Installation
(for qualified installers only)
7
Travis Industries
9 3 5 0 8 1 0 9
1 8 0 5 0 1
Fireplace Placement Requirements
Minimum Framing Dimensions
The 1Ó stand-offs along the front corners, the 1Ó clearance requirement around the sides and back,
and the 10-1/2" stand-offs on the top of the fireplace separate the fireplace from combustible
materials (e.g.: combustible framing members, plywood, sheetrock, paper-backed insulation). The
stand-offs may contact the framing members but no material may be placed between the stand-offs or
into the required 1Ó clearance to the sides and back
AAAA
AAAA
AAAA
A
AAAA
AAAA
AAAA
A
AA
A
A
A
A
AA
AA
A
A
A
AA
AA
AA
AA
A
Gas line (3/8" M.P.T. or 1/2"
F.P.T.) should be routed 6-12"
behind the framing opening
and 2-3/8" above the base of
the fireplace (see "Gas Line
Connection" for details).
52"
24-3/8"
50-3/4"
Route the electrical line to a position
at the right rear of the fireplace.
If using a remote
control or thermostat,
route the wire to a
location near the gas
line (include an extra 3'
length for hookup).
NOTE
: if venting directly to the rear,
make sure there is a min. 12" space
centered behind the fireplace.
NOTE:
If using the power heat vent,
allow for the duct passage when
framing the enclosure.
Required Firestop (included with
the fireplace)
3" Clearance Min. (after firestop)
Minimum 65-1/2" above the
base of the fireplace (includes
18" min. rise before elbow -
see the section "Horizontal
Termination Requirements")
5-1/2" Clearance Min.
(before firestop)
1" Clearance min. to the sides
and below the vent (before or
after firestop).
The fireplace enclosure
must not be less than
75" above the base of
the fireplace.
75" Min.
•
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
•
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
•
Due to the high temperature of the fireplace, it should be located out of traffic and away from furniture
and draperies.