Integrated Fire Protection System

 

Mechanical Section - Non Interlock Preaction System - Pneumatic Release

 

 

FM-076A-0-41C 

1- Installation, operation & maintenance 

instructions 

Note:  

Numbers indicated between brackets refer to figure 1 

DETAILED  SYSTEM  TRIM  SCHEMATICS

  from  this  section  and 

section 

 D 

 

AIR SUPPLY

1.1  Installation 

  1.  Conform  to  local  municipal  or  other  codes  regarding 

installations of fire protection systems. 

  2.  Install  the 

T

OTAL

P

AC

 

®

3

  unit  and  connect  the  system 

according  to  instruction  manual  and  technical  data 
supplied. 

IMPORTANT !  

The  cabinet must  be  firmly  anchored  to  the 

floor  using  all  four (4)  anchoring  holes  (see  section 

 G 

 

CABINET

). 

Note:  

The  drain  collector  shall  be  connected  to  an  open 

drain.  Do not restrict or reduce drain piping. 

  3.  Install  the  system  piping  network  and  the  pneumatic 

release  piping  network  (pilot  line)  in  accordance  with 
applicable standards. 

  4.  Connect all supervisory and alarm signals according to 

electrical schematics (see section 

 F 

 

ELECTRICAL

). 

  5.  If  applicable,  connect  the  AC  power  to  the  air 

compressor  on  a  separate  breaker  in  the  electric 
distribution panel (see section 

 F 

 

ELECTRICAL

). 

Notes:

 

AC  power  connections  must  be  made  by  a  qualified 
installer  according  to  national  standards  and  equipment 
specifications. 

  Do not apply AC power to the air compressor yet. 

  6.  Perform  preliminary  inspection  prior  to  put  system  in 

service (see paragraph 1.2 of the current section). 

  7.  Place  the  system  in  service  (see  paragraph 1.3  of  the 

current section). 

  8.  Perform  the  annual  inspection  sequence  (see 

paragraph 1.8 of the current section). 

  9.  If  the  system  does  not  operate  as  it  should,  make  the 

necessary  corrections  according  to  manuals  issued  or 
consult your distributor or 

F

IRE

F

LEX

 Systems Inc. 

 10.  Make  sure  that  building  owner  or  a  delegated 

representative  has  received  instructions  regarding  the 
operation of the system. 

WARNING !

  

T

OTAL

P

AC

 

®

3

  unit  must  be installed  in  an area 

not subject to freezing temperatures or physical damage. 

1.2  Preliminary inspection before placing the system in 

service 

  1.  Open door to mechanical section. 
 

a)  Main water supply valve 

(D1)

 must be 

CLOSED

 

b)  Priming valve 

(B1)

 must be 

CLOSED

 

c)  Air  supply  for  system  piping  network  and  pneumatic 

release  piping  network  (pilot  line)  must  be 

CLOSED

 

(see section 

 D 

 AIR

 

SUPPLY

). 

 

d)  Flow  test  valve 

(B6)

  and  main  drain  valve 

(D3)

  must 

be 

CLOSED

 

e)  Alarm test valve 

(B5)

 must be 

CLOSED

 

f)  Gauges 

(B11,  B12,  E3 

and

  F4) 

should  show  0 PSI 

(0 kPa). 

 

g)  If applicable, the shut-off valve 

(D4)

 must be 

OPEN

  2. 

OPEN

  the  manual  emergency  release  valve 

(B10)

  and 

make sure the deluge valve 

(A1)

 is tripped. 

  3.  Using the built-in contractor's hydrostatic test ports (see 

figure 1  of  this  section  and  section 

 D 

  AIR

 

SUPPLY

),  fill 

system piping network with water and maintain pressure 
as per NFPA-13 requirements. 

WARNING !

  Do  not  subject  the  pressure  gauges  and 

pressure transducer to hydrostatic pressure above 250 PSI 
(1724 kPA).    Close  gauge  valves  before  proceeding  with 
hydrostatic test. 

  4.  Correct leaks if any before completing test. 

  5.  Verify that main water supply valve 

(D1)

 is still 

CLOSED

  6. 

OPEN

  main  drain  valve 

(D3)

  to  completely  drain  the 

system piping network

.

 

  7.  If  applicable,  apply  AC  power  to  the  air  compressor.  

The  air  supply  must  be 

CLOSED

  (see  section 

 D 

  AIR

 

SUPPLY

). 

Содержание TOTALPAC 3

Страница 1: ...FM 076A 0 1C Advanced Integrated Fire Protection System TOTALPAC 3 Owner s Operation and Maintenance Manual NON INTERLOCK PREACTION SYSTEM PNEUMATIC RELEASE...

