background image

4

INSTALLATION

Connecting the Antenna

A Quad band GSM antenna is provided with the unit. Optional high gain antennae (see ACCES-
SORIES) can be ordered if the site in question has weak cell coverage.

The antenna connections on the enclosure are factory installed to prevent water from entering
the enclosure.

DO NOT

 change any of these existing connections.

Simply screw either antenna to the connector (see Figure 1) on the top of the enclosure. Be sure
the connection is tight.

Startup Procedure

Take the transmitter to the area where the equipment to be monitored is located.

The transmitter will be able to send messages in locations where GSM cell phones will work. If
the equipment is in an area where an GSM cell phone cannot get a signal, it is unlikely the trans-
mitter will be able to get a signal. 

(

NOTE:

 A remote antenna is available, see next section)

.

Plug in the battery pack into the battery pack connector (see below). Connect AC power to the
appropriate terminals located in the lower right corner. 

The transmitter will begin a startup routine. The startup time will vary but may last up to several
minutes as the transmitter establishes a connection to a cell site and registers a message.

During the startup routine, the Signal Strength Indicator 7-segment LED display segments will
rotate. Initially, the middle display segment will not be lit. When the middle segment comes on,
the transmitter has successfully completed the first half of the startup routines.

Dipswitch Settings

The inTouch unit contains 4 user configurable dipswitches. Some dipswitch settings take effect
during the power up initialization sequence. Changing a dipswitch on the fly may require a power
on/off sequence.

SWITCH OFF

ON

ONE (1)

Do not report end of lockout

Report end of lockout

TWO (2)

4800 Baud Rate

9600 Baud Rate

Note: All connected controls must have the same baud rate.

THREE (3)

For dry contact inputs 3 & 4 , alarm on close

For dry contact inputs 3 & 4, alarm on open

FOUR (4)

For voltage inputs 7 & 8, alarm with voltage present

For voltage inputs 7 & 8, alarm with no voltage present

Содержание InTouch IT1000

Страница 1: ...distinct messages for each monitored point Two each of the dry contact and AC voltage inputs can be configured to alarm on contact close or open or on voltage present or absent Also every 24 hours the...

Страница 2: ...outdoor mounting Dimensions 7 1 8 W x 9 5 8 H x 3 1 2 D 18 x 24 5 x 8 9cm Material UV Resistant ABS Grey Knockouts 3 bottom 3 rear 1 2 3 4 concentric Inputs RS485 Modbus RTU Protocol 4800 9600 baud se...

Страница 3: ...within the range of 0 through 9 When con figuring the inTouch over the web site the device installed will be the base address of the inTouch plus the unit address of the Flame Monitor MicroM or Burne...

Страница 4: ...AC power to the appropriate terminals located in the lower right corner The transmitter will begin a startup routine The startup time will vary but may last up to several minutes as the transmitter e...

Страница 5: ...23 24 85 120 VAC 60 Hz 12 Use this knockout for Class I leads 13 Device wiring 22 earth ground 14 Voltage inputs 13 20 24 120 VAC or 5 48 VDC 10 11 12 19 13 14 15 16 18 17 20 23 21 24 22 15 Terminal b...

Страница 6: ...ng underneath Use all three tabs to secure the unit DO NOT drill any holes into or through the enclosure Filed wiring to the inputs must be a minimum of AWG and a maximum of 12 AWG Wiring Guidelines R...

Страница 7: ...ng the Device ID number Without this number the device cannot be config ured at the web site Testing To complete the test the transmitter must be configured at the Fireye web site see Configuring the...

Страница 8: ...efer to Figure 6 on page 10 for an illustration overview Plug the ED512 cable into either of the telephone style jacks located in the upper left corner of the EP or EPD programmer module Refer to Figu...

Страница 9: ...page 10 for an illustration overview Plug the ED512 cable into either of the telephone style jacks located in the underside of the YB110 or ZB110 module Refer to Figure 5 on page 10 Connect the other...

Страница 10: ...the OPTION button 3 times The 7 seg ment LED display will switch to a dash symbol followed by the addresses of the devices it is successfully communicating The display will then show the dash symbol f...

Страница 11: ...ystem provides for the connection of 4 dry contact and 4 AC inputs see Fig 1 These can be used to transmit messages when a contact is detected as closed open or power is applied not applied to the AC...

Страница 12: ...will automatically see the Edit User Info screen shown in Fig 7 Otherwise you can access this screen by clicking on the menu item Edit user Info or if you know the User Info is correct move on to the...

Страница 13: ...ee Fig 11 If you have any existing transmitters they will appear in a list To add your new device click on the menu item Install New Device see Fig 8 THESE ARE THE DEFAULT LOCATIONS FOR MESSAGE DELIVE...

Страница 14: ...St for Street or Rd for Road if you plan to use the voice mes sage delivery Do not use uppercase letters for words if you plan to use for voice message delivery example use flow not FLOW as the synth...

Страница 15: ...THE ADDRESS OF THE EQUIPMENT THE TRANSMITTER IS MONITORING THIS INFORMATION SHOULD BE COMPLETE ENOUGH TO ALLOW A SERVICE PERSON TO GET THE APPROPRIATE PARTS BEFORE COMING TO THE EQUIPMENT SITE CLICK...

Страница 16: ...ow many times Fireye will attempt to deliver a message if the message is not successfully received When the message is delivered successfully no more attempts will be made If the message is not succes...

Страница 17: ...bring up the Device Information screen Fig 12 A summary of the information which was entered in Fig 8 New Equipment Information appears If any of the information is not correct click on the button Ed...

Страница 18: ...gured to be sent to various addresses using different delivery methods To change an existing delivery address click on any field in the Delivery Address column to change it Note the only acceptable ch...

Страница 19: ...19 FIGURE 15 TO MAKE ANY CHANGES CLICK ON EDIT DELETE OR ADD...

Страница 20: ...e e mail message appears below Make sure the appropriate individuals were paged that the appropriate faxes were sent and the appropriate phone calls were made Check the messages Confirm the equipment...

Страница 21: ...o input the information on where the User or where the transmitter will be located Once you have filled in all the required fields click on the Submit button Credit Application The inTouch service may...

Страница 22: ...HEN YOU HAVE COMPLETED THE FORM AND ARE READY TO BECOME A MEMBER THIS ADDRESS IS THE BILLING ACCOUNT ADDRESS OF THE ACCOUNT HOLDER THIS INFORMATION IS USED TO CONTACT THE ACCOUNT HOLDER THIS IS NOT WH...

Страница 23: ...e passwords to them ACCESSING YOUR inTouch ACCOUNT After your inTouch device is installed and Flame Monitor or MicroM controls are properly con nected and verified you can check the historical status...

Страница 24: ...Remember every inTouch device can have multiple pieces of equipment connected and each piece of equipment must have its own Device ID For example in the figure above Dev ID 1082 and 1083 are actually...

Страница 25: ...h Also from this page you are allowed to edit the device infor mation such as the contact person and phone number or description of equipment For instance when you click on the one of the last 3 locko...

Страница 26: ...stablished to transmit to the message server after 1 00 AM However due to signal levels below the minimum required the inTouch system was not able to consistently report in at its regular time When st...

Страница 27: ...27 You can also click on any of the stored lockouts to get a view of the message delivery of that particu lar lockout...

Страница 28: ...s found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND F...

Отзывы: