background image

T

OTAL

P

AC

 

®

3

 

Page 11 of 12 

Integrated Fire Protection System

 

Air Supply - Preaction System

 

 

FM-076A-0-86C 

4.2  Accelerator 

The  Viking  Model E-1  accelerator  is  a  quick-opening 
device  featuring  automatic  reset.    The  Viking  Model E-1 
accelerator  is  used  without  the  anti-flood  device  to  speed 
the  action  of  a  pneumatic  release  system  on  preaction 
system. 

Operation 

The Viking Model E-1 accelerator operates on the principle 
of  unbalanced  pressures.    As  the  accelerator  is 
pressurized, air enters the inlet chamber, goes through the 
screen filter into the middle chamber and through an orifice 
into  the  lower  chamber.    From  the  middle  chamber,  air 
slowly  enters  the  upper  chamber  through a  filtered  orifice 
restriction in the cover diaphragm. 
In the SET position, the system air pressure is the same in 
all  chambers.    When  a  sprinkler  or  release  device 
operates,  the  pressure  in  the  middle  and  lower  chambers 
is reduced at the same rate as the system pressure.  The 
orifice  restriction  in  the  cover  diaphragm  restricts  the  air 
flow  from  the  upper  chamber,  temporarily  causing  higher 
pressure in the upper chamber. 
The pressure differential forces the cover diaphragm down, 
pushing  the  actuator  rod  down.    This  action  vents  the 
pressure  from  the  lower  chamber  to  the  outlet  vent, 
allowing residual pressure in the inlet chamber to force the 
clapper  diaphragm  open.    After  the  clapper  diaphragm 
opens,  any  pressure  remaining  in  the  inlet  chamber  and 
associated piping is vented to atmosphere. 
On  a  pneumatic  release  system,  when  the  accelerator 
operates,  the  outlet  pressure  is  vented  to  atmosphere, 
speeding the release system operation. 

To enable the accelerator device 

  1. 

OPEN

 the isolation valve of the accelerator. 

CAUTION !

  The  system  air  pressure  should  be  higher  or 

equal  to  the  upper  chamber  of  the  accelerator  prior  to 
opening the main water supply valve 

(D1)

Note :

  Ensure  that  the  isolation  valve  of  the  accelerator  is 

open in normal supervisory mode. 

To isolate the accelerator device 

This  operation  can  be  necessary  in  order  to  verify  the 
pressure  adjustments  or  to  allow  the  pressure  switches 
adjustments. 

  1. 

CLOSE

 the isolation valve of the accelerator. 

Refer  to  instructions  described  on  Viking  datasheet  #122 
(form No. 071692). 

To reset the accelerator device 

Make  sure  the  system  is  properly  drained  and  reset.  
Observe  the  upper  chamber  pressure  of  the  accelerator.  
The  gauge  must  read  zero  before  the  accelerator  will 
automatically  reset.    It  may  be  necessary  to  loosen, 
remove and re-install the accelerator air gauge (using the 
appropriate wrench) to vent trapped air pressure from the 
upper chamber, even when the gauge indicates zero if the 
air supply is on while performing the reset. 
Make  sure  system  is  pressurized  according  to 
recommended settings. 

WARNING

  Do not exceed 60 PSI (414 kPa). 

After every operation, and each time water is allowed to 
enter the system 

  1.  Inspect the interior of the accelerator for the presence of 

water.    Dampness  or  condensation  may  indicate  that 
the air supply is not being dried adequately.  If water is 
allowed  to  enter  the  middle  or  upper  chamber  of  the 
accelerator,  it  may  contaminate  the  accelerator  orifices 
and prevent it from operating properly. 

  2.  Remove  the  1/2"-NPT  (15 mm)  plug  from  the  base  of 

the  accelerator.    If  water  or  dampness  is  present,  the 
accelerator  must  be  disassembled,  cleaned  and  dried.  
For  more  information  about  this  procedure,  refer  to 
Viking datasheet #122 (form No. 071692). 

  3.  Weekly  inspection  is  recommended  unless  system  is 

provided  with  low  air  alarm,  then  monthly  inspection 
may be adequate. 

  4.  Check  the  upper  chamber  pressure  of  the  accelerator.  

The  air  pressure  should  be  equal  to  the  air  pressure 
maintained in the system on which it is installed. 

 

  A  difference in  pressure  other  then  slight  variation  due 

to  gauge  calibration  may  indicate  gauge  malfunction, 
plugged  accelerator  orifices  and/or  filters,  or  other 
maintenance is required. 

Note :  

Standard  tolerance  allowance  in  pressure  gauge 

calibration  may  result  in  a  slight  variation  when  pressure 
readings of any two gauges are compared. 

  5.  Verify  that  all  other  trim  valves  are  in  their  normal 

operating position. 

  6.  Check for signs of mechanical damage and/or corrosive 

activity.    If  detected,  perform  maintenance  as  required 
or, if necessary, replace device. 