Страница 2: ...ual is prohibited While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy FIREFLEX Systems Inc assumes no liability resulting from any errors or omissions...

Страница 3: ...4 System operation 1 5 Emergency instructions 1 6 Placing the system back in service after operation 1 7 Inspections tests 1 8 Maintenance 2 System trim 2 1 Normal condition Trim Options Section C 1...

Страница 4: ...Page iv TOTALPAC 3 Integrated Fire Protection System OWNER S OPERATION MAINTENANCE MANUAL FM 076A 0 1C This page is left intentionally blank...

Страница 5: ...unit is identified with its unique serial number This number is located on an adhesive label inside the main door panel and is used to maintain a record in our computerized data base Have this serial...

Страница 6: ...he following diameters 1 40 mm 3 80 mm 6 150 mm 2 50 mm 4 100 mm 8 200 mm TOTALPAC 3 preaction system is supplied with groove groove deluge valve Unit with flange flange deluge valve is also available...

Страница 7: ...l inspection sequence see paragraph 1 8 of the current section 9 If the system does not operate as it should make the necessary corrections according to manuals issued or consult your distributor or F...

Страница 8: ...e priming chamber of the deluge valve A1 through the priming line which includes a normally open priming valve B1 strainer B2 restricted orifice B3 and spring loaded check valve B4 Water supply pressu...

Страница 9: ...ce for an extended period of time all water must be removed from the priming chamber trim piping water supply piping and any other trapped areas 1 6 Placing the system back in service after operation...

Страница 10: ...supply valve D1 10 When full flow develops from the flow test valve B6 CLOSE the flow test valve Verify there is no flow from drip check valve B7 when the plunger is pushed 11 FULLY OPEN the main wate...

Страница 11: ...wner is responsible for maintaining the fire protection system and devices in proper operating condition The system shall be maintained in full operation condition at all times All troubles or impairm...

Страница 12: ...se Note Numbers indicated between brackets refer to figure 1 DETAILED SYSTEM TRIM SCHEMATICS from this section and section D AIR SUPPLY 2 1 Normal condition 1 Valves a Main water supply valve D1 is OP...

Страница 13: ...7 2 B9 B2 TOTALPAC 3 Base shown without enclosure FM 061H 0 102C Trim components A1 Deluge valve B1 Priming valve N O B2 Strainer B3 1 16 1 6 mm Restricted orifice B4 Spring loaded check valve B5 Alar...

Страница 14: ...Page 8 of 8 TOTALPAC 3 B Integrated Fire Protection System Mechanical Section Non Interlock Preaction System Pneumatic Release FM 076A 0 41C This page is left intentionally blank...

Страница 15: ...sure the main drain valve D3 is completely CLOSED Return the system in service as per section B PLACING THE SYSTEM BACK IN SERVICE 5 Fully OPEN the shut off valve D4 Reset the release control panel as...

Страница 16: ...utside face of the mounting base or cabinet surface On skid unit the surface of the flange on the outlet riser will always be 6 inches above the dimension shown on the dimensional data of the system o...

Страница 17: ...dry nitrogen cylinders and piped to the air inlet port of the unit Air supply style B provides an APMD air pressure maintenance device trim factory mounted in the TOTALPAC 3 cabinet The APMD regulate...

Страница 18: ...one shot Proceed by steps 3 OPEN the main drain valve D3 and let the pressure drop until the air compressor restarts Check pressure reading on the system pressure gauge when the air compressor stops a...

Страница 19: ...valve head entirely off while the compressor is operating Ejection of valve parts could cause severe injury 3 2 Air supply Style B or C refer to figure 3 or 4 The Viking Model D 2 APMD air pressure ma...

Страница 20: ...7 kPa 35 PSI 241 kPa 25 PSI 172 kPa B or D 35 PSI 241 kPa n a n a 25 PSI 172 kPa Release pilot line C 35 PSI 241 kPa n a n a 25 PSI 172 kPa Table 3 Water pressure from 175 PSI to 250 PSI 1207 kPa to 1...

Страница 21: ...plugged with SureFire or non interlock preaction trim Pressure relief valve FM 061H 0 118C 1 CONTRACTOR S HYDROSTATIC TEST PORT system side 2 E2 E11 TO DRAIN COLLECTOR TO SPRINKLER RISER E9 Air style...

Страница 22: ...im This section replaced by Dehydrator option when used Contractor external Air or Nitrogen connection E7 E6 3 TO PNEUMATIC ACTUATOR plugged when not used FM 061H 0 119B 1 CONTRACTOR S HYDROSTATIC TES...

Страница 23: ...c actuator E14 E6 FM 061H 0 120B E5 To pneumatic release piping network E13 To optional accelerator plugged when not used Contractor external air or Nitrogen connection Air style components E5 APMD ai...

Страница 24: ...E16 E3 TO OPTIONAL ACCELERATOR plugged when not used Contractor external air or Nitrogen connection E6 3 TO PNEUMATIC ACTUATOR plugged when not used Warning The external air supply must be restricted...

Страница 25: ...t Viking P N 16854 which includes the dehydrator desiccant and mounting brackets 9 The unit is to be used on compressed air service only Operation of dehydrator The dehydrator directs the incoming air...

Страница 26: ...H 0 124B 1 From air supply Desiccant sight glass To sprinkler riser Dehydrator bowl Figure 7 Dehydrator option for air supply Style B To air Style B trim E12 Desiccant sight glass B13 E14 To drain col...

Страница 27: ...itches adjustments 1 CLOSE the isolation valve of the accelerator Refer to instructions described on Viking datasheet 122 form No 071692 To reset the accelerator device Make sure the system is properl...

Страница 28: ...ed Fire Protection System Air Supply Preaction System FM 076A 0 86C Figure 8 Accelerator Option For preaction system and pilot line release Upper chamber pressure gauge Drain plug To air line Accelera...

Страница 29: ...red to a terminal strip TBA TBC for contractor s field wiring see figure 2 and the section F ELECTRICAL SECTION 1 2 Technical data Steel enclosure Refer to section G CABINET SECTION for further detail...

Страница 30: ...l SYSTEM DEVICES OPT FM 061H 0 151A Factory Wired Air Compressor or Excess Pressure Pump Isolating Switch E15 AC POWER 120VAC 50 60Hz or 220 240VAC 50 60Hz All conduits are installed by the Contractor...

Страница 31: ...building s Central Fire Alarm Panel OPTIONAL LOS ANGELES OPTION CHICAGO OPTION NOTE All devices are shown in their normal supervisory state NOTES Use dry contacts with power limited circuits only Cont...

Страница 32: ...Page 2 of 2 TOTALPAC 3 F Integrated Fire Protection System Electrical Section Non Interlocked Preaction System Pneumatic Release FM 076A 0 61C This page is left intentionally blank...

Страница 33: ...ressure system air pressure and priming water pressure are all visible through clear Lexan windows Multiple units installation is easily achieved by jointing manifold sections together at their water...

Страница 34: ...3 41 1054 34 870 43 1105 47 1194 2 50 2 51 2 51 2 51 23 584 25 635 77 1956 4 102 8 222 11 292 13 349 3 95 2 70 2 70 8 203 11 292 27 686 38 965 42 1067 34 883 44 1130 48 1232 3 80 4 102 3 76 2 51 35 90...

Страница 35: ...m 21 530mm Figure 3 Cabinet doors clearance detail TOTALPAC 3 UNIT FM 061H 0 275A 1 B min C min A min B min TYPICAL MECHANICAL ROOM Figure 4 Knockouts details 2 Typ 65mm 9 230mm High voltage Low volta...

Страница 36: ...50mm 2 50mm 8 200mm 12 305mm 17 445mm 2 50mm Figure 6 Open drain details for multiple units refer to dimensions in table 5 TOTALPAC 3 Unit Shown Without Front Doors Drain Collector running between wal...

Страница 37: ...phosphate base Multiple units installation is easily achieved by jointing manifold sections together at their water inlets Drains outlet shall remain separate and open for each unit Refer to figure 1...

Страница 38: ...292 13 349 3 95 2 70 2 70 8 203 11 292 27 686 37 953 41 1054 34 870 43 1105 47 1194 2 50 2 51 2 51 2 51 23 584 25 635 4 102 8 222 11 292 13 349 3 95 2 70 2 70 8 203 11 292 27 659 38 965 42 1067 34 88...

Страница 39: ...40mm 25 635mm 15 380mm 2 50mm 25 635mm 15 380mm 3 80mm 37 959mm 15 380mm 4 100mm 37 959mm 15 380mm 6 150mm 48 1220mm 15 380mm Figure 9 Skid clearance detail B min A min TYPICAL MECHANICAL ROOM TOTALP...

Страница 40: ...55mm 13 350mm 2 50mm 6 150mm 11 280mm 13 350mm 2 50mm Figure 11 Open drain details for multiple units refer to dimensions in table 10 B Typical Air Gap A Water Supply Pipe Can Be Manifolded Drain Coll...

Страница 41: ...its inconveniences transportation charges or other damages suffered by anyone There are no other warranties expressed or implied with regard to the products other than those contained herein Some juri...

Страница 42: ...Page 2 of 2 TOTALPAC 3 H Integrated Fire Protection System Limited Warranty FM 076A 0 96C User Notes...

Отзывы: