with 2-wire smoke detectors; zones 2-8 can be used with 4-wire 
smoke detectors; any wireless zone can be used as a fire zone. 

Type 10 

Interior w/Delay 

  Provides entry delay (using the programmed entry time), if tripped when the panel is armed in Away mode.  

  Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit 

delay zone was tripped first.  

  Bypassed when the panel is armed in the Stay or Instant modes.  

Type 12 

Monitor Zone 

  Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "

ALARM-24 

Hr. Non-Burg. -#XXX 

" (where XXX is the zone number) will be sent to the Central Station. The system 

keypad will display a “check” message indicating the appropriate zone (but keypad beeping does not 
occur). Upon restoral of the zone, the message, "

RESTORE-24 Hr. Non-Burg. -#XXX 

" will be sent to the 

Central Station.  

  The “check” message will automatically disappear from the keypad dynamically when the zone restores; a 

user code + off sequence is not needed to reset the zone.  

  Faults of this zone type are independent of the system, and can exist at the time of arming without 

interference. 

  Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.” 

Type 14 

Carbon Monoxide 

  Assigned to any zone with a carbon monoxide detector.   

  The bell output will pulse when this zone type is alarmed.  

  Always active and cannot be bypassed. 

Type 15 

24-Hour 

Medical/Personal 

Emergency 

  Usually assigned to a zone containing an emergency button.   

  Sends report to the central station (Contact ID event code “100”) and provides an alarm sound at the 

keypad

 (no bell output is provided)

.  

  UL: may not use this zone type in UL installations. 

Type 16 

Fire w/Verification 

  Provides a fire alarm when zone is shorted, but only after alarm verified.  

  System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit 

within 90 seconds triggers fire alarm. 

  Provides a trouble response when zone is open. 

Type 20 

Arm-Stay 

  Arms the system in Stay mode when the zone is activated.  

  Pushbutton units send the user number to the central station when arming or disarming. 

  User code for button must be assigned. 

Содержание FA168C-GP

Страница 1: ... Sy ys st te em m Programming Guide ON OFF ARMED READY A B C D 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY FA260 R ARMED READY FA560 6 4 7 BYPASS 9CHIME 3STAY 5TEST 8CODE 0 2AWAY 1OFF MAX INSTANT READY R AWAY STAY PAGE K5305 5GPPRV2 9 04 Rev A ...

Страница 2: ...9 or 4204 Relay modules Powerline Carrier devices or on board triggers 81 Zone List Programming Zone Lists for relay powerline carrier activation chime zones pager zones etc 82 Alpha Programming Zone alpha descriptors INITIALIZE DOWNLOAD and RESET DEFAULTS 96 Initializes download ID and subscriber account number 97 Sets all data fields to original factory default values TO EXIT PROGRAMMING MODE 98...

Страница 3: ... must be minimum 16 min option 4 34 EXIT DELAY 60 60 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 secs 97 120 secs 98 180 secs 99 240 secs SIA Installations minimum exit delay is 45 seconds UL see inst instr for requirements 35 ENTRY DELAY 1 zone type 01 30 30 Part 1 Part 2 Common zones use same delay as partition 1 00 96 0 96 seconds 97 120 seconds SIA Installations 98 180 ...

Страница 4: ...st be 15 max 55 DYNAMIC SIGNALING PRIORITY 0 0 Primary Dialer first 1 Long Range Radio first For UL Commercial Burglary installations that use a DACT and LRR this field must be 0 56 57 58 Menu Modes These are Menu Mode commands not data fields for Zone Programming Function Key Programming and Expert Mode Zone Programming respectively See page 2 and their respective sections in the Installation and...

Страница 5: ...y disabled if field 199 is set to 1 2 digit display 87 MISC FAULT DELAY TIME used with Configurable Zone Types digit 6 0 0 15 seconds 6 2 1 2 min 12 8 min 1 30 seconds 7 3 min 13 10 min 2 45 seconds 8 4 min 14 12 min 3 60 seconds 9 5 min 15 15 min 4 90 seconds 10 6 min 5 2 minutes 11 7 min UL may only be used on non burglar alarm non fire alarm zones when used in fire and or UL burglar alarm insta...

