FIELD
TITLE and DATA ENTRIES
EXPLANATION
*59
Exit Error Report Code
0 = no report
1-F = see description above
SIA-Compliant Controls:
[1] Always enabled.
After arming the system, entry/exit and interior zones remaining open
after exit delay expires cause an alarm sound at the keypad and
external sounder (keypad also displays “EXIT ALARM”), and entry
delay begins. Disarming before the end of the entry delay stops the
alarm sounding and no message is sent to the central station. The
keypad displays “CA” (fixed-word) or “ALARM CANCELED” (alpha).
If the system is not disarmed before entry delay expires, an “EXIT
ALARM” message (
SIA-Compliant Controls:
also zone alarm
message) will be sent to the central station if Exit Error Report Code
is enabled. The keypad will display “EA” (fixed-word ) or “EXIT
ALARM” (alpha display), and alarm sounding continues until the
system is disarmed (or timeout occurs).
An Exit Alarm condition will also result if a fault occurs in an exit or
interior zone within 2 minutes following the end of the exit delay, and
an “EXIT ALARM” message will be sent to the central station
(except
for
SIA-Compliant Controls:
, see field *69 Recent Closing report).
1
With Contact ID format, the message will contain the zone number
and error code 374 (“ALARM–EXIT ERROR”).
*60
Trouble Report Code
0 = no report
1-F = see description above *59
This will be sent if a zone has a trouble condition.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*61
Bypass Report Code
0 = no report; 1-F = see description above *59
This will be sent when a zone is manually bypassed.
UL: Required for UL commercial burglar alarm installations.
*62
AC Loss Report Code
0 = no report
1-F = see description above *59
Timing of this report is random with up to a 4-hour delay. If AC
restores before the report is sent, there is no “AC RESTORE” report.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*63
Low Bat Report Code
0 = no report; 1-F = see description above *59
Sent when a low-battery condition exists in the system’s battery.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*64
Test Report Code
0 = no report
1-F = see description above *59
† NOTE: Make sure the Real-Time Clock is
set to the proper time before entering the
test report schedule command to ensure
that test reports are sent when expected.
(see Setting the Real-Time Clock section on
page 12-3)
Sent periodically to test that the communicator and phone lines are
operational. Frequency of report is set in Scheduling mode (event 11)
or by the following key commands:
installer code + [#] + 0 + 0 = test report sent every 24 hrs
installer code + [#] + 0 + 1 = test report sent once per week
installer code + [#] + 0 + 2 = test report sent every 28 days
Each mode sets schedule 32 (FA168CPS) or 8 (FA148CP) to the
selected repeat option; first test report sent 12 hours after command†.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*65
Open Report Code
0 = no report; 1-F = see description above *59
This is sent upon disarming of the system in the selected partitions.
UL: Required for UL commercial burglar alarm installations.
*66
Arm Away/Stay Report Code
0 = no report
1-F = see description above *59
This option allows for independent programming of Away and Stay
reports for each partition, including the common lobby.
NOTE: “OPEN” reports are not sent if the associated closing report
is not enabled.
*67
RF Trans. Low Batt. Report Code
0 = no report; 1-F = see description above *59
Sent when a wireless transmitter low-battery condition exists.
UL installations: must be enabled if wireless devices are used.
*68
Cancel Report Code
0 = no report; 1-F = see description above *59
Sent upon disarming after an alarm condition was reported.
SIA-Compliant Controls:
[10] Report enabled.
*69
Recent Closing Report Code
SIA-Compliant Controls Only:
Always enabled.
Field does not apply to other controls.
SIA-Compliant Controls Only:
Similar to the Exit Error condition described in field *59, but occurs
if any burglary zone is faulted within two minutes after the initial
exit delay expires. Disarming the system within the two minutes
stops the alarm sound and displays "ALARM CANCELED " or "CA"
and the faulted zone number. No message is sent to the Central
Station.
If the system is not disarmed within two minutes, the alarm sound
continues and a “recent closing” and a “zone alarm” message are sent
to the Central Monitoring Station (after dial delay expires).
4-5
Содержание FA148CP Series
Страница 20: ...Installation Instructions 2 14...
Страница 48: ...Installation Instructions 5 8...
Страница 54: ...Installation Instructions 6 6...
Страница 58: ...Installation Instructions 8 2...
Страница 68: ...11 4...
Страница 76: ...Installation Instructions 13 4...
Страница 81: ...NOTES 14 5...
Страница 82: ...NOTES Installation Instructions 14 6...
Страница 83: ...NOTES 14 7...
Страница 84: ...NOTES Installation Instructions 14 8...
Страница 85: ...NOTES 14 9...
Страница 86: ...NOTES Installation Instructions 14 10...
Страница 87: ...NOTES 14 11...
Страница 88: ...NOTES Installation Instructions 14 12...