Introduction 

1.1

 

General Information 

The FP-08850 Discharge Delay Module provides the FP-08450 or FP-08451 Fire Control Panel 
to activate additional FirePro generators, or delay the activation sequence of the fire system 
via programmable delay.  The Discharge circuits are monitored. 

1.2

 

Discharging Additional FirePro Generators 

The number of FirePro generators a  FP-08450 or FP-0451 Fire Control Panel can discharge 
depends on the voltage from the available power supply. 
 

12vDC 

Max 2 x FirePro Generators 

 

24vDC 

Max 4 x Firepro Generators 

Where risk requires a more FirePro Units to be used, or a delay in the activation.  The Discharge 
Delay  module  must  be  used.    The  module  will  activate  FirePro  generators  sequentially  in 
multiples of the quantities as per the available power supply. 

1.3

 

Delaying Discharge 

The discharge delay function includes a programmable timer that can be used to delay the 
activation of the FirePro generators until suitable.  This can be set to account for vehicle or 
site specific conditions, for example; large areas of leakage, time allowance for evacuation, or 
increased hold time in the risk area. 

2

 

Components List 

 

FP-08850 
Discharge Delay Module

 

2x DP-3000 

Deutsch Plug 3 Pin M/F, c/w 
heatshrink 

3

 

Design Considerations 

3.1

 

Normal Output 

The 

“Normal”  output

  (marked  yellow  1)  activates  any  connected  FirePro  generators 

immediately when the activation sequence begins - it is NOT affected by the delay timer. 
Where a system requires the use of only the delayed discharge circuit, the supplied 

3k3Ω End

-

of-line resistor 

must 

be installed on the 

“Normal” output

, or a fault will be displayed. 

3.2

 

Discharge Delayed Output 

The “Discharge Delay” output (marked yellow 2) ac

tivates any connected FirePro generators 

as per the programming to the delay timer.  The delay timer initiates when the control panel 
begins the activation sequence.  When the programmed time is reached, the connected FirePro 
generators will discharge. 

 

 

Содержание FP-08850

Страница 1: ...ischarge Delay Module 3 3 4 Maximum Number of Discharge Delay Modules that can be used 3 3 5 Mounting 4 3 6 Cabling Requirements 4 3 7 Multiple Discharges Voltage Limitations 4 3 8 Connecting Multiple...

Страница 2: ...mer that can be used to delay the activation of the FirePro generators until suitable This can be set to account for vehicle or site specific conditions for example large areas of leakage time allowan...

Страница 3: ...perating ONLY AFTER DELAY The 3k3 EOL resistor must be in place on the Normal output of a fault will display 3 4 Maximum FirePro units that may be connected 12v DC 2 units per output 24v DC 4 units pe...

Страница 4: ...remain secure Male plugs locking mechanism is orange Female plugs locking mechanism is green 5 Using the heat shrink seal the back of the plug Cables are colour coded for easy identification When inst...

Страница 5: ...dules must not be connected together by the normal output 3 10 Connecting Multiple FirePro Generators If multiple FirePro Generators are being installed on a single output they must be connected using...

Страница 6: ...d Discharge output the 3k3 End of line resistor should be terminated into the supplied 3 pin deutsch plug and then connected to the Normal output on the module marked yellow 1 The end of line plug sho...

Страница 7: ...ds after the FIP has entered an alarm condition Individual programming of modules must not exceed 4 5 minutes the total time power is applied to the activation circuit Mode Delay Timer Switch Mode Del...

Страница 8: ...separate delay value in seconds as follows The delay time is programmed by setting the required switches to the OFF position When multiple switches are used the delay values are added together allowi...

Страница 9: ...nnect the FirePro FP 08800 Universal Test Lamp and reconnect all installed FirePro aerosol generators 8 Servicing and Maintenance Inspection and servicing of the installed fire system should occur in...

Страница 10: ...talled generators exceeds maximum OR FirePro Generators have discharged Check connection of any extension cables Inspect condition of FirePro Generators Check internal battery of FirePro Test lamp For...

Отзывы: