Figure 38: Language strings download during panel run time
Callout
Description
1
Choice of language
9 Key- Restore default
Use the Restore default option from the
PROGRAMMING menu to restore the default setting.
Use the
9
Key to select restore default. See Figure
26,0
Figure 39: Restore Default
In this phase, the keypad and keys have the
following functions:
Alphanumeric keypad
No function is related to the alphanumeric keypad.
Cursor keys
No functions are related to the
Up
,
Down
,
Right
, or
Left
keys.
ESC and ENTER keys
Table 54: ESC and ENTER key function in restore
default
Key
Function
ESC
Use to cancel the operation or
return to the previous screen
ENTER
Use to start the default settings
restore procedure
Note:
If the motherboard of the panel
is connected with a FC500IP module, the
procedure to restore factory Default (
9
key)
has no effect. To restore the FC500IP module to
factory default, refer to the procedure for the
FireClass FC500 (FC501_FC503_FC506) Console
software.
FC500 repeater address
After the FC503 or FC506 control panels have been
connected, the FC500 repeater verifies the presence
of the address and its conformity at the first start-
up. If the address is correct, the repeater starts to
FC503 and FC506 Addressable Fire Control Panels
61