background image

Where  multiple  modules  are  used,  the  modules  are  to  be  connected  using  the 

“Discharge 

Delay

 output (marked yellow 2) as below.  

 

The  FP-0450/8451  fire  control  panel  activation  sequence  is  limited  to  prevent  accidental 
discharges when servicing.  The maximum amount of time power is supplied to the activation 
circuit is 4.5 minutes.

  Any programming to the Discharge Delay modules must not 

exceed  this  time  limitation,  or  the  modules  will  not  operate. 

(For  example;  if 

programmed M1 

 2.5min, M2 

 2.5min, M3 

 2.5min; module 3 will not operate). 

Note:

 Discharge Delay modules

 must not 

be connected together by the “normal” output.

 

3.10

 

Connecting Multiple FirePro Generators 

If multiple FirePro Generators are being installed on a single output, they must be connected 
using the FP-08919 Splitter Lead.  The Splitter Lead enables the activation current to pass 
uninterrupted to all connected FirePro generators and allows for continuous monitoring.   
Splitter Leads can be installed at any point on the activation circuit and do not need to be 
installed adjacent to the fire control panel or the discharge delay module.  For ease of install, 
servicing and more efficient field wiring, Splitter Leads should be installed in areas easy to 
access and should be used to minimise the required extension leads, and to bypass obstacles. 
 

 

 

 

Содержание FP-08850

Страница 1: ...ischarge Delay Module 3 3 4 Maximum Number of Discharge Delay Modules that can be used 3 3 5 Mounting 4 3 6 Cabling Requirements 4 3 7 Multiple Discharges Voltage Limitations 4 3 8 Connecting Multiple...

Страница 2: ...mer that can be used to delay the activation of the FirePro generators until suitable This can be set to account for vehicle or site specific conditions for example large areas of leakage time allowan...

Страница 3: ...perating ONLY AFTER DELAY The 3k3 EOL resistor must be in place on the Normal output of a fault will display 3 4 Maximum FirePro units that may be connected 12v DC 2 units per output 24v DC 4 units pe...

Страница 4: ...remain secure Male plugs locking mechanism is orange Female plugs locking mechanism is green 5 Using the heat shrink seal the back of the plug Cables are colour coded for easy identification When inst...

Страница 5: ...dules must not be connected together by the normal output 3 10 Connecting Multiple FirePro Generators If multiple FirePro Generators are being installed on a single output they must be connected using...

Страница 6: ...d Discharge output the 3k3 End of line resistor should be terminated into the supplied 3 pin deutsch plug and then connected to the Normal output on the module marked yellow 1 The end of line plug sho...

Страница 7: ...ds after the FIP has entered an alarm condition Individual programming of modules must not exceed 4 5 minutes the total time power is applied to the activation circuit Mode Delay Timer Switch Mode Del...

Страница 8: ...separate delay value in seconds as follows The delay time is programmed by setting the required switches to the OFF position When multiple switches are used the delay values are added together allowi...

Страница 9: ...nnect the FirePro FP 08800 Universal Test Lamp and reconnect all installed FirePro aerosol generators 8 Servicing and Maintenance Inspection and servicing of the installed fire system should occur in...

Страница 10: ...talled generators exceeds maximum OR FirePro Generators have discharged Check connection of any extension cables Inspect condition of FirePro Generators Check internal battery of FirePro Test lamp For...

Отзывы: