background image

T

OTAL

P

AC

 

®

3

 

Page 1 of 2 

Integrated Fire Protection System

 

General Section - Non Interlock Preaction System - Pneumatic Release

 

 

FM-076A-0-21D 

1- General description 

This 

T

OTAL

P

AC

 

®

3

  integrated fire protection system by 

F

IRE

F

LEX

 Systems Inc. consists of a preaction system trim 

totally pre-assembled, pre-wired and factory tested.   All 
electrical and mechanical components of the system are 
contained in one single unit. 

Note:

  Skid units include the trim components only and must 

be wired by the installing contractor. 

The only connections required for installation are the water 
supply inlet, the water discharge outlet, the main drain, the 
pneumatic  release  inlet,  the electrical supervisory and 
alarm connections, as well as the AC power line for the 
optional air compressor.  The discharge outlet is 
connected to a fixed piping network  of automatic 
sprinklers,  in parallel to the pneumatic release  piping 
network (pilot line).  Water is the extinguishing agent. 

On system piping network and pneumatic  release  piping 
network, closed heat sensitive automatic sprinklers are 
spaced and located in accordance with recognized 
installation standards in order to detect a fire.  Only those 
sprinklers immediately over or near to fire operate, 
minimizing water damage. 

Non interlock preaction system with pneumatic release 
uses closed automatic sprinklers on the system  piping 
network, which is supervised with air pressure.    A 
pneumatic  release  piping  network is installed  in parallel 
with the system piping network and is designed to operate 
before an automatic sprinkler fuses from the system piping 
network.  Pneumatic release  system operates first and 
gives a supervisory signal. 

Non interlock  preaction system is designed so the deluge 
valve will open when either a loss of pressure  from  the 
pneumatic  release  piping  network  or from the system 
piping network occurs.  When the deluge valve opens, 
water will flow into the system  piping  network  and out of 
any open automatic  sprinklers and other opening on the 
system. 

In the event of no operation of the pneumatic release, the 
system will operate as a dry system.  In the event of 
damage to the system  piping  network  or an automatic 
sprinkler, the deluge valve will open.  Water will flow from 
any open automatic  sprinklers and any other opening in 
the system piping network. 

Note:  

Every 

T

OTAL

P

AC

 

®

3

  unit is identified with its unique 

serial number.  This number is located on an adhesive 
label inside the main door panel and is used to maintain a 
record in our computerized data base.  Have this serial 
number handy when calling for information on your unit 
(format is TOT3#### or TOTS#### for skid units). 

2- Listings and approvals 

In addition to  being fabricated under tight ISO-9001 
manufacturing and quality control procedures, your 

T

OTAL

P

AC

 

®

3

  unit has also been tested and approved by 

recognized laboratories. 

Here is the list of Listings & Approvals it meets: 

-  Underwriters Laboratories Inc. (UL): Preaction 

T

OTAL

P

AC

 

®

3

  systems are UL Listed under "Special 

System Water Control Valves -  Assembled Units, 
category # VKYL.EX4641" and "Assembled Units 
Certified for Canada, Category # VKYL7.EX4641 (c-UL)". 

-  Factory Mutual Research <FM>:  Preaction 

T

OTAL

P

AC

 

®

3

 

systems are FM Approved under the heading: "Automatic 
Water Control Valves" when installed with specific 
components. 

-  OSHPD pre-approval OSP-0341-10 (optional). 

WARNING

  Any unauthorized modification or addition made 

on-site to a factory built Listed  unit will void this Listing.  
Such modifications or additions may void the unit's 
warranty as well.  Consult your nearest 

F

IRE

F

LEX

 Systems 

authorized  distributor before proceeding with such 
modifications or additions. 

3- Applicable standards 

The 

T

OTAL

P

AC

 

®

3

 complies with the following standards: 

-  NFPA-13 Sprinkler Systems 

-  NFPA-15 Water Spray Fixed Systems 

-  NFPA-16 Foam-Water Sprinkler and Foam-Water Spray 

Systems 

-  NFPA-72 Fire Alarm Systems 

Before installation, the contractor installing the unit shall 
also be familiar with the following documents and 
standards: 

-  Applicable Local & State Building Codes 

-  Any additional requirements of the Local Authority Having 

Jurisdiction 

4- Environment 

T

OTAL

P

AC

®

3

  unit  shall be installed in a dry and clean 

location.  Verify that all equipment is properly heated and 
protected to prevent freezing and physical damage.  Refer 
to section 

 E 

 

CONTROL SECTION

 for environment data. 

The unit and its components must be kept free of foreign 
matter, freezing conditions, corrosive atmospheres, 
contaminated water supplies, and any condition that could 
impair its operation or damage the components. 

The frequency of the inspections and maintenance will 
vary depending on these environmental conditions as well 
as the condition of the air supply to the system.  The owner 
is responsible for maintaining the fire protection system 
and devices in proper operating condition.  Refer to 
section 

 B 

 

MECHANICAL SECTION

 

for maintenance 

instructions. 