Страница 6: ...ional prefix characters up to 16 digits 0 9 11 12 13 2 second pause 165 PAGER 2 REPORT OPTIONS 0 0 0 Part 1 Part 2 common See field 162 for reporting options Select for each partition use zone list 10 if using options 12 or 13 166 PAGER 3 PHONE No Enter up to 20 digits 0 9 11 12 13 2 second pause 167 PAGER 3 CHARACTERS Enter the optional prefix characters up to 16 digits 0 9 11 12 13 2 second paus...

Страница 7: ... 2 AUI 1 Must set AUI address to 1 AUI 2 Must set AUI address to 2 Enter each touch screen AUI device s home partition 0 disabled 1 partition 1 2 partition 2 3 partition 3 common NOTE Use of AUI does not affect the number of standard keypads supported AUI Compatibility Note To ensure proper AUI device operation connect only to controls having microprocessor version 3 0 or higher and use AUI device...

Страница 8: ... disarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault by code OFF 12 verification see zone type 16 0 no 1 delay 1 2 delay 2 0 no 4 use exit delay 0 no 8 yes see note 2 Entry 7 fault display power reset verification Entry 8 entry delay 1 entry delay 2 exit delay interior zone type ENTRY 9 ENTRY 10 Alarm Sounds Use Bell Timeout Respond as Fire Zone Trouble Sounds Chime when ...

Страница 9: ... BR 52 1 BR 53 1 BR 54 1 BR 55 1 BR 56 1 BR 57 1 BR 58 1 BR 59 1 BR 60 1 BR 61 1 BR 62 1 BR 63 1 BR 64 1 BR 95 15 N A N A N A keypad 1 96 09 N A N A N A keypad 3 99 07 N A N A N A keypad NOTES Zone Type see chart on page 12 Report Code enabled if any digit entered as 1st digit Hardwire Type zns 1 8 0 EOL 3 ZD 1 NC 4 DB 2 NO Input Type 2 AW zones 9 48 3 RF zones 9 48 4 UR zones 9 48 5 BR zones 49 6...

Страница 10: ... 80 and 81 Applicable only if Relays and or Powerline Carrier Devices are to be used 79 RELAY POWERLINE CARRIER DEVICE X 10 MAPPING Must program before using 80 OUTPUT TYPE OUTPUT TYPE Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 11 04 12 05 13 06 14 07 15 08 16 17 On Board Trigger 1 norm output 1 18 On Board...

Страница 11: ...ction 0 off 1 close 2 secs 2 stay closed 3 pulse 4 toggle 5 duration 1 6 duration 2 duration is set in program field 177 Output Number 1 18 Device Type R relay T trigger X X10 ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 23 No Alarm Response 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 24 Silent Burglary 02 Entry Exit 2 07 24 H...

Страница 12: ...on or to a zone containing monitoring devices such as water or temperature sensors Sends a report to the central station and provides a keypad alarm sound No bell output is provided Type 09 Fire Provides a fire alarm on short circuit and a trouble condition on open circuit A fire alarm produces a pulsing bell output This zone type is always active and cannot be bypassed Note Hardwired zone 1 shoul...

Страница 13: ...is faulted all alarm sounding and dialer reporting stops except for fire alarms which immediately terminate the voice session and cause a fire report to be sent When the zone is restored session ended sounding resumes if bell timeout has not expired and reports that were stopped are sent Types 90 93 Installer Defined These zone types can be programmed for various custom responses See data fields 1...

Страница 14: ...7 PERIMETER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIGHT 175 SLIDING 176 SMOKE 178 SONS 179 SOUTH 180 SPRINKLER 182 STATION 184 STORE 185 STORAGE 186 STORY 190 SUPERVISED 191 SUPERVISION 192 SWIMMING 1...

Страница 15: ...Default Templates For 5804 Loop Function Zone Type For 5804BD Loop Function Zone Type TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23 2 Disarm 22 2 No Response 23 3 Arm Away 21 3 Arm Away 21 4 No Response 23 4 Disarm 22 TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24 hour audible 7 TEMPL...

Страница 16: ...00 OHMS PLUS EOLR RESPONSE ZONES 1 8 10 350 OR 700 MSEC PROGRAMMABLE 8 PIN CONNECTOR USED FOR 1361X10 TRANSFORMER CONNECTIONS AND FOR ON BOARD TRIGGERS SEE INSTRUCTIONS 7 8 USE SA4120XM 1 CABLE TIP BROWN THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE ...

Отзывы: