3.3

 

How to install a Discharge Delay Module 

Connecting ADDITIONAL UNITS 

 

USING for DELAYED DISCHARGE 

 

 

 

This  shows  3  x  FirePro  Generators  operating 
immediately (through the Normal Activation Circuit) 
and 1 FirePro unit firing after a delay.

 

 

This shows 2 x Firepro Generators operating ONLY 
AFTER DELAY.  

The 3k3Ω E

OL resistor must be in 

place on the Normal output of a fault will  display 

3.4

 

Maximum FirePro units that may be connected 

12v DC

 

2 units per output

 

24v DC

 

4 units per output

 

3.5

 

Maximum Number of Discharge Delay Modules that can be used 

Maximum of 10 Modules may be used on any single panel 

 from an electrical point of view.    

Actual maximum will be determined by delay programming.  If more modules are required, 
consult with your supplier.

 

Содержание FP-08850

Страница 1: ...ischarge Delay Module 3 3 4 Maximum Number of Discharge Delay Modules that can be used 3 3 5 Mounting 4 3 6 Cabling Requirements 4 3 7 Multiple Discharges Voltage Limitations 4 3 8 Connecting Multiple...

Страница 2: ...mer that can be used to delay the activation of the FirePro generators until suitable This can be set to account for vehicle or site specific conditions for example large areas of leakage time allowan...

Страница 3: ...perating ONLY AFTER DELAY The 3k3 EOL resistor must be in place on the Normal output of a fault will display 3 4 Maximum FirePro units that may be connected 12v DC 2 units per output 24v DC 4 units pe...

Страница 4: ...remain secure Male plugs locking mechanism is orange Female plugs locking mechanism is green 5 Using the heat shrink seal the back of the plug Cables are colour coded for easy identification When inst...

Страница 5: ...dules must not be connected together by the normal output 3 10 Connecting Multiple FirePro Generators If multiple FirePro Generators are being installed on a single output they must be connected using...

Страница 6: ...d Discharge output the 3k3 End of line resistor should be terminated into the supplied 3 pin deutsch plug and then connected to the Normal output on the module marked yellow 1 The end of line plug sho...

Страница 7: ...ds after the FIP has entered an alarm condition Individual programming of modules must not exceed 4 5 minutes the total time power is applied to the activation circuit Mode Delay Timer Switch Mode Del...

Страница 8: ...separate delay value in seconds as follows The delay time is programmed by setting the required switches to the OFF position When multiple switches are used the delay values are added together allowi...

Страница 9: ...nnect the FirePro FP 08800 Universal Test Lamp and reconnect all installed FirePro aerosol generators 8 Servicing and Maintenance Inspection and servicing of the installed fire system should occur in...

Страница 10: ...talled generators exceeds maximum OR FirePro Generators have discharged Check connection of any extension cables Inspect condition of FirePro Generators Check internal battery of FirePro Test lamp For...

Отзывы: