Integrated Fire Protection System
General Section - Non Interlock Preaction System - Pneumatic Release
FM-076A-0-21D
5- Features
The
T
OTAL
P
AC
®
3
unit is superior to many other products
which are actually available on the fire protection market.
It is manufactured by
F
IRE
F
LEX
Systems Inc. which has
developed and introduced the concept of integrated fire
protection systems.
Main features are:
Trouble free design for safe and easy application
Available in 6 sizes from 1½" (40 mm) to 8" (200 mm)
diameter
Uses the Viking deluge valve
Skid version available
Compact, aesthetic and easy to move
User-friendly standardized owner's manual with every
unit
Unique serial number on every unit
Uses only c-UL-us Listed and FM Approved components
Designed in accordance with NFPA Standards
Trim is fully assembled and tested at the factory
All trims are galvanized steel, Listed and Approved for
250 PSI (1724 kPa) service maximum
Quick connections to water supply and drain on both
sides, and sprinkler riser on top of unit, all available with
grooved end or flanged fittings
No open drain cup inside unit
Sturdy 14 gauge steel cabinet or skid, painted fire red
with oven baked polyester powder on phosphate base
Textured rust proof finish
Neoprene gasket on all doors to eliminate vibrations
Separate unlocked access hatch to emergency manual
release
Key-alike locks on all cabinet doors
Manufactured under ISO-9001 quality control procedures
6- Configuration description
T
OTAL
P
AC
®
3
preaction system is built around the Viking
trim using straight through deluge valve model F-1
(model F-2 is the Halar
®
coated version for use in
corrosive environments).
The valve is rated up to a maximum of 250 PSI WWP
(1724 kPa) and is available in the following diameters:
1½" (40 mm)
3" (80 mm)
6" (150 mm)
2" (50 mm)
4" (100 mm)
8" (200 mm)
T
OTAL
P
AC
®
3
preaction system is supplied with groove/
groove deluge valve. Unit with flange/flange deluge valve
is also available on request.
6.1 Non interlock preaction system
Both pneumatic release piping network and system piping
network are pressurized with air or nitrogen gas. The
preaction system uses the Viking deluge valve which
opens either by the releasing of the pneumatic release
piping network, the fusing of an automatic sprinkler in the
system piping network, or anytime the handle of the
emergency release valve is pulled.
If the pneumatic release piping network releases due to
fire, damage or malfunction, the deluge valve will open but
the water will be trapped inside the system piping network
until an automatic sprinkler fuses, flowing water.
If the pneumatic release piping network does not operate,
the preaction system will operate as a dry pipe system. If
the system piping network is broken or an automatic
sprinkler fuses, the deluge valve opens, flowing water.
7- System release
7.1 Pneumatic release
Preaction system with pneumatic release requires a
pneumatic release piping network equipped with
thermostatic (rate of rise) releases, and/or fixed
temperature releases, and/or pilot heads. Release trim for
the deluge valve requires a pneumatic actuator normally
held closed by the pressure maintained in the pneumatic
release piping network and the system piping network.
In fire condition, when the pneumatic release piping
network releases, or when an automatic sprinkler fuses on
the system piping network, the deluge valve opens. If
automatic sprinklers are still closed, water will be trapped
inside the system piping network until an automatic
sprinkler fuses. If any automatic sprinkler fuses, water will
flow from the preaction system through opened sprinklers.
Automatic sprinkler must open to allow water to flow from
the preaction system.