Troubleshooting
Problem
Possible Cause
Solution
“Normal” Output/Primary
Discharge not operating
Disconnected or poor
connection to FirePro generators
Check connection of any
extension cables.
“
Discharge Delay
”
Output/Secondary Discharge
not operating
Incorrect programming at fire
control panel
OR
Disconnected or poor
connection to FirePro generators
Check programming at fire
control panel.
Check connection of any
extension cables.
Fault displayed on fire control
panel (3 Beeps)
Disconnected or poor
connection to FirePro generators
OR
Number of installed generators
exceeds maximum
OR
FirePro Generators have
discharged
Check connection of any
extension cables.
Inspect condition of FirePro
Generators.
Check internal battery of FirePro
Test lamp.
For additional assistance contact your supplier.
11
Specifications
FP-08850
Dimensions
140L x 65W x 30D
Enclosure material
Die Cast Aluminium
Operating voltage
12-30VDC
Outputs
Discharge, max 2A at 12VDC and 2A at 24VDC
Outputs Fuse
Self-resetting Polyswitch trips at 2A
Discharge end-of- line
3K3 resistor
Fault-sensing
Discharge wiring open-circuit
Operating Temp.
40 to 85 degrees Celsius
Ingress Protection
IP65
Max no. of Modules
Up to 10
–
If more modules are required, consult with your
supplier.
Actual maximum will be determined by delay programming.