FIELD
TITLE and DATA ENTRIES
EXPLANATION
*29
Long Range Radio Output
0 = not used
1 = using Long Range Radio output
If selected, all messages programmed to go to the primary telephone
line receiver will also be sent to the connected 7720PLUS, 7820,
7835, or 7845 Radio (sent in Contact ID format). The data line is
supervised as well as certain functions in the radio. If
communication is lost or a trouble develops, an attempt will be made
to send a message via both radio and telephone to the central station.
Program the radio for device address 3.
Zone Sounds & Timing (
∗∗∗∗
31–
∗∗∗∗
39)
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*31
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming
period for a given zone
SIA-Compliant Controls:
If “0,” “alarm sounding per zone” will be
the same as the “number of reports in armed period” set in field *93
(1 if 1 report, 2 if 2 reports, unlimited for zones in zone list 7).
*32
Fire Alarm Sounder Timeout
0 = yes; fire sounder timeout after time
programmed in field
∗
33
1 = no fire sounder timeout; continue
sounding until manually turned off
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses.
UL fire alarm installations: must be 1.
*33
Alarm Sounder Timeout
0 = No timeout
3 = 12 min
1 = 4 min
4 = 16 min
2 = 8 min
This field determines whether the external sounder will shut off after
time allotted, or continue until manually turned off.
UL installations: For residential fire alarm installation, must be set
for a minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum of 16 min (option 4).
*34
Exit Delay
00 - 96 = 0 - 96 seconds
97 = 120 seconds
SIA-Compliant Controls:
45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-
sec delay.
The system waits the time entered before arming entry/exit zones. If
the entry/exit door is left open after this time expires, an alarm will
occur. Common zones use same delay as partition 1.
UL installations: For UL Commercial Burglar Alarm (Grade AA) and
UL Residential Burglar Alarm installations with line security, total
exit time must not exceed 60 seconds. For UL Burglar Alarm
installations without line security (Grade A), total exit time must not
exceed 120 seconds.
SIA Guidelines: minimum exit delay is 45 seconds
*35
Entry Delay 1
00 - 96 = 0 - 96 seconds
97 = 120 secs; 98 = 180 secs; 99 = 240 secs
SIA-Compliant Controls:
30-96 = 30 - 96 secs;
97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-sec
delay.
Upon entering, the system must be disarmed before the time entered
expires, otherwise it sounds an alarm. Common zones use same delay
as partition 1.
UL installations: For UL Residential Burglary Alarm installations,
must be set for a maximum of 30 seconds; entry delay plus dial delay
should not exceed 1 min. For UL Commercial Burglar Alarm, total
entry delay may not exceed 45 seconds.
SIA Guidelines: minimum entry delay is 30 seconds
*36
Entry Delay 2
See *35 above for entries and explanation.
*37
Audible Exit Warning
0 = no; 1 = yes
Warning sound consists of slow continuous beeps until last 10 seconds,
then it changes to fast beeps. Sound ends when exit time expires.
SIA Guidelines: must be enabled (enter 1)
SIA-Compliant Controls:
Feature always enabled; field removed.
*38
Confirmation Of Arming Ding
0 = no ding
1 = confirmation ding after arming system
2 = confirmation ding after arming from RF
button or RF keypad only
Confirmation of arming is 1/2 second external sounder “ding.”
If “1” selected, ding occurs when closing report is sent, or at the end of
Exit Delay. If “2” selected, ding occurs upon reception of the wireless
arming command.
UL installations: must be “1” for UL Commercial Burglar Alarm
installations.
*39
Power-Up In Previous State
0 = always power-up in a disarmed state
1 = assume the system status prior to
power down
When the system powers up armed, an alarm will occur 1 minute after
arming if a zone is faulted.
Note that if the previous state was armed Away or Stay, the system
will not respond to sensor changes for 1 minute, which allows time for
sensors such as PIRs to stabilize.
UL Installations: must be 1 (power-up in previous state)
SIA Guidelines: must be 1
SIA-Compliant Controls:
Feature must be enabled.
Installation Instructions
4-2
Содержание FA148CP Series
Страница 20: ...Installation Instructions 2 14...
Страница 48: ...Installation Instructions 5 8...
Страница 54: ...Installation Instructions 6 6...
Страница 58: ...Installation Instructions 8 2...
Страница 68: ...11 4...
Страница 76: ...Installation Instructions 13 4...
Страница 81: ...NOTES 14 5...
Страница 82: ...NOTES Installation Instructions 14 6...
Страница 83: ...NOTES 14 7...
Страница 84: ...NOTES Installation Instructions 14 8...
Страница 85: ...NOTES 14 9...
Страница 86: ...NOTES Installation Instructions 14 10...
Страница 87: ...NOTES 14 11...
Страница 88: ...NOTES Installation Instructions 14 12...