  7.  Verify that the main water supply valve 

(D1)

 is 

OPEN

 and 

secure and that the by-pass valve 

(1)

 is 

OPEN

 

Содержание TOTALPAC 3

Страница 1: ...FM 076A 0 1C Advanced Integrated Fire Protection System TOTALPAC 3 Owner s Operation and Maintenance Manual NON INTERLOCK PREACTION SYSTEM PNEUMATIC RELEASE...

Страница 2: ...ual is prohibited While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy FIREFLEX Systems Inc assumes no liability resulting from any errors or omissions...

Страница 3: ...4 System operation 1 5 Emergency instructions 1 6 Placing the system back in service after operation 1 7 Inspections tests 1 8 Maintenance 2 System trim 2 1 Normal condition Trim Options Section C 1...

Страница 4: ...Page iv TOTALPAC 3 Integrated Fire Protection System OWNER S OPERATION MAINTENANCE MANUAL FM 076A 0 1C This page is left intentionally blank...

Страница 5: ...unit is identified with its unique serial number This number is located on an adhesive label inside the main door panel and is used to maintain a record in our computerized data base Have this serial...

Страница 6: ...he following diameters 1 40 mm 3 80 mm 6 150 mm 2 50 mm 4 100 mm 8 200 mm TOTALPAC 3 preaction system is supplied with groove groove deluge valve Unit with flange flange deluge valve is also available...

Страница 7: ...l inspection sequence see paragraph 1 8 of the current section 9 If the system does not operate as it should make the necessary corrections according to manuals issued or consult your distributor or F...

Страница 8: ...e priming chamber of the deluge valve A1 through the priming line which includes a normally open priming valve B1 strainer B2 restricted orifice B3 and spring loaded check valve B4 Water supply pressu...

Страница 9: ...ce for an extended period of time all water must be removed from the priming chamber trim piping water supply piping and any other trapped areas 1 6 Placing the system back in service after operation...

Страница 10: ...supply valve D1 10 When full flow develops from the flow test valve B6 CLOSE the flow test valve Verify there is no flow from drip check valve B7 when the plunger is pushed 11 FULLY OPEN the main wate...

Страница 11: ...wner is responsible for maintaining the fire protection system and devices in proper operating condition The system shall be maintained in full operation condition at all times All troubles or impairm...

Страница 12: ...se Note Numbers indicated between brackets refer to figure 1 DETAILED SYSTEM TRIM SCHEMATICS from this section and section D AIR SUPPLY 2 1 Normal condition 1 Valves a Main water supply valve D1 is OP...

Страница 13: ...7 2 B9 B2 TOTALPAC 3 Base shown without enclosure FM 061H 0 102C Trim components A1 Deluge valve B1 Priming valve N O B2 Strainer B3 1 16 1 6 mm Restricted orifice B4 Spring loaded check valve B5 Alar...

Страница 14: ...Page 8 of 8 TOTALPAC 3 B Integrated Fire Protection System Mechanical Section Non Interlock Preaction System Pneumatic Release FM 076A 0 41C This page is left intentionally blank...

Страница 15: ...sure the main drain valve D3 is completely CLOSED Return the system in service as per section B PLACING THE SYSTEM BACK IN SERVICE 5 Fully OPEN the shut off valve D4 Reset the release control panel as...

Страница 16: ...utside face of the mounting base or cabinet surface On skid unit the surface of the flange on the outlet riser will always be 6 inches above the dimension shown on the dimensional data of the system o...

Страница 17: ...dry nitrogen cylinders and piped to the air inlet port of the unit Air supply style B provides an APMD air pressure maintenance device trim factory mounted in the TOTALPAC 3 cabinet The APMD regulate...

Страница 18: ...one shot Proceed by steps 3 OPEN the main drain valve D3 and let the pressure drop until the air compressor restarts Check pressure reading on the system pressure gauge when the air compressor stops a...

Страница 19: ...valve head entirely off while the compressor is operating Ejection of valve parts could cause severe injury 3 2 Air supply Style B or C refer to figure 3 or 4 The Viking Model D 2 APMD air pressure ma...

Страница 20: ...7 kPa 35 PSI 241 kPa 25 PSI 172 kPa B or D 35 PSI 241 kPa n a n a 25 PSI 172 kPa Release pilot line C 35 PSI 241 kPa n a n a 25 PSI 172 kPa Table 3 Water pressure from 175 PSI to 250 PSI 1207 kPa to 1...

Страница 21: ...plugged with SureFire or non interlock preaction trim Pressure relief valve FM 061H 0 118C 1 CONTRACTOR S HYDROSTATIC TEST PORT system side 2 E2 E11 TO DRAIN COLLECTOR TO SPRINKLER RISER E9 Air style...

Страница 22: ...im This section replaced by Dehydrator option when used Contractor external Air or Nitrogen connection E7 E6 3 TO PNEUMATIC ACTUATOR plugged when not used FM 061H 0 119B 1 CONTRACTOR S HYDROSTATIC TES...

