![First Alert FA148CP Series Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/first-alert/fa148cp-series/fa148cp-series_installation-and-setup-manual_2293328024.webp)
Type 06
24-hour Silent Alarm
•
Usually assigned to a zone containing an emergency button.
•
Sends a report to the central station but provides no keypad display or sounding.
Type 07
24-hour Audible Alarm
•
Assign to a zone that has an emergency button.
•
Sends a report to the central station, and provides an alarm sound at the keypad,
and an audible external alarm.
Type 08
24-hour
Auxiliary Alarm
•
Assign to a zone containing an emergency button, or to a zone containing
monitoring devices such as water or temperature sensors.
•
Sends a report to the central station and provides an alarm sound at the keypad.
(No bell output is provided.)
Type 09
Supervised Fire
•
Provides a fire alarm on short circuit and a trouble condition on open circuit. A
fire alarm produces a pulsing bell output.
•
This zone type is always active and cannot be bypassed.
Type 10
Interior w/Delay
•
Provides entry delay (using the programmed entry time), if tripped when the
panel is armed in the Away mode.
•
Entry Delay 1 begins whenever sensors in this zone are violated, regardless of
whether or not an entry/exit delay zone was tripped first.
•
Bypassed when the panel is armed in the Stay or Instant modes; if armed in
Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not
bypassed when system armed in Night-Stay mode.
Type 12
Monitor Zone
•
Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a
short/open, the message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the
zone number) will be sent to the Central Station. The system keypad will display
a “check” message indicating the appropriate zone (but keypad beeping does not
occur). Upon restoral of the zone, the message, "*RESTORE*-24 Hr. Non-Burg. -
#XXX " will be sent to the Central Station.
•
The “check” message will automatically disappear from the keypad dynamically,
when the zone restores; a user code + off sequence is not needed to reset the zone.
•
Faults of this zone type are independent of the system, and can exist at the time
of arming without interference.
•
Since this is a “trouble” zone type, do not use this zone type with relays set to
activate upon “alarm.”
Type 14
24 Hour Carbon
Monoxide Monitor
•
Assigned to any zone with a carbon monoxide detector.
•
The bell output will pulse when this zone type is alarmed.
•
Always active and cannot be bypassed.
Type 16
Fire w/Verification
•
Provides a fire alarm when zone is shorted, but only after alarm verified.
•
System verifies alarm by resetting zones for 12 seconds after short is detected. A
subsequent short circuit within 90 seconds triggers fire alarm.
•
Provides a trouble response when zone is open.
Type 20
Arm-Stay (BR only)
•
Arms the system in Stay mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or
disarming.
•
User number for button must be assigned.
Type 21
Arm-Away (BR only)
•
Arms the system in Away mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or
disarming.
•
User number for button must be assigned.
Type 22
Disarm (BR only)
•
Disarms the system when the zone is activated.
•
User number for button must be assigned.
Type 23 *
No Alarm Response
•
Can be used on a zone when an output relay action is desired, but with no
accompanying alarm (e.g., lobby door access).
Installation Instructions
3-4
Содержание FA148CP Series
Страница 20: ...Installation Instructions 2 14...
Страница 48: ...Installation Instructions 5 8...
Страница 54: ...Installation Instructions 6 6...
Страница 58: ...Installation Instructions 8 2...
Страница 68: ...11 4...
Страница 76: ...Installation Instructions 13 4...
Страница 81: ...NOTES 14 5...
Страница 82: ...NOTES Installation Instructions 14 6...
Страница 83: ...NOTES 14 7...
Страница 84: ...NOTES Installation Instructions 14 8...
Страница 85: ...NOTES 14 9...
Страница 86: ...NOTES Installation Instructions 14 10...
Страница 87: ...NOTES 14 11...
Страница 88: ...NOTES Installation Instructions 14 12...