Page 8 of 8
T
OTAL
P
AC
®
3
G
Integrated Fire Protection System
Dimensional Data & Cabinet
FM-076A-0-110A
Figure 10 - Open drain details for single unit
Air Gap
A
Single Unit Detail
Water Supply Pipe
B
Unit Drain Pipe
(dia. = C)
4'' (100mm)
min.
Drain Pipe (pipe diameter
per drain flow calculation)
FM-061H-0-137A
Table 10 - Manifold dimensions
Unit size
A
B
C
1½"
(40mm)
8¾"
(222mm)
13¾"
(350mm)
2"
(50mm)
2"
(50mm)
8¾"
(222mm)
13¾"
(350mm)
2"
(50mm)
3"
(80mm)
10"
(255mm)
13¾"
(350mm)
2"
(50mm)
4"
(100mm)
10"
(255mm)
13¾"
(350mm)
2"
(50mm)
6"
(150mm)
11"
(280mm)
13¾"
(350mm)
2"
(50mm)
Figure 11 - Open drain details for multiple units
(refer to dimensions in table 10)
B
Typical Air Gap
A
Water Supply Pipe
(Can Be Manifolded)
Drain Collector running
between wall and units
(pipe diameter per
drain flow calculations)
Unit Drain Pipe
(dia. = C)
DO NOT MANIFOLD !
FM-061H-0-138A
4'' (100mm) min.
Multiple Units Detail
12'' min.
Notes:
1. Water supply and drain pipes can be connected on either sides of skid.
2. All pipes and fittings should meet applicable codes.
3. Actual drain collector diameter shall be determined with detailed hydraulic calculations and is the responsibility of the system
designer.