Содержание TOTALPAC 3

Страница 1: ...FM 076A 0 1C Advanced Integrated Fire Protection System TOTALPAC 3 Owner s Operation and Maintenance Manual NON INTERLOCK PREACTION SYSTEM PNEUMATIC RELEASE...

Страница 2: ...ual is prohibited While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy FIREFLEX Systems Inc assumes no liability resulting from any errors or omissions...

Страница 3: ...4 System operation 1 5 Emergency instructions 1 6 Placing the system back in service after operation 1 7 Inspections tests 1 8 Maintenance 2 System trim 2 1 Normal condition Trim Options Section C 1...

Страница 4: ...Page iv TOTALPAC 3 Integrated Fire Protection System OWNER S OPERATION MAINTENANCE MANUAL FM 076A 0 1C This page is left intentionally blank...

Страница 5: ...unit is identified with its unique serial number This number is located on an adhesive label inside the main door panel and is used to maintain a record in our computerized data base Have this serial...

Страница 6: ...he following diameters 1 40 mm 3 80 mm 6 150 mm 2 50 mm 4 100 mm 8 200 mm TOTALPAC 3 preaction system is supplied with groove groove deluge valve Unit with flange flange deluge valve is also available...

Страница 7: ...l inspection sequence see paragraph 1 8 of the current section 9 If the system does not operate as it should make the necessary corrections according to manuals issued or consult your distributor or F...

Страница 8: ...e priming chamber of the deluge valve A1 through the priming line which includes a normally open priming valve B1 strainer B2 restricted orifice B3 and spring loaded check valve B4 Water supply pressu...

Страница 9: ...ce for an extended period of time all water must be removed from the priming chamber trim piping water supply piping and any other trapped areas 1 6 Placing the system back in service after operation...

Страница 10: ...supply valve D1 10 When full flow develops from the flow test valve B6 CLOSE the flow test valve Verify there is no flow from drip check valve B7 when the plunger is pushed 11 FULLY OPEN the main wate...

Страница 11: ...wner is responsible for maintaining the fire protection system and devices in proper operating condition The system shall be maintained in full operation condition at all times All troubles or impairm...

Страница 12: ...se Note Numbers indicated between brackets refer to figure 1 DETAILED SYSTEM TRIM SCHEMATICS from this section and section D AIR SUPPLY 2 1 Normal condition 1 Valves a Main water supply valve D1 is OP...

Страница 13: ...7 2 B9 B2 TOTALPAC 3 Base shown without enclosure FM 061H 0 102C Trim components A1 Deluge valve B1 Priming valve N O B2 Strainer B3 1 16 1 6 mm Restricted orifice B4 Spring loaded check valve B5 Alar...

Страница 14: ...Page 8 of 8 TOTALPAC 3 B Integrated Fire Protection System Mechanical Section Non Interlock Preaction System Pneumatic Release FM 076A 0 41C This page is left intentionally blank...

Страница 15: ...sure the main drain valve D3 is completely CLOSED Return the system in service as per section B PLACING THE SYSTEM BACK IN SERVICE 5 Fully OPEN the shut off valve D4 Reset the release control panel as...

Страница 16: ...utside face of the mounting base or cabinet surface On skid unit the surface of the flange on the outlet riser will always be 6 inches above the dimension shown on the dimensional data of the system o...

Страница 17: ...dry nitrogen cylinders and piped to the air inlet port of the unit Air supply style B provides an APMD air pressure maintenance device trim factory mounted in the TOTALPAC 3 cabinet The APMD regulate...

Страница 18: ...one shot Proceed by steps 3 OPEN the main drain valve D3 and let the pressure drop until the air compressor restarts Check pressure reading on the system pressure gauge when the air compressor stops a...

Страница 19: ...valve head entirely off while the compressor is operating Ejection of valve parts could cause severe injury 3 2 Air supply Style B or C refer to figure 3 or 4 The Viking Model D 2 APMD air pressure ma...

Страница 20: ...7 kPa 35 PSI 241 kPa 25 PSI 172 kPa B or D 35 PSI 241 kPa n a n a 25 PSI 172 kPa Release pilot line C 35 PSI 241 kPa n a n a 25 PSI 172 kPa Table 3 Water pressure from 175 PSI to 250 PSI 1207 kPa to 1...

Страница 21: ...plugged with SureFire or non interlock preaction trim Pressure relief valve FM 061H 0 118C 1 CONTRACTOR S HYDROSTATIC TEST PORT system side 2 E2 E11 TO DRAIN COLLECTOR TO SPRINKLER RISER E9 Air style...

Страница 22: ...im This section replaced by Dehydrator option when used Contractor external Air or Nitrogen connection E7 E6 3 TO PNEUMATIC ACTUATOR plugged when not used FM 061H 0 119B 1 CONTRACTOR S HYDROSTATIC TES...

