Commissioning 

Commissioning should be performed when the siren and shutdown relays are connected, and 
fire control panel is not in an alarm/fault condition. 
1.

 

Isolate and disconnect the any installed FirePro aerosol generators.  This should generate 
a fault on the fire control panel. 

2.

 

Connect  a  FirePro  FP-08800  Universal  Test  Lamp

s  to  “Normal”  and  “Discharge  Delay” 

outputs. 

 

3.

 

Perform an activation test, by pressing and holding the buttons on the fire control panel or 
through the detection circuits. 

4.

 

Ensure that all Test Lamps connected to the 

“Normal” output

 operate. 

5.

 

Obse

rve the programmed delay and ensure that all Test Lamps connected to the “Discharge 

Delay” output operate

6.

 

Reset the fire control panel and all connected test lamps.   

7.

 

The fire control panel should no longer be in a fault or alarm condition. 

8.

 

Disconnect the FirePro FP-08800 Universal Test Lamp and reconnect all installed FirePro 
aerosol generators. 

8

 

Servicing and Maintenance 

Inspection  and  servicing  of  the  installed  fire  system  should  occur  in  accordance  with  the 
relevant  Australian  Standards.    This  should  include  a  visual  inspection  of  the  enclosure  to 
ensure the seals are intact. 
Monitoring  and  operation  of  any  installed  modules  should  be  tested  as  outlined  in  7. 
Commissioning.  

9

 

Operation 

The Discharge Delay Module operates automatically when the fire control panel in is an alarm 
condition  or  the  fire  system  has  been  manually  activated.    When  activated,  the  FirePro 

generators  connected  to  the  “normal”  output

  will  discharge  immediately,  and  initiate  the 

programmed  time  delay  for  the  secondary  activation  sequence.    When  the  time  delay  is 
completed, the secondary activation will operate and the FirePro generators connected to the 

“discharge delay” output will discharge

The Fire Control Panel will not isolate or reset until the activation sequence is complete. 

 

 

 

Содержание FP-08850

Страница 1: ...ischarge Delay Module 3 3 4 Maximum Number of Discharge Delay Modules that can be used 3 3 5 Mounting 4 3 6 Cabling Requirements 4 3 7 Multiple Discharges Voltage Limitations 4 3 8 Connecting Multiple...

Страница 2: ...mer that can be used to delay the activation of the FirePro generators until suitable This can be set to account for vehicle or site specific conditions for example large areas of leakage time allowan...

Страница 3: ...perating ONLY AFTER DELAY The 3k3 EOL resistor must be in place on the Normal output of a fault will display 3 4 Maximum FirePro units that may be connected 12v DC 2 units per output 24v DC 4 units pe...

Страница 4: ...remain secure Male plugs locking mechanism is orange Female plugs locking mechanism is green 5 Using the heat shrink seal the back of the plug Cables are colour coded for easy identification When inst...

Страница 5: ...dules must not be connected together by the normal output 3 10 Connecting Multiple FirePro Generators If multiple FirePro Generators are being installed on a single output they must be connected using...

Страница 6: ...d Discharge output the 3k3 End of line resistor should be terminated into the supplied 3 pin deutsch plug and then connected to the Normal output on the module marked yellow 1 The end of line plug sho...

Страница 7: ...ds after the FIP has entered an alarm condition Individual programming of modules must not exceed 4 5 minutes the total time power is applied to the activation circuit Mode Delay Timer Switch Mode Del...

Страница 8: ...separate delay value in seconds as follows The delay time is programmed by setting the required switches to the OFF position When multiple switches are used the delay values are added together allowi...

Страница 9: ...nnect the FirePro FP 08800 Universal Test Lamp and reconnect all installed FirePro aerosol generators 8 Servicing and Maintenance Inspection and servicing of the installed fire system should occur in...

Страница 10: ...talled generators exceeds maximum OR FirePro Generators have discharged Check connection of any extension cables Inspect condition of FirePro Generators Check internal battery of FirePro Test lamp For...

Отзывы: