current rated sounders not exceeding a maximum
current of 2 A.
The possibility of the configuration of extinction,
although present in the FC410SNM module, is not
available for FC503 and FC506 control panel.
Note:
The extinction configuration is not
available in the FC503 or FC506 modules.
FC410TSM Door control module
The FC410TSM door control module closes a fire
door in case of alarm or fault. The door is normally
kept open by electromagnets. The door control
module disconnects the electromagnets from
power supply in order to allow the door to close.
The FC410TSM has a relay changeover output and
a monitored input. The FC410TSM contains an
integrated line isolator and self-monitoring circuits
(monitoring of communication with a panel, loop
power monitoring), which enables the fire door
to be closed when communication with a panel is
lost for longer than 45 s (±5 s) or the loop power
drops below Umin=19 V for more than 15 s (± 5 s). In
addition, the FC410TSM monitors the external 24 V
supply.
FC410DDM Universal fire and
gas detector module
The FC410DDM provides the ability to connect and
interface 2 zones of 20 VDC 2-wire conventional
fire detectors, or two 4-20 mA signaling sensors, to
the FireClass fire alarm controller. The FC410DDM
monitors the status of the detectors and the wiring
to the detectors and signals detector and wiring
status back to the controller. The conventional
detector circuits can be configured to monitor 1 or 2
Class B spur circuits. The 4-20 mA signaling sensors
may be one of two types:
•
Current sinking
•
Current sourcing
FC410QMO Quad monitored
output module
The FC410QMO module comprises of four relays
with selectable wiring supervision.
The output wiring is monitored for any short or
open circuit. Spur and Loop configurations are
supported.
The module has an integral loop isolator. If it
activates, a yellow LED illuminates. The activation
remains in place until the short is removed.
FC410QRM Quad relay module
The module provides four voltage free relay
changeover outputs. The outputs are monitored
with parallel contacts of the relays. Connect
the outputs to an auxiliary voltage source to
monitor its voltage. Additionally, all the outputs are
configurable to the high voltage relay (HVR) mode,
which allows you to connect up to four HVR800
modules for switching. For example, 240 V loads
galvanically isolated.
The module has an integral loop isolator. If the
integral loop isolator activates, a yellow LED
illuminates. The activation remains in place until the
short is removed.
Maximum relay current: 2 A
Maximum relay voltage: 30 V
FC410QIO Quad input output
module
The module provides four monitored digital
inputs and four potential free relay changeover
outputs.The outputs are monitored with parallel
contacts of the relays. The outputs can be
connected to an auxiliary voltage source and
the voltage can be monitored. Additionally, all
the outputs can be connected to the HVR800, for
switching high power galvanic isolated loads. For
more details, refer to the HVR800 documentation.
The module has an integral loop isolator. If this
activates, a yellow LED illuminates. The activation
remains in place until the short is removed. The
digital input monitoring and isolator functions are
both configurable.
Maximum relay current: 2 A
Maximum relay voltage: 30 V
FC440SB Addressable Base
Sounder
The visual indicating device (VID) sounder-beacons
and sounders are loop powered units driven from
an addressable controller panel. Set the tone and
volume in the FireClass FC500 (FC501_FC503_FC506)
Console.
Selectable flash rates are:
1. 1 Hz (flash every second)
2. 0.5 Hz (flash every 2 seconds)
The visual indicating device sounder-beacons are
available in ceiling and wall mounted variants,
FC503 and FC506 Addressable Fire Control Panels
79
Johnson Controls - CONFIDENTIAL