Страница 23: ...c actuator E14 E6 FM 061H 0 120B E5 To pneumatic release piping network E13 To optional accelerator plugged when not used Contractor external air or Nitrogen connection Air style components E5 APMD ai...

Страница 24: ...E16 E3 TO OPTIONAL ACCELERATOR plugged when not used Contractor external air or Nitrogen connection E6 3 TO PNEUMATIC ACTUATOR plugged when not used Warning The external air supply must be restricted...

Страница 25: ...t Viking P N 16854 which includes the dehydrator desiccant and mounting brackets 9 The unit is to be used on compressed air service only Operation of dehydrator The dehydrator directs the incoming air...

Страница 26: ...H 0 124B 1 From air supply Desiccant sight glass To sprinkler riser Dehydrator bowl Figure 7 Dehydrator option for air supply Style B To air Style B trim E12 Desiccant sight glass B13 E14 To drain col...

Страница 27: ...itches adjustments 1 CLOSE the isolation valve of the accelerator Refer to instructions described on Viking datasheet 122 form No 071692 To reset the accelerator device Make sure the system is properl...

Страница 28: ...ed Fire Protection System Air Supply Preaction System FM 076A 0 86C Figure 8 Accelerator Option For preaction system and pilot line release Upper chamber pressure gauge Drain plug To air line Accelera...

Страница 29: ...red to a terminal strip TBA TBC for contractor s field wiring see figure 2 and the section F ELECTRICAL SECTION 1 2 Technical data Steel enclosure Refer to section G CABINET SECTION for further detail...

Страница 30: ...l SYSTEM DEVICES OPT FM 061H 0 151A Factory Wired Air Compressor or Excess Pressure Pump Isolating Switch E15 AC POWER 120VAC 50 60Hz or 220 240VAC 50 60Hz All conduits are installed by the Contractor...

Страница 31: ...building s Central Fire Alarm Panel OPTIONAL LOS ANGELES OPTION CHICAGO OPTION NOTE All devices are shown in their normal supervisory state NOTES Use dry contacts with power limited circuits only Cont...

Страница 32: ...Page 2 of 2 TOTALPAC 3 F Integrated Fire Protection System Electrical Section Non Interlocked Preaction System Pneumatic Release FM 076A 0 61C This page is left intentionally blank...

Страница 33: ...ressure system air pressure and priming water pressure are all visible through clear Lexan windows Multiple units installation is easily achieved by jointing manifold sections together at their water...

Страница 34: ...3 41 1054 34 870 43 1105 47 1194 2 50 2 51 2 51 2 51 23 584 25 635 77 1956 4 102 8 222 11 292 13 349 3 95 2 70 2 70 8 203 11 292 27 686 38 965 42 1067 34 883 44 1130 48 1232 3 80 4 102 3 76 2 51 35 90...

Страница 35: ...m 21 530mm Figure 3 Cabinet doors clearance detail TOTALPAC 3 UNIT FM 061H 0 275A 1 B min C min A min B min TYPICAL MECHANICAL ROOM Figure 4 Knockouts details 2 Typ 65mm 9 230mm High voltage Low volta...

Страница 36: ...50mm 2 50mm 8 200mm 12 305mm 17 445mm 2 50mm Figure 6 Open drain details for multiple units refer to dimensions in table 5 TOTALPAC 3 Unit Shown Without Front Doors Drain Collector running between wal...

Страница 37: ...phosphate base Multiple units installation is easily achieved by jointing manifold sections together at their water inlets Drains outlet shall remain separate and open for each unit Refer to figure 1...

Страница 38: ...292 13 349 3 95 2 70 2 70 8 203 11 292 27 686 37 953 41 1054 34 870 43 1105 47 1194 2 50 2 51 2 51 2 51 23 584 25 635 4 102 8 222 11 292 13 349 3 95 2 70 2 70 8 203 11 292 27 659 38 965 42 1067 34 88...

Страница 39: ...40mm 25 635mm 15 380mm 2 50mm 25 635mm 15 380mm 3 80mm 37 959mm 15 380mm 4 100mm 37 959mm 15 380mm 6 150mm 48 1220mm 15 380mm Figure 9 Skid clearance detail B min A min TYPICAL MECHANICAL ROOM TOTALP...

Страница 40: ...55mm 13 350mm 2 50mm 6 150mm 11 280mm 13 350mm 2 50mm Figure 11 Open drain details for multiple units refer to dimensions in table 10 B Typical Air Gap A Water Supply Pipe Can Be Manifolded Drain Coll...

Страница 41: ...its inconveniences transportation charges or other damages suffered by anyone There are no other warranties expressed or implied with regard to the products other than those contained herein Some juri...

Страница 42: ...Page 2 of 2 TOTALPAC 3 H Integrated Fire Protection System Limited Warranty FM 076A 0 96C User Notes...

Отзывы: