T
OTAL
P
AC
®
3
Page 1 of 8
Integrated Fire Protection System
G
Dimensional Data & Cabinet
FM-076A-0-110A
1- Cabinet for TotalPac
®
3 unit
The
TotalPac
®
3
unit cabinet is made of sturdy 14 gauge
steel. Bottom base is made of 11 gauge and 7 gauge steel.
Cabinet is available in four (4) sizes:
23" x 25" x 77" (584mm x 640mm x 1960mm) for 1½"
(40mm) or 2" (50mm) system
35¾" x 25" x 77" (908mm x 640mm x 1960mm) for 3"
(80mm) or 4" (100mm) system
46" x 25" x 77" (1170mm x 640mm x 1960mm) for 6"
(150mm) system
54" x 31" x 81" (1370mm x 790mm x 2060mm) for 8"
(200mm) system
All external and internal surfaces are rust proof coated, inside
and outside, with fire red, oven baked polyester powder on
phosphate base. Cabinet is provided with two doors, both
provided with a neoprene gasket to absorb vibrations.
The cabinet unit is pre-assembled, pre-wired and factory
tested under ISO-9001 specifications. Each cabinet door is
provided with hinges that can be disassembled on site to
remove the door assemblies for servicing.
Note
Ground wire has to be disconnected prior to remove a
door. It must be reconnected once the door is reinstalled.
Gauges to indicate water supply pressure, system air
pressure and priming water pressure are all visible through
clear Lexan windows.
Multiple units installation is easily achieved by jointing
manifold sections together at their water inlets. Drains outlet
shall remain separate and open for each unit. Refer to
figure 6
OPEN DRAIN DETAILS FOR MULTIPLE UNITS
.
IMPORTANT !
TotalPac
®
3
unit is NOT designed to be
installed where it will be subjected to outdoors and/or
freezing conditions. Refer to paragraph 3
ENVIRONMENT
in
section
A
GENERAL DESCRIPTION
for additional details.
Subjecting the unit to conditions outside these limitations
might hamper the normal operation of the system.
A field wiring electrical junctions box is integrated within the
cabinet for connection of all electrical components in the trim
to remotely controlled release control panel. Pressure
switches, supervisory switches, etc. are all factory wired to a
terminal strip (TBA and optional TBC) for contractor's field
wiring. Terminal strip TBB is required for AC power
connection to air compressor (when provided). Refer to
section
F
ELECTRICAL
for additional information.
Table 1 - System weight in cabinet
System size
Weight
1
1½" (40mm)
450 lb (204 kg)
2" (50mm)
455 lb (206 kg)
3" (80mm)
655 lb (297 kg)
4" (100mm)
730 lb (331 kg)
6" (150mm)
1080 lb (490 kg)
8" (200mm)
1445 lb (655 kg)
(1) Without air compressor.