Страница 23: ...c actuator E14 E6 FM 061H 0 120B E5 To pneumatic release piping network E13 To optional accelerator plugged when not used Contractor external air or Nitrogen connection Air style components E5 APMD ai...

Страница 24: ...E16 E3 TO OPTIONAL ACCELERATOR plugged when not used Contractor external air or Nitrogen connection E6 3 TO PNEUMATIC ACTUATOR plugged when not used Warning The external air supply must be restricted...

Страница 25: ...t Viking P N 16854 which includes the dehydrator desiccant and mounting brackets 9 The unit is to be used on compressed air service only Operation of dehydrator The dehydrator directs the incoming air...

Страница 26: ...H 0 124B 1 From air supply Desiccant sight glass To sprinkler riser Dehydrator bowl Figure 7 Dehydrator option for air supply Style B To air Style B trim E12 Desiccant sight glass B13 E14 To drain col...

Страница 27: ...itches adjustments 1 CLOSE the isolation valve of the accelerator Refer to instructions described on Viking datasheet 122 form No 071692 To reset the accelerator device Make sure the system is properl...

Страница 28: ...ed Fire Protection System Air Supply Preaction System FM 076A 0 86C Figure 8 Accelerator Option For preaction system and pilot line release Upper chamber pressure gauge Drain plug To air line Accelera...

Страница 29: ...red to a terminal strip TBA TBC for contractor s field wiring see figure 2 and the section F ELECTRICAL SECTION 1 2 Technical data Steel enclosure Refer to section G CABINET SECTION for further detail...

Страница 30: ...l SYSTEM DEVICES OPT FM 061H 0 151A Factory Wired Air Compressor or Excess Pressure Pump Isolating Switch E15 AC POWER 120VAC 50 60Hz or 220 240VAC 50 60Hz All conduits are installed by the Contractor...

Страница 31: ...building s Central Fire Alarm Panel OPTIONAL LOS ANGELES OPTION CHICAGO OPTION NOTE All devices are shown in their normal supervisory state NOTES Use dry contacts with power limited circuits only Cont...

Страница 32: ...Page 2 of 2 TOTALPAC 3 F Integrated Fire Protection System Electrical Section Non Interlocked Preaction System Pneumatic Release FM 076A 0 61C This page is left intentionally blank...

Страница 33: ...ressure system air pressure and priming water pressure are all visible through clear Lexan windows Multiple units installation is easily achieved by jointing manifold sections together at their water...

Страница 34: ...3 41 1054 34 870 43 1105 47 1194 2 50 2 51 2 51 2 51 23 584 25 635 77 1956 4 102 8 222 11 292 13 349 3 95 2 70 2 70 8 203 11 292 27 686 38 965 42 1067 34 883 44 1130 48 1232 3 80 4 102 3 76 2 51 35 90...

Страница 35: ...m 21 530mm Figure 3 Cabinet doors clearance detail TOTALPAC 3 UNIT FM 061H 0 275A 1 B min C min A min B min TYPICAL MECHANICAL ROOM Figure 4 Knockouts details 2 Typ 65mm 9 230mm High voltage Low volta...

Страница 36: ...50mm 2 50mm 8 200mm 12 305mm 17 445mm 2 50mm Figure 6 Open drain details for multiple units refer to dimensions in table 5 TOTALPAC 3 Unit Shown Without Front Doors Drain Collector running between wal...

Страница 37: ...phosphate base Multiple units installation is easily achieved by jointing manifold sections together at their water inlets Drains outlet shall remain separate and open for each unit Refer to figure 1...

Страница 38: ...292 13 349 3 95 2 70 2 70 8 203 11 292 27 686 37 953 41 1054 34 870 43 1105 47 1194 2 50 2 51 2 51 2 51 23 584 25 635 4 102 8 222 11 292 13 349 3 95 2 70 2 70 8 203 11 292 27 659 38 965 42 1067 34 88...

Страница 39: ...40mm 25 635mm 15 380mm 2 50mm 25 635mm 15 380mm 3 80mm 37 959mm 15 380mm 4 100mm 37 959mm 15 380mm 6 150mm 48 1220mm 15 380mm Figure 9 Skid clearance detail B min A min TYPICAL MECHANICAL ROOM TOTALP...

Страница 40: ...55mm 13 350mm 2 50mm 6 150mm 11 280mm 13 350mm 2 50mm Figure 11 Open drain details for multiple units refer to dimensions in table 10 B Typical Air Gap A Water Supply Pipe Can Be Manifolded Drain Coll...

Страница 41: ...its inconveniences transportation charges or other damages suffered by anyone There are no other warranties expressed or implied with regard to the products other than those contained herein Some juri...

Страница 42: ...Page 2 of 2 TOTALPAC 3 H Integrated Fire Protection System Limited Warranty FM 076A 0 96C User Notes...

Отзывы: