FIRECLASS Prescient III
2.2 General Description
Application, Installation & Commissioning Doc. version 2
9
5
Two fully monitored Actuator circuits.
6
Repeater outputs for:
– Zone 1 Fire Detected
– Zone 2 Fire Detected
– Auxiliary Zone Fire Detected
– Manual Release Activated
– System Disabled
– Isolation Valve Closed
– Isolation Valve Abnormal
– Emergency Hold Activated (configurable for auto
& manual mode)
– Emergency Abort Activated (configurable for
manual only mode)
7
Two Auxiliary 24 V DC supply outputs.
8
RS485 communication link to drive external Status
Lamp Units.
9
Fully monitored inputs for:
– Gas Discharged Pressure Switch
– Gas Low Pressure Switch
– Gas Isolation Valve
– Gas Trapped In Manifold
– Emergency Hold Switch
– Emergency Abort Switch
– Manual Only (Lock-Off) Switch
– Remote Controls Switches (Sound alarms,
Silence Alarms, Reset)
10 Fully Monitored Outputs (Configurable for Volt-Free
operation) for:
– First Stage Shutdown
– Second Stage Shutdown
– Third Stage Shutdown
– Auxiliary Fire Signal
– Auxiliary Fault Signal
– Gas Released Signal
11 Volt-Free Relay Contacts for Auxiliary Equipment
Reset
12 Terminals for Internal Standby Batteries
13 Site Configuration DIL Switches
14 Fault indication LEDs
15 Internal Buzzer
2.2.1
Alternative Language Inserts
The panel is available in a variety of languages but it is
also possible for the installer to print inserts with their
chosen language.
A template document in English is available on the prod-
uct CDROM. This can be edited and printed on to a grey
card as detailed in the template document.
The inserts can then be cut out and inserted into the dis-
play board.
Notes:
1
Zone Location inserts are supplied blank and are
therefore not included in the template.
2
DO NOT remove or alter the Model Name/Number
or approvals information.