Application, Installation & Commissioning Doc. version 2
5.4 Detector Compatibility
FIRECLASS Prescient III
632H
90 deg c heat detector
17
4” BASE
Series 600 base
-
6” BASE
Series 600 base
-
Zettler/Thorn/
Wormald
MR613T
High performance optical detector
24
MR613
Optical detector
24
MD613
ROR heat detector
24
MF613
90 deg c heat detector
24
MD623
60 deg c heat detector
24
MU601
Carbon Monoxide Detector
24
KAC
WR2072-470
Manual call point
32
WR2061-120-470
Manual call point
32
Fulleon
CX
Manual call point
32
CXL
Manual call point
32
Manufacturer
Part No.
Description
Max. per zone
(** See notes)
Table 13: Detector Compatibility (cont.)
Notes
The following points are to be noted:
Detector quantities are based on the use of
a 22
u
F capacitor as the end-of-line device,
except for intrinsically safe devices, in
which case the EOL is a 10 kΩ resistor.
If the DIL switch option ‘3.9 kΩ EOL’ is
selected, then the maximum number of
detectors per zone will be reduced. In this
case the maximum detector current in
standby should not exceed 2.3 mA. As a
general rule the quantities shown above
should be halved.
Detector models not listed above may be
compatible if electrically similar to the
above devices. Consult your supplier for
advice.
All break glass units (call points) must have
a resistor fitted to them to produce an
alarm condition on the panel. Any value
between 100 Ohm and 680 Ohm is
acceptable. Please check with your sup-
plier if you are not sure.
It is not permitted to connect more than 32
detectors to any zone. (The Manual
Release circuit is not a detection zone and
therefore should only have MCPs fitted).