11
SNOOZE Feature
To allow for regularly scheduled testing of boiler/burner safeties such as flame failure, low water cut
out, air flow checks, etc., without alarm messages being transmitted, the inTouch provides a
SNOOZE feature. During the SNOOZE period the inTouch will not respond to any alarm or reset
events.
The SNOOZE period lasts for 120 minutes and will automatically cancel if left uninterrupted. The
SNOOZE feature can be cancelled at anytime after safety tests are satisfactorily performed.
To active the SNOOZE feature, press the SERVICE button. A service message will be dispatched
and the display LED will change from its current signal strength reading to ‘F’. The automatic 120
minute SNOOZE period will now begin.
To de-active the SNOOZE period and resume normal operation, do nothing and this function will
cease after the 120 time out period or press the SERVICE button. The display LED will indicate the
current signal strength reading.
Auxiliary Device Connection
The inTouch system provides for the connection of 4 dry contact and 4 AC inputs, see Fig. 1 . These
can be used to transmit messages when a contact is detected as closed/open or power is applied/not
applied to the AC inputs. The AC inputs. The AC inputs accept voltages from 24 to 120 VAC at
3mA. Refer to dipswitch selection for dry contacts 3 & 4 and voltage inputs 7 & 8.
These can be used to connect to other equipment located in a boiler room such as other flame safe-
guard equipment that provide alarm output only. Dry contact devices used to detect empty fuel tanks,
condensate spills or water on the floor can be connected and give instant alarm when unwanted
events occur.
The messages transmitted can be configured to exactly what is causing the alarm condition. For
example, the default message Input 1 Activated can easily be changed to transmit Air Flow Input
Open. See the section on message configuration for more information.
M
M
AIR FLOW INPUT
CONDENSATE INPUT
AUX 1 USER DEFINED
AUX 2 USER DEFINED
COMPRESSOR
RELAY
FAN RELAY
FAN INPUT
COMPRESSOR INPUT
FAN MOTOR
COMPRESSOR
COMPRESSOR RELAY
LO PRESSURE LIMIT
HIGH PRESSURE LIMIT
HIGH PRESSURE INPUT
LO PRESSURE INPUT
AIR FLOW OK
CONDENSATE SPILL